HomeMy WebLinkAboutVWC CONV STORE26 E1.2 10-14-2021SCALE: 1/4" = 1'-0"
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION220V
GFI
GFI
GFI
GFI
HIGH FOR SIGN AND/OR SHOW WINDOWS
POS
POS
DED
DED
DED
GFI
GFI
GFI
GFI
DRAWING NOTES:
1.
2.
3.
4.
5.
MINIMUM WIRE SIZE TO BE #12 AWG COPPER
INSTALLATION TO MEET ALL STATE AND LOCAL CODES.
ALL WIREING TO BE INSTALLED IN METAL RACEWAYS
OR MC CABLE WHERE PERMITTED BY CODE.
MAXIMUM LOAD OF 1,600 WATTS FOR 20 AMP BRANCH CIRCUITS.
FINAL LOCATIONS OF ALL DEVICES AND EQUIPMENT
CONNECTIONS TO BE VERIFIED BY THE OWNER.
ELECTRICAL RISER
DIAGRAM
2-1
2" PVC CONDUIT WITH (4) 4
0 AL AND (1) #2 GROUND WIRE
NOT TO SCALE
SUPPLY FAN:
USE CIRCUIT 20
115 V
1/2 HP
4.80 AMPS
EXHAUST FAN:
USE CIRCUIT 22
115 V
3/4 HP
13.80 AMPS
CONDENSER
USE CIRCUIT 24
20 AMP
2 POLE
EVAPORATOR
USE CIRCUIT 26
15 AMP
2 POLE
FOR HOOD SYSTEM (FUTURE)
GROUND ROD
TO
#6 THHN
#4 THHN TO THE
BUILDING STEEL
DISCONNECT
200 AMP
3 PHASE
42 SPACE
PANEL
GROUND ROD
TO
#6 THHN
#4 THHN TO THE
BUILDING STEEL
DISCONNECT
200 AMP
3 PHASE
42 SPACE
PANEL
METER BASE
AS REQUIRED
#4 THHN TO THE
BUILDING STEEL
SUB-PANEL
GROUND ROD
TO
#6 THHN
FOR FUEL SYSTEMS100 AMP
SINGLE PHASE
USE DUAL RATED THHN WIRE
4 WIRE PER CABLE
FOR COOLERS AND FREEZER
DISCONNECT
20A/2P CIRCUIT FOR CONDENSER
IN COOLER AND FREEZER
15A/2P CIRCUIT FOR LIGHTS
200 AMP 200 AMP 100 AMP
400 AMP CT CABINET
TWO 200 AMP DISCONNECTS
METER BASE FEED FROM PUBLIC SERVICE
LOCATE PER LOCAL UTILITY REQUIREMENTS
UNDERGROUND SERVICE
DRIVEWAY RATED
SODA
ON ONE CIRCUIT
2 RECEPT.
GFI
GFI GFI GFI GFI GFI GFI GFIGFI
15A/2P CIRCUIT FOR EVAPORATOR
ENTIRE BEVERAGE AREA
11 RECEPTACLES ON 8 CIRCUITS
COUNTS SODA INDICATED
ALL GFI PROTECTED
FOOD SERVICE AREA
5 RECEPTICLES ON 2 CIRCUITS
GFI
GFI
GFI
GFI
GFI
GFI
ELECTRICAL POWER PLAN
POS
FREEZER SIMILAR
TO COOLER REQUIREMENTS
110V DUPLEX RECEPTICAL
GFI 110 V RECEPTICAL GF PROTECTED
DED 110 V RECEPTICAL, DEDICATED
220 B RECEPTICAL220V
PHONE / DATA OUTLET
SYMBOLS
ELECTRICAL SPECIFICATIONS AND GENERAL REQUIREMENTS:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND
SPECIFICATIONS ON THE DRAWINGS. THE INTENT OF THE CONTRACT
DOCUMENTS IS TO INCLUDE ITEMS NECESSARY FOR THE PROPER EXECUTION
OF THE WORK.
BUILDING CODES: NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE
CITY, STATE AND LOCAL BUILDING CODES FOR THIS CLASS OF WORK.
ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND
DIMENSIONS AT THE JOBSITE. IF DISCREPANCIES ARE FOUND THE GENERAL
CONTRACTOR SHALL BE NOTIFIES BEFORE PROCEEDING WITH ANY WORK OR
ORDERING ANY EQUIPMENT OR MATERIAL IN THE AFFECTED AREA.
FIT AND QUANTITY OF THE WIRING, ELECTRICAL EQUIPMENT, THE VARIOUS
NECESSARY PARTS AND MATERIALS TO MAKE A COMPLETE AND FINISHED JOB
SHALL BE VERIFIED AND COORDINATED PRIOR TO START OF CONSTRUCTION
AND ARE THE EXCLUSIVE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
LOCAL UTILITY COORDINATION: ELECTRICAL CONTRACTOR SHALL
COORDINATE TRANSFORMERS AND SERVICE REQUIREMENTS WITH THE LOCAL
UTILITY COMPANY. THE E.C. SHALL CONSULT WITH THE LOCAL UTILITY TO
ESTABLISH REQUIRED kACI RATINGS.
ALL FIXTURES, EQUIPMENT AND MATERIALS SHALL BE INSTALLED PER THE
MANUFACTURER'S SUGGESTED INSTALLATION REQUIREMENTS IN A NEAT AND
WORKMANLIKE MANNER.
UL LABELING: ALL ELECTRICAL EQUIPMENT SHALL HAVE "UL" LABELS.
WIRING DEVICES SHALL BE SPECIFICATION GRADE.
PROVIDE ALL DISCONNECTS REQUIRED PER NATIONAL AND LOCAL ELECTRICAL
CODES RATED TO UTILITY SUPPLIED kAIC LIMITS, OR, IF NOT SUPPLIED, TO NEC
MINIMUMS.
ALL EXPOSED WIRE AND WIRING BELOW CONCRETE SLABS SHALL BE IN
CONDUIT.
WIRE: ALL WIRE SHALL BE COPPER, MINIMUM SIZE #12 AWG. ALL
CONDUCTORS SHALL HAVE TYPE "THHN" INSULATION. CONDUCTORS #10 AND
SMALLER MAY BE SOLID. GROUNDING CABLES SHALL BE NO SMALLER THAN 4
COPPER.
BREAKER PANELS: FURNISH AND INSTALL A BREAKER PANEL AS
MANUFACTURED BY SQUARE D OR ITE. INSTALL PANEL SO TOP BREAKER IS NO
HIGHER THAN 6'-0".
FURNISH AND INSTALL TYPEWRITTEN DIRECTORY. IDENTIFY AND LABEL ALL
ELECTRICAL SERVICE EQUIPMENT.
GROUNDING: GROUNDING SHALL BE DONE STRICTLY ACCORDING TO SECTION
250.52 OF THE NATIONAL ELECTRIC CODE USING ACCEPTABLE ELECTRODES
AND CONNECTIONS.
SWITCHES: ALL SWITCHES SHALL BE RATED 20 AMP, 125 VOLT AND SHALL BE
MOUNTED 4'-6" AFF, UNLESS NOTED OTHERWISE.
RECEPTICALS: ALL RECEPTACLES TO BE 15 AMP, 125 VOLT, GROUNDING TYPE
AND SHALL BE MOUNTED 18" AFF, UNLESS NOTED OTHERWISE.
PROVIDE TEMPORARY POWER REQUIRED BY THE GENERAL CONTRACTOR AND
OTHER TRADES. COORDINATE POWER REQUIREMENTS WITH GC PRIOR TO
INSTALLATION.
LIGHTING FIXTURES: LIGHTING FIXTURES TO BE FURNISHED AND INSTALLED
COMPLETE WITH LAMPS AS DETAILED ON THE PLANS OR AS INTENDED. SEE
REFLECTED CEILING PLAN AND/OR LIGHTING PLAN FOR THE EXACT LOCATION
OF THE CEILING GRID, LIGHT FIXTURES, OR THE GENERAL INTENT OF THE
DRAWINGS.
SEE THE ELECTRICAL DRAWING(S) FOR THE FIXTURE SCHEDULE, NOTES AND
OTHER SPECIFICATION REQUIREMENTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR NOTICE TO THE INSPECTING
AUTHORITIES, ARCHITECT, OR GENERAL CONTRACTOR, SO THAT WORK CAN BE
INSPECTED OR APPROVED BEFORE COVERING. THIS PROCEDURE SHALL
OCCUR WITHOUT AFFECTING CONSTRUCTION PROGRESS AND COMPLETION.
THE INTENTION OF THESE DOCUMENTS IS TO PROVIDE THE OWNER WITH A
BUILDING COMPLETE IN ITS ENTIRETY AT THE TIME OF OCCUPANCY. IT IS THE
SUB-CONTRACTOR'S RESPONSIBILITY TO CONTACT THE GENERAL
CONTRACTOR DURING THE BIDDING/PRICING PHASE OF ANY DETAILS MISSING,
VAGUE, OR INCOMPLETE SO THAT AN APPROPRIATE ADDENDUM OR
CLARIFICATION CAN BE ISSUED. THE SELECTED CONTRACTOR SHALL PROVIDE
ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, AND SERVICES NECESSARY FOR A
COMPLETE, FUNCTIONAL, AND OPERATIONAL FACILITY.
E1.2