GENERAL REQUIREMENTS AND GUIDELINES FOR THIS PROJECT:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND SPECIFICATIONS
ON THE DRAWINGS. THE INTENT OF THE CONTRACT DOCUMENTS IS TO
INCLUDE ITEMS NECESSARY FOR THE PROPER EXECUTION OF THE WORK.
THE CONTROLLING CODE FOR ALL WORK UNDER THESE DRAWINGS SHALL BE
THE INTERNATIONAL BUILDING CODE 2014 WITH INDIANA AMENDMENTS, ALL IN
THEIR CURRENT ADDITIONS.
THE CONTROLLING DOCUMENT FOR ALL WORK UNDER THESE DRAWINGS
SHALL BE THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION,
AIA (AMERICAN INSTITUTE OF ARCHITECTS) DOCUMENT A201, CURRENT
EDITION. AGREEMENT BY ANY PARTY TO WORK UNDER THIS CONTROLLING
DOCUMENT SHALL COMMENCE WITH THE START OF ANY WORK DESCRIBED
WITHIN THESE DOCUMENTS.
THE ARCHITECT SHALL FILE FOR STATE PLAN REVIEW AND PROVIDE A RELEASE
FOR USE IN OBTAINING LOCAL PERMITS. THE GENERAL CONTRACTOR SHALL
FILE DRAWINGS OR OTHER MATERIALS FOR PERMIT APPLICATION AT THE
LOCAL LEVEL AND SECURE ALL NECESSARY BUILDING PERMITS. SUB-
CONTRACTORS TO THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING THEIR OWN LOCAL PERMITS.
PRIOR TO COMMENCING ACTIVITIES, EACH CONTRACTOR AND MATERIAL
SUPPLIER SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT
DOCUMENTS AND BECOME FULLY AWARE OF THE REQUIREMENTS. EACH
CONTRACTOR AND MATERIAL SUPPLIER SHALL TAKE FIELD MEASUREMENTS
AND VERIFY FIELD CONDITIONS AND SHALL CAREFULLY COMPARE SUCH
MEASUREMENTS AND CONDITIONS WITH THE CONTRACT DOCUMENTS.
IN THE EVENT OF INCONSISTENCIES WITHIN OR BETWEEN THE CONTRACT
DOCUMENTS, EACH CONTRACTOR OR MATERIAL SUPPLIER SHALL PROVIDE THE
BETTER QUALITY OR GREATER QUANTITY OF THE WORK, AND SHALL COMPLY
WITH THE STRICTER REQUIREMENT. INCONSISTENCIES DISCOVERED SHALL BE
IMMEDIATELY REPORTED TO THE ARCHITECT IN WRITING.
NO PLEAS OF IGNORANCE RESULTING FROM FAILURE TO EXAMINE THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS OR THE CONDITIONS UNDER
WHICH THE WORK IS TO BE PERFORMED WILL BE ACCEPTED AS AN EXCUSE
FOR FAILURE OR OMISSION ON THE PART OF EACH CONTRACTOR AND
MATERIAL SUPPLIER TO FULFILL IN EVERY RESPECT ALL REQUIREMENTS OF
THE CONTRACT DOCUMENTS.
VERIFY THAT SURFACES TO RECEIVE MATERIALS ARE IN A CONDITION TO
ACCOMMODATE INSTALLATION. IMMEDIATELY REPORT TO THE ARCHITECT ANY
ARCHITECT / ENGINEER NOTIFICATION:
IF THE GENERAL CONTRACTOR DISCOVERS CONDITIONS THAT ARE NOT
SUBSTANTIALLY LIKE THE ARCHITECT’S DRAWINGS, THE ARCHITECT OR
ENGINEER SHALL BE IMMEDIATELY NOTIFIED.
THIS NOTIFICATION RELATES TO ALL PARTS OF THIS PROJECT, INCLUDING BUT
NOT LIMITED TO DISCOVERED SOIL CONDITIONS, INAPPROPRIATE OR NON-
SPECIFIED PRODUCTS DELIVERED AND/OR INSTALLED ON SITE, OR ANY
QUESTION REGARDING POSSIBLE VIOLATION OF CODES OR ORDINANCE
STANDARDS.
PROCEEDING WITH THE WORK SHALL CONSTITUTE ACCEPTANCE BY THE
GENERAL CONTRACTOR OF THE EXISTING CONDITIONS, AND THAT THE
PROJECT CAN BE BUILT STRUCTURALLY SOUND AND MEETING LOCAL CODES.
Indiana Adopted Codes for Building Construction
In effect December 1, 2014
2014 Indiana Building Code Adoption by Reference: 2012 International
Building Code First Printing plus Indiana Amendments, effective December
1st 2014.
2009 Indiana Electrical Code Adoption by Reference: 2008 National
Electric Code First Printing plus Indiana Amendments, effective August 26,
2009.
2014 Indiana Fuel Gas Code Adoption by Reference: 2012 International
Fuel Code First Printing plus Indiana Amendments, effective December 1st
2014.
2014 Indiana Mechanical Code Adoption by Reference: 2012 International
Mechanical Code First Printing plus Indiana Amendments, effective
December 1st 2014.
2012 Indiana Plumbing Code Adoption by Reference: 2006 International
Plumbing Code Second Printing plus the Indiana Amendments, effective
December 24, 2012.
2005 Indiana Residential Code Adoption by Reference: 2003 International
Residential Code Fifth Printing plus Indiana Amendments, effective
September 11, 2005.
2014 Indiana Fire Code Adoption by Reference: 2012 International Fire
Code First Printing plus Indiana Amendments, effective December 1st 2014.
2010 Indiana Energy Conservation Code Adoption by Reference: 2007
Edition ASHRAE 90.1 plus Indiana Amendments, effective May 6, 2010.
A Complete list of all codes and other rules adopted by the Fire Prevention & Building
Safety Commission of the State of Indiana along with PDF versions of the Indiana
Amendments can be found at:
http://www.in.gov/dhs/2490.htm
DISCREPANCIES OR ERRORS WHICH WOULD RESULT IN POOR APPLICATION OR
CAUSE LATENT DEFECTS IN WORKMANSHIP. IF A CONTRACTOR OR SUB-
CONTRACTOR PROCEEDS WITH INSTALLATION OF MATERIALS OVER ANOTHER
CONTRACTOR'S WORK, IT SHALL BE ASSUMED THAT THE CONTRACTOR OR SUB-
CONTRACTOR ACCEPTS THE WORK TO RECEIVE HIS MATERIAL.
ALL LABOR, CONSTRUCTION MATERIALS, PROVIDED AND INSTALLED TO
COMPLETE THE WORK OF THESE CONTRACT DOCUMENTS SHALL BE EXECUTED
IN COMPLETE COMPLIANCE WITH ALL LOCAL, STATE AND FEDERAL CODES,
PRACTICES OR ORDINANCES AND WITHIN THE CONSTRAINTS OF THE HIGHEST
ACCEPTABLE CONSTRUCTION PRACTICES.
UPON COMPLETION OF THE PROJECT, OBTAIN ALL FINAL INSPECTIONS AS
REQUIRED BY THE LOCAL JURISDICTIONS AND FURNISH OWNER WITH
EVIDENCE OF ALL SUCH INSPECTIONS AND CERTIFICATES OF OCCUPANCY, IF
ISSUED BY THE JURISDICTION.
THE GENERAL CONTRACTOR SHALL PROVIDE REASONABLE SUPERVISION AND
COORDINATION OF ALL SUB-CONTRACTORS WORK INCLUDING WORK
PERFORMED BY OTHERS SUCH AS SUPPLIERS OF OWNER-SUPPLIED ITEMS.
UPON COMPLETION OF PROJECT, PROVIDE OWNER WITH ALL INSTRUCTION
MANUALS, WARRANTIES OR OTHER DOCUMENTS REQUIRED FOR THE PROPER
OPERATION OR MAINTENANCE OF ANY PART OF THE CONTRACTOR'S WORK.
THE GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY PROTECTION
AND SECURITY MEANS FOR HIS WORK UNTIL TURNED OVER TO THE OWNER. IF
THE PROJECT AREA IS TO BE USED BY EMPLOYEES OR THE PUBLIC DURING
CONSTRUCTION, FULLY PROTECT THE CONSTRUCTION SITE, CONSTRUCT
BARRIERS AND FENCING, AND PROVIDE APPROPRIATE SIGNAGE TO PROTECT
THESE PERSONS.
THE GENERAL CONTRACTOR SHALL PROVIDE AND MAINTAIN MINIMUM GENERAL
LIABILITY INSURANCE. THE FRANCHISEE, FRANCHISER, AND THE ARCHITECTS
SHALL BE HELD HARMLESS AGAINST ALL GENERAL LIABILITY CLAIMS THAT MAY
RESULT AS A PART OF THIS PROJECT.
SOILS:
OTHERS HAVE CHOSEN TO NOT TEST SOILS FOR THIS PROJECT, NOR MAKE
SOIL DATA AVAILABLE TO THE ARCHITECT. THE ARCHITECT SHALL BE HELD
HARMLESS FOR ANY COMMON SOIL FAILURES SUCH AS FAILURE OF
COMPACTION; DENSITY FAILURE; GENERAL SOIL SHEAR OR SHRINKAGE;
SETTLEMENT FAILURE; SLOPE FAILURE; FLOW SLIDE FAILURE; MOVEMENTS
CAUSED BY EXPANISIVE OR HIGHLY PLASTIC SOILS; OR ANY OTHER COMMONY
ANALYIZED SOIL FAILURES.
CONVENIENCE STORE / FOOD MART
VILLAGE OF WEST CLAY
CARMEL, INDIANA
SOUTHWEST CORNER OF
HARLESTON STREET AND TOWNE ROAD
OCTOBER 14, 2021
INDEX OF DRAWINGS OF THIS SET:
ARCHITECTURAL, STRUCTURAL, PLUMBING,
MECHANICAL, ELECTRICAL DRAWINGS:
COVER SHEET GENERAL PROJECT GUIDELINES; INDIANA
BUILDING CODES
A1.1 FLOOR PLAN
A1.2 FOUNDATION PLAN; CONCRETE SPECIFICATIONS
A1.3 REFLECTED CEILING PLAN; ACOUSTIC CEILING
SPECIFICATIONS; BULKHEAD GUIDELINES
A1.4 ROOF FRAMING PLAN; JOIST BRACING CUT SHEET
A1.5 ROOF PLAN; ROOF MEMBRANE SPECS.; SCUPPER CUT
SHEETS
LS1.1 LIFE SAFETY PLAN; BUILDING CODE SUMMARY
A2.1 BUILDING ELEVATIONS
A2.2 BUILDING ELEVATIONS
A3.1 TRANSVERSE SECTION THRU TYPICAL MASONRY WALLS
A3.2 TRANSVERSE SECTION THRU SOUTH DOORS
A3.3 TRANSVERSE SECTION THRU NORTH DOORS AND SOUTH
STOREFRONT
A3.4 STOREFRONT WINDOW DETAIL; STOREFRONT
SPECIFICATIONS; NORTH WALL DETAIL SECTION
A3.5 COOLER SECTION AND WEST WALL DETAIL SECTION;
COOLER SPECIFICATIONS
A4.1 STEEL DETAILS; STEEL OPEN-WEB JOIST SPECIFICATIONS;
GENERAL STEEL REQUIREMENTS
A4.2 RESTROOM DETAIL PLAN AND OTHER INTERIOR ELEVATIONS
A4.3 SPECIFICATIONS; ELECTRICAL GROUNDING
SPECIFICATIONS; GROUNDING SCHEMATIC
A4.4 ROOF EQUIPMENT SCREENING SPECIFICATIONS;
SCREENING CUT SHEETS
A4.5 ADA DETAILS
A5.1 DUMPSTER AND SOUTH MASONRY WALL ELEVATIONS AND
DETAILS
A6.1 FUEL CANOPY PLANS AND STRUCTURAL DETAILS; FUEL
CANOPY CONCRETE SPECIFICATIONS; PRE-ENGINEERED FUEL
CANOPY SPECIFICATIONS
A6.2 FUEL CANOPY ELEVATIONS; REFLECTED CEILING /
LIGHTING PLAN; LIGHT CUT SHEETS
A7.1 BUILDING SIGNAGE; GROUND SIGN; CANOPY SIGNAGE
P1.1 SANITARY SEWER PLAN; PLUMBING SPECIFICATIONS
P1.2 PLUMBING ISOMETRIC; DOMESTIC WATER DISTRIBUTION
SPECIFICATIONS
M1.1 MECHANICAL PLAN; MECHANICAL SPECIFICATIONS;
MECHANICAL EQUIPMENT SCHEDULE
E1.1 ELECTRICAL POWER PLAN; ELECTRICAL SPECIFICATIONS;
RISER DIAGRAM
E1.2 ELECTRICAL LIGHTING PLAN; EXTERIOR SCONCE LIGHT CUT
SHEET
CIVIL ENGINEERING DRAWING:
C101 SITE DEVELOPMENT PLAN
LANDSCAPE DRAWINGS:
L1.0 SITE LANDSCAPE PLAN
L2.0 LANDSCAPE NOTES AND DETAILS
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION30'-8"14'-4"42'-3"
87'-3"
29'-0"14'-4"44'-0"
11'-4"16'-4"1'-4"50'-8"SCALE: 1/4" = 1'-0"
FLOOR PLAN
PRE-FABRICATED BEVERAGE COOLER
40'-8 1/8"7'-6"8'-5"SODA DISPENSER
HAND SINK
8'-0"
2" GAP
15'-8 5/8"1'-0"58'-0"3'-0"
FURRED, INSULATED WALLS
FURRED WALL
MEN'S RR
WOMEN'S RR
SEE DETAILS, SHEET A1.2
CMU INFILL WALLS
ANODIZED STOREFTONT ANODIZED STOREFTONT
22'-2"8'-0"8'-0"4'-1"4'-1"8'-0"8'-0"10'-7"
TYPICAL FURRED WALL
3 5/8" STEEL STUDS 24" O.C.
4" FIBERGLASS INSULATION
.006 VISQUEEN
5/8" DRYWALL FREEZER BY OTHERS
BY OTHERS
2" GAP
6"x6"x3/8" TUBE STEEL
TYPICAL ALL COLUMNS
6"x6"x3/8" TUBE STEEL
TYPICAL ALL COLUMNS
3 FALSE WINDOWS 3 FALSE WINDOWS
TYPICAL FURRED WALL
3 5/8" STEEL STUDS 24" O.C.
4" FIBERGLASS INSULATION
.006 VISQUEEN
5/8" DRYWALL
37'-4 3/4"2'-6"4 3/4"7'-8"4'-7 1/2"28'-3"5'-9 1/2"19'-4 3/8"19'-7 3/4"4 3/4"4'-0"4 3/4"12'-11 1/2"2'-6"4 3/4"R-19
R-19
5'-0 1/4"1'-4"21'-4 5/8"1'-10 5/8"87'-4"
A1.1
1
A3.1
1
1
A3.1
1
A3.1
1
1
A3.2
A3.2 A3.3
A3.3
A3.4
1
1
A3.5
1
A3.5
1
1
A3.4
1
A3.4
A3.4
A3.4
2
2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/4" = 1'-0"
FOUNDATION PLAN
CONCRETE REQUIREMENTS AND SPECIFICATIONS:
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE
SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.
SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS
CONFLICT WITH THESE STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH
EACH OTHER, THE STRICTEST PROVISIONS SHALL GOVERN.
GOVERNING CODES: INTERNATIONAL BUILDING CODE, 2008, WITH CURRENT
INDIANA AMENDMENTS.
FOUNDATIONS:
NOTIFY THE ARCHITECT AS SOON AS POSSIBLE OF ANY UNUSUAL SOIL
CONDITIONS, SUCH AS UNEXPECTED SPRING OR SEEPAGE WATER, OR SOIL OF
QUESTIONABLE BEARING CAPACITY.
ALL FOOTINGS SHALL BEAR ON FIRM UNDISTURBED SOIL OR ENGINEERED FILL
WITH AN ALLOWABLE BEARING CAPACITY OF 2,000 POUNDS PER SQUARE FOOT.
PERIMETER FOOTINGS SHALL BEAR A MINIMUM OF 3'-0" BELOW EXTERIOR
GRADE. STEP FOOTINGS AS REQUIRED. WHERE UNDERGROUND UTILITIES
ENTER OR EXIT THE BUILDING, STEP TOPS OF ALL FOOTINGS BELOW UTILITY
INVERT ELEVATIONS.
DESIGN NET SOIL PRESSURES
SPREAD FOOTINGS:
CONTINUOUS FOOTERS
2,000 PSI
1,500 PSI.
BACKFILL AND FILL MATERIALS: PROVIDE SATISFACTORY SOIL MATERIALS FOR
BACKFILL AND FILL, FREE OF CLAY, DEBRIS, WASTE, FROZEN MATERIALS,
VEGETABLE AND OTHER DELETERIOUS MATTER.
REINFORCED CONCRETE:
ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318-95, "BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE".
SPECIFICATIONS: IN GENERAL, COMPLY WITH ACI 301-96, "STANDARD
SPECIFICATIONS FOR STRUCTURAL CONCRETE".
PLACEMENT AND CURING OF CONCRETE SHALL CONFORM TO ACI 305 "HOT
WEATHER CONCRETING" AND ACI 306 "COLD WEATHER CONCRETING".
ALL REINFORCING DETAILS SHALL CONFORM TO ACI 315-86, "MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES"
UNLESS DETAILED OTHERWISE ON THE STRUCTURAL DRAWINGS.
ALL DEFORMED REINFORCING BARS: ASTM A615, GRADE 60
ALL WELDED WIRE FABRIC:ASTM A185, DELIVERED IN FLAT SHEETS
REINFORCING SUPPLIER SHALL PROVIDE ALL BAR ACCESSORIES, CHAIRS, AND
SUPPORTS NECESSARY TO SECURE STEEL IN ACCORDANCE WITH "ACT CODE
OF STANDARD PRACTICE".
WHERE ANY STEPS IN FALL FOOTING ELEVATIONS OCCUR, PROVIDE MAXIMUM
STEP OF ONE VERTICAL TO TWO HORIZONTAL.
CONCRETE COVER: UNLESS OTHERWISE NOTED, DETAIL REINFORCING TO
PROVIDE MINIMUM COVER AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:3
INCHES
CONCRETE EXPOSED TO EARTH OR WEATHER, #5 RE-BARS OR SMALLER:
1/2 INCHES
ALL OTHER:2 INCHES
1
CONCRETE CONTRACTOR SHALL VERIFY SOIL BEARING PRIOR TO CONCRETE
PLACEMENT. REPORT DEVIATIONS TO GENERAL CONTRACTOR AND
ARCHITECT.
CONCRETE IN THE FOLLOWING AREAS SHALL CONSIST OF NATURAL SAND FINE
AGGREGATE AND NORMAL WEIGHT COARSE AGGREGATES CONFORMING TO
ASTM C33, TYPE 1 PORTLAND CEMENT CONFORMING TO ASTM C150, AND SHALL
HAVE THE FOLLOWING COMPRESSIVE STRENGTH AT 28 DAYS:
FOOTINGS AND PADS:
SLABS-ON-GRADE
AND PIERS:
3,000 PSI
4,000 PSI
RETAINING WALLS, CURBS, SIDEWALKS, AND SLABS EXPOSED TO DE-
ICERS.
4,000 PSI (6% + 1% ENTRAINED AIR BY
VOLUME)
NO PART OF THE STRUCTURE SHALL BE PLACED ON FROZEN OR WET SOIL.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING THE
FOUNDATION AND SOIL WITHIN THE BUILDING AREA FROM FREEZING DURING
WINTER CONSTRUCTION.
FOOTINGS AND PIERS:
DOWELS IN FOOTINGS SHALL MATCH VERTICAL PIER REINFORCING.
PROVIDE CORNER BARS AT FOOTING CORNERS TO MATCH HORIZONTAL
REINFORCING. MINIMUM LENGTHS OF EACH LEG TO BE 45 BAR DIAMETERS.
BACKFILL AGAINST BOTH SIDES OF WALLS EQUALLY UNTIL THE LOWER
ELEVATION IS ATTAINED. BRACE ALL FOUNDATION WALLS BEFORE
BACKFILLING AND COMPACTING.
PROVIDE LEAN CONCRETE (CLASS IV) UNDER FOUNDATIONS FOR ACCIDENTAL
OVER-EXCAVATION, SOFT SPOTS, AND TRENCHES.
BUILT-IN WORK:
INSTALL ALL ANCHORS, INSERTS, NOSINGS, REGLETS AND LIKE ITEMS
FURNISHED BY OTHER TRADES FOR INSTALLATION IN CONCRETE WORK. ALL
BUILT-IN ITEMS SHALL BE IN PROPER
LOCATION AND SHALL BE SO MAINTAINED DURING THE PERFORMANCE OF
CONCRETE WORK.
SLEEVES, CONDUITS, PIPES AND LIKE ITEMS PASSING THROUGH FLOORS,
WALLS, OR BEAMS SHALL BE OF SUCH SIZE OR IN SUCH LOCATION AS NOT TO
IMPAIR UNDULY THE STRENGTH OF THE CONSTRUCTION.
VAPOR BARRIER PLACEMENT:
USE A CONCRETE MIXTURE WITH AN ADEQUATE CEMENT FACTOR - MINIMUM OF
5 1/2 BAGS PER CUBIC YARD. USE A SMALL AMOUNT OF AIR-ENTRAINMENT IN
THE MIXTURE TO REDUCE BLEEDING - ABOUT 3% TO 5% AIR. EXTERIOR
CONCRETE SHALL HAVE 5 1/2% AIR. PLACE CONCRETE AT LOWEST PRACTICAL
SLUMP. A WATER-REDUCING ADMIXTURE MAY BE USED TO LOWER THE MIX
WATER CONTENT, IF USED STRICTLY ACCORDING TO WRITTEN
MANUFACTURER'S INSTRUCTIONS.
PERIMETER INSULATION:
A TOTAL OF FOUR FEET WIDTH OF PERIMETER INSULATION SHALL BE PUT IN
PLACE. THIS CAN BE A COMBINATION OF HORIZONTAL AND VERTICAL RIGID
INSULATION, AS SHOWN ON DRAWINGS.
4'-0" x 4'-0" x 1'-0"
CONCRETE FOOTER PAD
#5 REBARS 12" O.C. EACH WAY
24" x 24" CONCRETE COLUMN PIER
2'-0"8'-8"2'-0"9"
87'-4"50'-8"40'-11"1'-5"9"1'-5"29'-5"
27'-8"1'-5"9"2'-0"8'-8"2'-0"9"1'-5"42'-8"8"1'-0"4"2'-5"2'-11"8"8"4'-0"1'-4"7'-4"4" THICK CONCRETE FLOOR
SEE SPECIFICATIONS
COOLER FOOTPRINT
SEE SPECIAL FLOOR DETAILS
SEE SPECIAL FLOOR DETAILS
FREEZER FOOTPRINT
1
A3.1
1
1
A3.1
1
A3.1
1
1
A3.2
A3.2 A3.3
A3.3
A3.4
1
1
A3.5
1
A3.5
1
1
A3.4
1
A3.4
A3.4
A3.4
2
2
A1.2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONACOUSTICAL CEILINGS:
1. PROVIDE ALL ACOUSTICAL CEILINGS COMPLETE WITH
SUSPENSION SYSTEM AND RELATED ACCESSORIES AS SHOWN
ON THE DRAWINGS AND SPECIFIED HEREIN.
2. STORE AND HANDLE TO PREVENT SOILING, DAMAGE OR
WETTING.
3. INSTALL ALL ACOUSTIC CEILING AND SUSPENSION SYSTEMS IN
STRICT ACCORDANCE WITH MANUFACTURER’S
RECOMMENDATIONS. FINISHED CEILINGS SHALL BE LEVEL, WITH
ALL JOINTS SNUG AND SQUARE.
4. SUSPENSION SYSTEM INSTALLATION SHALL COMPLY WITH ASTM
C636 REQUIREMENTS AND BE WATER OR LASER LEVEL.
5. CEILING SUSPENSION SYSTEM SHALL BE SUPPORTED DIRECTLY
FROM THE BUILDING STRUCTURE. PROVIDE ADDITIONAL
SUPPORT FRAMING AS REQUIRED. PROVIDE SUPPORT AT ALL
FOUR (4) CORNERS OF FLUORESCENT LIGHT FIXTURES.
6. PROVIDE WALL ANGLE MOLDING AT PERIMETER OF ALL CEILING
TILE INSTALLATIONS. ANCHOR MOLDING TO WALL AT EACH POINT
OF MAIN RUNNER AND CROSS TEE BEARINGS AND ADDITIONALLY
AS REQUIRED TO PREVENT MOLDING FROM SAGGING OR
TWISTING.
7. INSTALL CEILING TO PERMIT BORDER UNITS OF THE GREATEST
POSSIBLE SIZE.
8. COORDINATE WORK WITH ELECTRICAL PLANS AND/OR
ELECTRICAL SUB-CONTRACTOR TO CONFIRM LIGHT FIXTURES
ARE CORRECTLY LOCATED.
9. IF REQUIRED IN THIS PROJECT, COORDINATE WORK WITH
SPRINKLER SYSTEM INSTALLER.
10. REMOVE AND REPLACE UNITS, WHICH ARE DAMAGED OR
IMPROPERLY INSTALLED.
11. CLEAN PAINTED SURFACES DAMAGED BY WORK OF THIS
INSTALLATION.
SCALE: 1/4" = 1'-0"
REFLECTED CEILING PLAN
TYPICAL 24"x24"
DIFFUSER
TYPICAL 24"x24"
LED FIXTURE
24"x 48"
LED PANEL
FIXTURE
LAY-IN ACOUSTIC TILE
CEILING AT 10'-0" AFF
LAY-IN ACOUSTIC TILE
CEILING AT 10'-0" AFF
LAY-IN ACOUSTIC TILE
CEILING AT 10'-0" AFF
LAY-IN ACOUSTIC TILE
CEILING AT 10'-0" AFF
GENERAL NOTES – BULKHEADS
CEILING, SOFFIT AND BULKHEAD FRAMING SYSTEMS SHALL BE
DESIGNED TO CARRY CEILING DEAD LOADS IN ADDITION TO FRAMING
MEMBERS, LIGHT FIXTURES, AIR DIFFUSERS, SPEAKERS, INSULATION,
AND SIGNAGE, ETC.
BLOCKING AND FRAMING SHALL BE 2X4 MINIMUM AND BE 16” O.C.
FRAMING. IT MAY BE 24”” O.C. IF ATTACHED TO PRE-ENGINEERED
WOOD TRUSSES, AND NOTICE OF THE BULKHEAD CONDITION IS A PART
OF THE TRUSS DESIGN AND SPECIFICATIONS.
POSITIVE TENSION-TYPE CONNECTIONS BACK TO STRUCTURE IS
REQUIRED. UNISTRUT TYPE METAL CONNECTIONS OR EQUAL.
DRYWALL SHALL BE 5/8” TYPE X.
STRICTLY FOLLOW RECOMMENDATIONS OF THE USG CORPORATION
AND THE NATIONAL GYPSUM COMPANY’S GOLD BOND BUILDING
PRODUCTS DIVISION.
ALL ACCESSORIES, INCLUDING SIMPSON JOIST HANGERS, CLIPS,
SCREWS, AND NAILS ETC. SHALL BE PER ROUGH FRAMING
SPECIFICATIONS THAT ARE A PART OF THESE CONTRACT DOCUMENTS.
EXECUTION:
ARRANGE FRAMING FOR CEILINGS TO PROVIDE SUPPORT
INDEPENDENT OF WALLS, COLUMNS, PIPES, AND DUCTS AND INSTALL
ALL WORK PLUMB.
NOTIFY ARCHITECT IF ANY QUESTIONS ON STRUCTURAL ATTACHMENT
ARISE.
8'-0" AFF OR
PER COOLER MFGR.
MINIMUM 24" x 30"
ATTIC ACCESS
1
A3.1
1
1
A3.1
1
A3.1
1
1
A3.2
A3.2 A3.3
A3.3
A3.4
1
1
A3.5
1
A3.5
1
1
A3.4
1
A3.4
A3.4
A3.4
2
2
A1.3
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/4" = 1'-0"
ROOF FRAMING PLAN
CANTILEVER JOIST ENDS HERE
MECHANICAL WALK-DECK
ALLOW FOR THREE
HVAC UNITS OF 500# EACH
BRACING AS REQUIRED
G.C AND STEEL SUPPLIER
SHALL VERIFY ACTUAL
EQUIPMENT
30 K 90 / 50 24" O.C.W18 x 46 W18 x 46 W18 x 46
30 K 90 / 50 24" O.C.W18 x 46 W18 x 46 W18 x 46
MINIMUM BRIDGING: 1 1/2" x 7/64" OR R = .35 MAX. SPACING 9'-8" O.C.
MINIMUM BRIDGING: 1 1/2" x 7/64" OR R = .35 MAX. SPACING 9'-8" O.C.
BRIDGING DETAILS
NOTE: FINAL DESIGN SHALL BE THE RESPONSIBILITY
OF THE STEEL JOIST SUPPLIER. CONSULT ARCHITECT
FOR REQUIRED INFORMATION, IF NEEDED.
A1.4
1
A3.1
1
1
A3.1
1
A3.1
1
1
A3.2
A3.2 A3.3
A3.3
A3.4
1
1
A3.5
1
A3.5
1
1
A3.4
1
A3.4
A3.4
A3.4
2
2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/4" = 1'-0"
ROOF PLAN
FIRESTONE TPO MECHANICALLY
ADHERED ROOFING OR EQUAL
ALUMINUM WALKABLE
EQUIPMENT DECK
SLOPE MIN. 1 : 12SLOPE MIN. 1 : 12ROOF EQUIPMENT SCREENING
SEE DETAILS
ROOF EQUIPMENT SCREENING
SEE DETAILS
GATE BY ROOF SCREENING
MANUFACTURER
GATE BY ROOF SCREENING
MANUFACTURER
5'-0" WIDE
5'-0" WIDE
TPO ROOFING GENERAL NOTES:
MISCELLANEOUS:
Any additional work such as changes to specified materials, applications or
processes, or other architectural features requiring decisions and not certified
by Gordon Clark must be promptly proposed by letter or email
(gclark4820@aol.com).
ROOFING MATERIAL:
Proposed manufacturer: Firestone UltraPly TPO Membrane, mechanically
attached to steel deck.
ROOF SCUPPERS:
Strictly follow drawings and recommendations by Firestone TPO thru-wall
Platinum TPO Coated Metal Scuppers.
REQUIREMENTS:
Provide a minimum 1: 12 roof slope.
Steel deck shall be a minimum 22 ga. Thickness.
Fastener Type: Firestone Heavy Duty Plus
Insulation Adhesive: Spray R insulation adhesive. Verify if steel deck must be
cleaned to meet Firestone requirements.
Adhesive Attachment: Full Application I.S.O. Spray S Insulation Adhesive.
Membrane Requirement: UltraPly Platinum TPO. Thickness 0.080”.
Seaming Requirement: Contractor’s option as long as it meets Firestone
standards.
Membrane Attachment: Maximum 12 ft. row spacing, fasteners spaced
maximum 6 o.c.
Edge Metal System: Firestone Coping System or as recommended otherwise
by Firestone.
EDGE OF ROOFING: CANT STRIP AS APPROVED BY FIRESTONE TPOEDGE OF ROOFING: CANT STRIP AS APPROVED BY FIRESTONE TPOEDGE OF ROOFING: CANT STRIP AS APPROVED BY FIRESTONE TPOEDGE OF ROOFING: CANT STRIP AS APPROVED BY FIRESTONE TPO
1
A3.1
1
A3.1
1
A3.2
A3.3
1
A3.5
1
A3.5
1
1
A3.4
1
A3.4
A3.4
A3.4
2
2
1 1
A3.1
1
A3.2 A3.3 A3.4
1
A1.5
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONCODE SUMMARY: CONVENIENCE STORE, VILLAGE
OF WEST CLAY, INDIANA
BUILDING TYPE:
BUILDING: TYPE II-B UNSPRINKLED
BUILDING OCCUPANCY:
M MERCANTILE, UNSPRINKLED
SQUARE FOOTAGE ALLOWED:
PER TABLE 503:
TYPE II-B MERCANTILE = 12,500 SF, 2 STORIES
ACTUAL SQUARE FOOTAGE:
BUILDING FOOTPRINT: 4,525 SF, 1 STORY
OCCUPANCY LOAD:
PER TABLE 1004.1.2:
OCCUPANCY BASED ON CONDITIONED SPACE. THIS OCCUPANCY
ELIMINATES THE COOLERS FROM REQUIRED BUILDING OCCUPANCY.
CONDITIONED SPACE = 3,345 30 SF GROSS PER PERSON = 112 PEOPLE
BUILDING EGRESS, CHAPTER 10:
MINIMUM EGRESS REQUIRED: PER SECTION 1015
M OCCUPANCY – 112 PEOPLE REQUIRES TWO ADA EXITS.
TWO PROVIDED. SEE PLANS.
EXIT DISCHARGE, CHAPTER 10:
ALL EXITS LEAD TO AN ADA STOOP AND ARE PROVIDED WITH LIGHTED EXIT
SIGNAGE. TRAVEL DISTANCE IS WELL UNDER 200 FEET.
EXIT SIGNAGE:
EXIT SIGNS SHALL MEET OR EXCEED SECTION 1011.
FIRE EXTINGUISHERS:
FIRE EXTINGUISHER SHALL BE INSTALLED AS SHOWN IN THE PLANS, PER
TABLE 906.3 OF THE INTERNATIONAL FIRE CODE, AND PER NFPA 10.
1 CLASS ABC EXTINGUISHER AND 1 K TYPE REQUIRED.56'-2 1/2"47'
-5
7
/8
"50'-3 7/8"14'-0 1/2"LIFE SAFETY PLAN
SCALE: 1/4" = 1'-0"
LS1.1
K TYPE FIRE
EXTINGUISHER
35'-
7"
7'-2 1/8"19'-1 7/8"10'-8 5/8"
25'
-
3
1
/
4
"28'-5 5/8"
ABC TYPE EXT.
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONWEST ELEVATION
SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
FACE BRICK
METAL COPING
EXTERIOR 12" x 12' TILE
TOWER
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
METAL COPING
TILE MEDALIAN AS SELECTED
BY ARCHITECT
ROOFTOP EQUIPMENT SCREENING
SEE DETAILS
EFIS
EXTERIOR LIGHT FIXTURES
MODERN FORMS "SKYSCRAPER"
EXTERIOR LIGHT FIXTURES
MODERN FORMS "SKYSCRAPER"
SECURITY ACCESS LADDER
NO ELEMENT IS TOWARD
THE GROUND WITHOUT
BEING UNLOCKED
EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
TILE MEDALIAN AS SELECTED
BY ARCHITECT
FACE BRICK SOLDIER COURSE
A2.1
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/4" = 1'-0"
EAST ELEVATION
NORTH ELEVATION
SCALE: 1/4" = 1'-0"
FACE BRICK
METAL COPING
EXTERIOR 12" x 12' TILE
TOWER
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
METAL COPING
SECURITY TYPE
ACCESS LADDER
THIS SECTION FOLDS UP
A2.2
SCALE: 1/2" = 1'-0"
1
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONW18 x 46
W18 x 46
OPEN WEB STEEL JOISTS
30 K 90 / 50
24" O.C.
4" RIGID INSULATION
CORRIGATED STEEL ROOF DECK
WMP-10 R-40 VINYL LINED INSULATION
12" SOLID CMU'S
2'-4"1'-0"2'-8"MINUMUM TOTAL OF 4'-0"
RIGID INSULATION 2" THICK
TYPICAL ALL EXTERIOR FOUNDATIONS
RIGID INSULATION "HOG-BACK"
AT EACH SCUPPER
TOP OF
MASONRY
16'-0" AFF
17'-10"TOP OF HIGH SCREEN WALL
TOP OF LOW SCREEN WALL1'-8"1'-10"19'-8" AFF
17'-10" AFF
19'-8"EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
STANDARD FACE BRICK
STANDARD FACE BRICK
STANDARD FACE BRICK
STD. 8" CMU'S
SOLDIER COURSE
TILE DIAMOND PANEL
STEEL STUD FURRING
TYPICAL FURRING
3 5/8" STEEL STUDS 24" O.C
.006 VISQUEEN
5/8" DRYWALL
2'-4"1'-0"2'-8"W18 x 46
TOP OF
MASONRY
16'-0" AFF
TPO ROOFING. SEE SPECS AND CUT SHEET
TRANSVERSE SECTION SHOWING TYPICAL WALLS
A3.1
A3.1
4" THICK CONCRETE SLAB. SEE SPECS.
MIN. 4" COMPACTED FILL
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/2" = 1'-0"
1 TRANSVERSE SECTION THRU SOUTH ENTRY DOORS
OPEN WEB STEEL JOISTS
30 K 90 / 50
24" O.C.
4" RIGID INSULATION
CORRIGATED STEEL ROOF DECK
WMP-10 R-40 VINYL LINED INSULATION
RIGID INSULATION "HOG-BACK"
AT EACH SCUPPER
2' x 2' LAY-IN ACOUSTIC CEILING AT 10'-0" AFF
BEVERAGE COOLER DOORS
SEE SPECIFICATIONS
RESTROOM DOOR
CLOSER
PRIVACY SET
SIGNAGE
ADA SIGNAGE
RESTROOM DOOR
CLOSER
PRIVACY SET
SIGNAGE
ADA SIGNAGE
MINUMUM TOTAL OF 4'-0"
RIGID INSULATION 2" THICK
4" THICK CONCRETE SLAB. SEE SPECS.
MIN. 4" COMPACTED FILL
2'-0"1'-0"2'-8"3 COURSES OF
12" SOLID CMU'S
4" SIDEWALK
SEE CIVIL DRAWINGS
SLOPE SLIGHTLY AWAY
FROM BUILDING
TYPICAL ALL EXTERIOR FOUNDATIONS
STOREFRONT ENTRANCE
SYSTEM
TOP OF
MASONRY
16'-0" AFF
17'-10"TOP OF HIGH SCREEN WALL
TOP OF LOW SCREEN WALL1'-8"1'-10"19'-8" AFF
17'-10" AFF
19'-8"EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
STANDARD FACE BRICK
STANDARD FACE BRICK
STANDARD FACE BRICK
STD. 8" CMU'S
SOLDIER COURSE
TILE DIAMOND PANEL
STEEL STUD FURRING
TYPICAL FURRING
3 5/8" STEEL STUDS 24" O.C
.006 VISQUEEN
5/8" DRYWALL
2'-4"1'-0"2'-8"W18 x 46
W18 x 46
EXTEND JOISTS INTO
ENTRANCE
PITCH POCKET OR
OTHER APPROVED CONNECTION
EXTEND INSULATION
6" STEEL STUDS 16" O.C.
R-19 FIBERGLASS INSULATION
EFIS FINISH
SURFACE
GALVANIZED 6" 20 GA.
STEEL STUD FRAMING
1 :12 SLOPE
METAL COPING
ROOF EQUIPMENT SCREENING
SEE DETAILS
TOP OF EFIS
25'-8" AFF
TPO ROOFING. SEE SPECS AND CUT SHEET
A3.2
A3.2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSCALE: 1/2" = 1'-0"
1 TRANSVERSE SECTION THRU NORTH ENTRY DOOR
OPEN WEB STEEL JOISTS
30 K 90 / 50
24" O.C.
4" RIGID INSULATION
CORRIGATED STEEL ROOF DECK
WMP-10 R-40 VINYL LINED INSULATION
RIGID INSULATION "HOG-BACK"
AT EACH SCUPPER
2' x 2' LAY-IN ACOUSTIC CEILING AT 10'-0" AFF
TOP OF
MASONRY
16'-0" AFF
17'-10"TOP OF HIGH SCREEN WALL
TOP OF LOW SCREEN WALL1'-8"1'-10"19'-8" AFF
17'-10" AFF
19'-8"BEVERAGE COOLER DOORS
SEE SPECIFICATIONS
MINUMUM TOTAL OF 4'-0"
RIGID INSULATION 2" THICK
4" THICK CONCRETE SLAB. SEE SPECS.
MIN. 4" COMPACTED FILL
1'-0"2'-8"3 COURSES OF
4" SIDEWALK
SEE CIVIL DRAWINGS
SLOPE SLIGHTLY AWAY
FROM BUILDING
TYPICAL ALL EXTERIOR FOUNDATIONS
TWO #5 REBARS CONTINUOUS
TYPICAL 1'-0"2'-8"SOLDIER
COURSE
8" CMU'S AT
ENTRANCE AREAS
3 COURSES OF
12" SOLID CMU'S
TWO #5 REBARS CONTINUOUS
TYPICAL
2'-4"
BULKHEAD ATTACHED WITH
UNISTRUT TO JOISTS
SECURITY GLASS BY OTHERS
IF OWNERS DECIDE TO INSTALL IT
8'-0" AFF
FOOD AND BEVERAGE COUNTERS
CASEWORK BY OTHERS
LAY-IN CEILING
STOREFRONT SYSTEM
SEE SPECIFICATIONS
TOS ROOFING. SEE SPECS AND CUT SHEET
12
1
STD. BRICK
LEDGE W/
REQUIRED
FLASHING
ADA PULL-OUT
A3.3
A3.3
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONEPDM ROOFING. SEE SPECIFICATIONS
4" RIGID INSULATION
CORRIGATED STEEL ROOF DECK
OPEN WEB STEEL JOISTS
30 K 90 / 50
24" O.C.
WMP-10 R-30 VINYL LINED INSULATION
ROOF EQUIPMENT SCREENING
SEE SPECS. AND OTHER DRAWINGS
LAY-IN CEILING AT 10'-0" AFF
BOND BEAM WITH TWO
CONTINUOUS #5 REBARS
R-19 FIBERGLASS
INSULATION
3 5/8" STEEL STUDS
SPECIFICATIONS AND REQUIREMENTS FOR
STOREFRONT AND ENTRANCE SYSTEMS:
This section includes windows and entrance systems.
Basis of Design and Standards:
Aluminum Framing Systems: Kawneer TRIFAB VG (VERSA GLAZE) 451,
(2” sight line)
Aluminum Entrance Doors: Kawneer 190 Narrow Stile with Finger Guards
Note: Interior and one exterior door are part of this work.
Frame Depth:4 ½”
Glass and Glazing:
Outside glazing: 1” insulated low E glazing (1/4” outside, ½” spacer, ¼”
inside glass.)
Interior glazing: ¼” tempered clear plate
Glaze to front.
Glazing materials shall be compatible with aluminum and shall be as
recommended by manufacturer.
Glazing methods
o Exterior: Elastomeric gasket and in accordance with
manufacturer’s standards.
o Interior: Snap-in type 0.062 aluminum glazing beads and a
compression wedge of dense elastomer.
Operable windows:
o Provide and install two (2) operable windows for ventilation
compatible with the storefront system. Provide shop drawings or
cut sheets for architect and/or owner review.
Stick fabrication, manufacturer’s standard parts and entrance systems.
Include SSG/Weather seal option
Include end-dams with sill flashing. Use concealed flashing, minimum 26 gage
dead-soft stainless steel, or .026” minimum extruded aluminum of alloy and type
compatible with adjacent materials.
Perimeter anchors: Aluminum.
All storefront metal to be clear anodized finish.
Exterior framing to be set in head receptor, bottom sill starter, set in caulk bed.
All framing to include perimeter caulking on interior and exterior sides.
Include all required sealants, with products selected for their intended use and
adjacent materials.
Use tempered glass where required by state and local codes and ordinances.
G.C. to provide solid wood blocking at heads/jambs for frame anchoring.
Head lintel to be self supportive, non-load-bearing, by G.C.
Field Measurements: G.C. shall advise storefront sub-contractor when field
measurements may be made in a timely fashion. Verify by field measurements
prior to fabrication. Keep a record of field measurements.
Storage:
Store products in manufacturer’s packaging unopened until ready for installation.
Store protected from soaking water, corrosion, and other damaging causes.
Entrance Systems:
Rails affixed to stiles utilizing threaded through-bolt with concealed
fasteners.
Water-rated bumper threshold, ADA compliant.
Hardware:
4” butt hinges, 1 or 2 pair determined by specified height.
3 point locking mechanism on active leaf, 2 point on inactive leaf.
Keyed cylinder with thumb-turn on interior of active leaf.
ADA compliant panic strike with tubular push/pull.
Glazing: Wet seal exterior with structural silicone per manufacturer’s
written instructions.
Weather Stripping: Manufacturer’s specified weather stripping installed
strictly in accordance with manufacturer’s written instructions.
Installation:
Installation shall be complete as intended for building use.
Protect work from damage during entire course of construction.
Install all storefront and entrance units plumb, level, and true to line without warp
or rack of frames or sash with manufacturer’s prescribed tolerances.
Weathertight Construction: Install sill members and other members in a bed of
sealant or with joint filler or gaskets, to provide weathertight construction.
Coordinate installation with wall flashings and other components of construction.
Provide support and anchor in place.
Provide all required accessories for a complete installation.
Adjust swing doors for operation in accordance with manufacturer’s written
instructions.
Clean in accordance with manufacturer’s written instructions. Remove temporary
coverings and protection of adjacent work areas. Repair or replace damaged
installed products.
Warranties:
Frames Warranty: Two (2) years from Date of Substantial Completion.
Submit manufacturer’s standard written warranty for Owner’s acceptance.
Insulating Glass: Warranted to be free from defects (excluding breakage) for a
period of five (5) years.
Submit standard written warranty for Owner’s acceptance.
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTED
BY ARCHITECT
STANDARD FACE BRICK
ALUM. ANODIZED STOREFRONT
2'-6"7'-3"EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
SOLDIER COURSE
STD. 8" CMU'S
STANDARD FACE BRICK
BOND BEAM
#5 REBAR CONTINUOUS
TOP OF
MASONRY
16'-0" AFF
4" CONCRETE FLOOR SLAB
MINUMUM TOTAL OF 4'-0"
RIGID INSULATION 2" THICK
TYPICAL ALL EXTERIOR FOUNDATIONS
2'-4"1'-0"2'-8"TWO CONTINUOUS #5 REBARS
12" SOLID CMU'S
TYPICAL AT BRICK CONDITIONS
SOLID 8" CMU
14'-8" TOM
CONTINUOUS FLASHING PER MASONRY
STANDARDS
EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
STANDARD FACE BRICK
STANDARD FACE BRICK
STD. 8" CMU'S
SOLDIER COURSE
TILE DIAMOND PANEL
STEEL STUD FURRING
HORIZONTAL REINF.
EACH THIRD CMU COURSE
EXTERIOR TILE LEDGE
COLOR: BLUE AS SELECTED
BY ARCHITECT
EXTERIOR TILE WATERTABLE
COLOR: BLUE AS SELECTEDBY ARCHITECT
STANDARD FACE BRICK
OPEN WEB STEEL JOISTS
30 K 90 / 50
24" O.C.
TOP OF
MASONRY
16'-0" AFF
14'-8" TOM
2'-6" AFF TOM
7'-3" AFF TOM
10'-0 1/2" TOM
HOG-BACK OR CRICKET SLOPED
TO SCUPPER. SEE ROOF PLAN.
HORIZONTAL REINFORCING
EVERY 2'-0" VERTICALLY
STANDARD MASONRY BRICK-LEDGE
FLASHING
MINUMUM TOTAL OF 4'-0"
RIGID INSULATION 2" THICK
TYPICAL ALL EXTERIOR FOUNDATIONS
TWO CONTINUOUS #5 REBARS
12" SOLID CMU'S
TYPICAL AT BRICK CONDITIONS
SOLID 8" CMU
SCALE: 1" = 1'-0"
1 SECTION THRU SOUTH STOREFRONT WINDOWS
SCALE: 1" = 1'-0"
SECTION THRU TYP.
NORTH WALL
1'-3"
1'-3"
MAIN BEAM CL
MAIN BEAM CL
A3.4A3.4A3.4
2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONNOTE:
THIS COOLER SYSTEM SHALL BE A PRE-ENGINEERED
UNIT FULLY OPERATIONAL. IT SHALL BE INSTALLED
STRICTLY ACCORDING TO MANUFACTURER'S WRITTEN
INSTRUCTIONS. INSTALLATION SHALL PREFERABLY BE
BY THE MANUFACTURER'S SERVICE REPRESENTATIVES.
THIS SHALL MEET ALL STATE AND LOCAL BUILING
CODES. CONSULT ARCHITECT WITH ANY QUESTIONS
OR UNUSUAL CONDITIONS ENCOUNTERED.
THE BASIS OF DESIGN IS "U.S. COOLER COMPANY"
2"x6" REDWOOD
(THERMAL-BREAK;
AROUND PERIMETER
AND DIVIDING WALLS)
VINYL SCREEDING
OR 2"x2" ALUM. ANGLE
6 MIL. VAPOR BARRIER
TAPE ALL JOINTS
COOLER WALL PANEL
4" CONCRETE SLAB
4" COMPACTED FILL
4" INSULATION OR COOLER FLOOR
PROVIDED BY COOLER MFGR.
TYPICAL EXTERIOR WALL
SEE OTHER DETAILS
SCALE: 1" = 1'-0"
1 SECTION THRU COOLER
OPEN-WEB STEEL JOISTS 24" O.C.
SEE OTHER DETAILS AND SPECIFICATIONS
UNISTRUT HANGERS FOR ALL BULKHEADS
3 5/8" STEEL STUDS 24" O.C.
5/8" DRYWALL SURFACE
SUSPENDED ACOUSTIC CEILING AT 10'-0" AFF
3 5/8" STEEL STUDS 24" O.C.
5/8" DRYWALL SURFACE
TYPICAL BULKHEAD
WALK-IN COOLER SPECIFICATIONS:
Refrigeration
A) Walk-in Refrigerator and Freezer Construction
1) General: Each panel shall consist of inner and outer metal skins, a 4” insulation
core, and be equipped with cam-action locking devices. The locking devices
shall be operable from inside the walk-in. Construction shall be as approved by
the NSF International and shall bear the NSF® Seal of Approval. All panels
shall be connected to one another by placing the tongue of the insulation core
of one panel into the groove of the core insulation of the adjacent panel. The
resultant tongue and groove joint shall be sealed at both sides by double
barreled NSF® approved gaskets. In order to avoid future swelling and mold
formation, no wood shall be permitted in the manufacture of the tongue and
groove panel profile.
(a) Wall Panels: Panel insulation shall be 4” thick, high quality, extruded
polystyrene or foamed-in-place polyurethane, modular panels joined by
not less than three (3) cam-lock devices; gasket to seal between panels;
R-28 or greater for refrigerators and R-32 or greater for freezers.
(b) Ceiling: Panel insulation shall be 4” thick, high quality, extruded
polystyrene or foamed-in-place polyurethane, modular panels joined by
not less than three (3) cam-lock devices; gasket to seal between panels;
R-28 or greater for refrigerators and R-32 or greater for freezers.
(a) Sloped Roof Package: When specified. For use on walk-ins
installed outdoors. May be required at certain snow loads. In order
to form a sloped roof profile, suitable quantities of sloped foam shall
be provided. The foam shall be cut in a manner that upon
installation, a ¼”:1’ slope is obtained. The membrane roof shall be
increased in size appropriately, in order to provide the additional
material required to properly cover the resultant profile.
(b) Roof panels shall be rated to withstand up to 90 mph winds.
(c) Finishes:
(i) Exterior Finishes:
(a) 26 gauge tan stucco embossed galvanized steel
(ii) Interior Finishes
(a) Wall Panels:
i. 26 gauge stucco embossed galvalume
(b) Ceiling Panels:
i. 26 gauge stucco embossed galvalume
(c) Floors:
i. 22 gauge smooth stainless steel
(d) Panel Dimensions: As required for layout.
2) Doors: R-25 or greater for refrigerators; R-32 or greater for freezers. Door shall
be flush mounted, positioned and hinged; provided with suitable sweep and
magnetic gaskets, door closer, one pre-wired vapor proof light fixture, light
switch with pilot light, dial thermometer, manual internal lock override, chrome
plated cam lift hinges, chrome plated door latches with strike.
(i) Outdoor Units: Doors on outdoor walk-ins shall have weather protected
light switch and door drip cap.
(ii) Freezer Doors: Freezer doors shall be identical to cooler doors, but
with the addition of UL approved heater wire on all four sides. Freezer
doors shall include a heated pressure relief port in the adjacent panel.
(b) Thermometer: See item specification for thermometers required for this
project: Thermometer installed flush-mount on hinge side of door panel.
(c) Digital Thermometer (optional): 3” round digital thermometer with probe,
installed flush-mount on hinge side of door panel.
(d) Digital Thermometer with Alarm (optional): Specifications available.
3) Pressure Relief Port: Provide heated relief port in freezers.
4) Lights: Per owner’s requirements.
(a) Fluorescent: 4’ vapor proof; optional per customer specification.
(b) Incandescent: Single bulb, vapor proof; installed on door panel.
(c) LED: Single bulb or 4’ vapor proof; optional per customer specification.
5) Installation: Dealer to install walk-in units.
(a) Drawings and Instructions: Manufacturer shall supply a set of installation
instructions and lay-out drawing. All panels shall have panel identification
corresponding with the lay-out drawing to facilitate rapid and accurate field
erection.
B) Refrigeration System: Complete operating system consisting of a condensing unit
and a evaporator coil.
1) Condensing Unit:
General: Condenser fan motors of under 1 h.p. must use electronically commutated
(EC) motors or permanent split capacitator-type (PSP) motors; splash lubrication
system using Mobil EAL Arctic 22 polyester synthetic refrigeration oil; oil sight glass;
removable oil drain plug; label indicating oil used;
(a) high/low pressure control; suction line filter; suction and discharge service
valves and copper/brass vibration isolators; receiver with fusible plug or
relief valve; liquid line shut-off valve; sight glass; molecular sieve filter
dryer; main power supply fused disconnect switch
(b) Outdoor: Weather proof housing; crank case heater and low ambient
temperature controls required to insure proper and efficient operation; fan
cycling controls where ambient temperatures do not fall below -15°; head
master valve and oversized, heated, insulated receiver and lines where
ambient temperatures fall below -15°F.
2) Evaporator Coil: Forced convection style; match to condensing unit and
suspend with air discharged parallel to the ceiling; lifetime sealed motors with
inherent motor protection; evaporator fan motors of under 1 hp and less than
460 volts must use electronically commutated (EC) motors; enclose coil section
and fans within aluminum housing
(a) Refrigerator: Air defrost
(b) Freezer and Low Temperature Refrigerator: Electric heater and controls
for positive automatic defrost
(c) Installation: Hang using plastic or nylon fasteners; spread coil weight
evenly over ceiling panels; support long span ceiling panels as required.
STEEL FINAL DESIGN SHALL BE ON A DESIGN/BUILD BASIS
4"x4"x3/8" ANGLE FOR SHEAR TRANSFER
AND STEEL DECK SUPPORT
ANGLE SHALL FOLLOW ROOF SLOPEBOND BEAM HEIGHT
VARIES WITH ROOF
SLOPE
HORIZONTAL REINFORCING
EVERY 2'-0" O.C.
2" AIR SPACE
4" CONCRETE FLOOR SLAB
SEE SPECS. AND OTHER DETAILS
TOP OF
MASONRY
16'-0" AFF
TOP OF
INTERMEDIATE BOND
BEAM 10'-0" AFFTO DO
A3.5
A3.5
THIS IS TYPICAL
ON ENTIRE PERIMETER
OF BUILDING MASONRY
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSTEEL JOISTS AND GIRDERS
PART 1 - GENERAL
1.1 SUMMARY
A. THIS SECTION INCLUDES THE FOLLOWING:
1. OPEN-WEB, K-SERIES STEEL JOISTS.
2. JOIST GIRDERS.
1.2 SUBMITTALS
A. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS OF ADEQUATE DETAIL
FOR ARCHITECT TO REVIEW PROPOSED INSTALLATION.
1.3 QUALITY ASSURANCE
A. MANUFACTURER QUALIFICATIONS: A FIRM EXPERIENCED IN
MANUFACTURING JOISTS SIMILAR TO THOSE INDICATED FOR THIS
PROJECT AND WITH A RECORD OF SUCCESSFUL IN-SERVICE
PERFORMANCE.
1. MANUFACTURER MUST BE CERTIFIED BY SJI TO MANUFACTURE
JOISTS COMPLYING WITH SJI STANDARD SPECIFICATIONS AND
LOAD TABLES.
B. WELDING (IF USED): QUALIFY PROCEDURES AND PERSONNEL
ACCORDING TO AWS D1.1, "STRUCTURAL WELDING CODE--STEEL," AND
AWS D1.3, "STRUCTURAL WELDING CODE--SHEET STEEL."
1.4 DELIVERY, STORAGE, AND HANDLING
A. DELIVER, STORE, AND HANDLE JOISTS AS RECOMMENDED IN SJI'S
"SPECIFICATIONS."
PART 2 - PRODUCTS
2.1 MATERIALS
A. STEEL: COMPLY WITH SJI'S "SPECIFICATIONS" FOR CHORD AND WEB
MEMBERS.
2.2 PRIMERS
A. PRIMER: SSPC-PAINT 15, TYPE I, RED OXIDE; FS TT-P-636, RED OXIDE;
OR MANUFACTURER'S STANDARD SHOP PRIMER COMPLYING WITH
PERFORMANCE REQUIREMENTS OF EITHER OF THESE RED-OXIDE
PRIMERS.
2.3 STEEL JOISTS
A. MANUFACTURE STEEL JOISTS ACCORDING TO SJI'S "SPECIFICATIONS,"
WITH STEEL-ANGLE TOP- AND BOTTOM-CHORD MEMBERS, AND AS
FOLLOWS:
1. MANUFACTURE K-SERIES STEEL JOISTS ACCORDING TO
"STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-
SERIES," WITH STEEL-ANGLE TOP- AND BOTTOM-CHORD
MEMBERS, UNDERSLUNG ENDS, AND PARALLEL TOP CHORD.
B. COMPLY WITH AWS REQUIREMENTS AND PROCEDURES FOR SHOP
WELDING, APPEARANCE, QUALITY OF WELDS, AND METHODS USED IN
CORRECTING WELDING WORK.
2.4 JOIST GIRDERS
A. MANUFACTURE JOIST GIRDERS ACCORDING TO "STANDARD
SPECIFICATIONS FOR JOIST GIRDERS," IN SJI'S "SPECIFICATIONS,"
WITH STEEL-ANGLE TOP- AND BOTTOM-CHORD MEMBERS; WITH END
AND TOP-CHORD ARRANGEMENTS INDICATED.
B. COMPLY WITH AWS REQUIREMENTS AND PROCEDURES FOR SHOP
WELDING, APPEARANCE, QUALITY OF WELDS, AND METHODS USED IN
CORRECTING WELDING WORK.
2.5 JOIST ACCESSORIES
A. BRIDGING: PROVIDE BRIDGING ANCHORS AND NUMBER OF ROWS OF
HORIZONTAL OR DIAGONAL BRIDGING OF MATERIAL, SIZE, AND TYPE
REQUIRED BY SJI'S "SPECIFICATIONS" FOR TYPE OF JOIST, CHORD
SIZE, SPACING, AND SPAN.
B. BRIDGING: SCHEMATICALLY INDICATED. DETAIL AND FABRICATE
ACCORDING TO SJI'S "SPECIFICATIONS."
C. SUPPLY MISCELLANEOUS ACCESSORIES, INCLUDING SPLICE PLATES
AND BOLTS REQUIRED BY JOIST MANUFACTURER TO COMPLETE JOIST
INSTALLATION.
PART 3 - EXECUTION
3.1 INSTALLATION
A. DO NOT INSTALL JOISTS UNTIL SUPPORTING CONSTRUCTION IS IN
PLACE AND SECURED.
B. INSTALL JOISTS AND ACCESSORIES PLUMB, SQUARE, AND TRUE TO
LINE; SECURELY FASTEN TO SUPPORTING CONSTRUCTION
ACCORDING TO SJI'S "SPECIFICATIONS," JOIST MANUFACTURER'S
WRITTEN RECOMMENDATIONS, AND REQUIREMENTS IN THIS SECTION.
C. BOLT JOISTS TO SUPPORTING STEEL FRAMEWORK USING CARBON-
STEEL BOLTS, UNLESS OTHERWISE INDICATED.
END OF SECTION 05210
COLUMN PER PLAN
3/4"x10"x10" @ TS 6x6
BASE PLATE
1 1/2"1 1/2"
PLANELEVATION
1 1/2"1 1/2"BOLTS (A36)
(4) - 3/4"Ø ANCHOR
2" NON-SHRINKGROUT6" PROJ.COLUMN BASE
TYPICAL TUBE
SCALE: 1/4" = 1'-0"
#5 REBARS 12" O.C.2'-8"1'-0""L" #5'S IN EACH CORNER
OF PIER
4" CONCRETE SLAB
SEE SPECS. AND DETAILS
6"x6"x3/8" TUBE STEEL COLUMNS
(TYPICAL ALL)
SCALE: 1/4" = 1'-0"
TYPICAL COLUMN FOOTER
4'-0"
#5 REBARS 12" O.C.
TYPICAL ALL
"L" #5'S IN EACH CORNER
OF PIER
24" SQUARE PIER
4'-0"4'-0"STEEL FRAMING GENERAL NOTES:
MISCELLANEOUS:
Any additional work such as canopies, overhangs, sunshades or other
architectural features requiring structural decisions and not certified by Gordon
Clark must be indicated on shop drawings certified by a professional engineer
licensed to practice in the state of Indiana.
STRUCTURAL STEEL:
Structural steel detailing, fabrication and erection shall conform to the AISC
“Specification for the Design, Fabrication, and Erection of Structural Steel for
Buildings” latest edition with amendments, and the current AISC “Code of
Standard Practice for Steel Buildings”.
Structural steel tubes and pipe shapes shall conform to ASTM A500 Grade 46.
Structural steel rolled shapes, except plates and angles, shall conform to
ASTM A500 Grade 45.
Anchor bolts shall conform to ASTM F1554 Grade 36, unless otherwise noted.
Erector shall maintain adequate temporary bracing in each direction until
diaphragm and lateral brace construction is completed.
Unless otherwise noted, bolted connections for structural steel members shall
be made with ¾” diameter high strength steel bolts conforming to ASTM A325.
Except as noted, bolted connections shall be tightened to the snug tight
condition. Bolted connections where used in brace elements shall be tightened
using the turn-of-nut condition. Connections shall conform to the “Specification
for Structural Joints using ASTM A325 or A490 Bolts”, approved by the
Research Council on Structural Connections of the Engineering Foundation.
Welding procedures shall conform to the latest edition of the American Welding
Society’s “Structural Welding Code for Steel ANSI / AWS D1.1”, Reinforcing
Steel ANSI / AWS D1.4, and Steet Steel ANSI / AWS D1.3”.
Splicing of structural steel members where not detailed on the Contract
Documents is prohibited without the prior approval of the architect as to
location, type of splice and connection to be made.
Surfaces within 2 inches of any field weld shall be free of materials that would
prevent proper welding or produce toxic fumes while welding is being done.
Beams shall be cambered upward unless indicated otherwise.
Structural steel shall be shop-painted with a rust inhibiting primer. Steel that
shall be exposed to the weather shall receive one additional finish coat.
Field measure steel prior to fabrication as often as possible.
Shop drawings shall be reviewed by the Architect for design concepts
expressed in the Contract Documents only. The Contractor shall be
responsible for all dimensions, accuracy, and fit of work.
DESIGN DATA:
The building structural has been designed in accordance with the 2012 Indiana
Building Code.
Roof Loads:
Dead Load: 13 psf
Live Load: 20 psf
Ground Snow Load (Pg): 20 psf
- Flat Roof Snow Load: (Pf): 20 psf
- Snow Exposure factor (Ce): 1.0
- Snow Load Importance Factor: (ls): 1.0
- Thermal Factor (Ct): 1.0
Wind Design Data:
Basic Wind Speed (3 second gust): 115 mph ULT; 90 mph Nominal
Risk Category: II
Wind Exposure Category: C
Internal Pressure Coefficient: +/- .18
Base Wind Pressure: 18.8 psf
Seismic Design Data:
Risk Category: II
Seismic Site Class: D
0.2 sec. Mapped MCE Ground Motion (Ss): 0.148
1.0 sec. Mapped MCE Ground Motion (S1): 0.082
0.2 sec. 5% Damped Spectral Response Acceleration (Sds): 0.157
1.0 sec. 5% Damped Spectral Response Acceleration (Sd1): 0.131
Seismic Design Category: B
Basic structural and seismic resisting system: Ordinary System Not
Specifically Detailed for Seismic Resistance.
Analysis Procedure: Equivalent lateral force procedure
Response Modification Coefficient ®: 3
Seismic response Coefficient (Cs): .052
Slab Capacity:
Post Load = 16K (Min. Base = 4” x 3”)
Uniform Loading = 1.0 K/sf
Back-to-Back Post Load = 12K (Min. Base = 4”x3”)
A4.1
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONADA TRANSACTION
PULL OUT DRAWER WITH
MIN. 30" WIDE x 24" DEEP
FOOTPRINT
DRAWER
POS BY OTHERS POS BY OTHERS
SECURITY GLASS INSTALLATION BY OTHERS
NOT PART OF WORK OF THIS SET OF DOCUMENTS
SCALE: 1/2" = 1'-0"
ELEVATION OF CASHIER AREA
OWNER'S OPTION. VERIFY.
3 COMPARTMENT SINK
FRP OR OTHER NON-ABSORBENT SURFACE
HAND SINK / 3 COMPARTMENT SINK / AND MOP SINK ELEVATION
SCALE: 1/2" = 1'-0"
MOP SINK
WATER HEATER
ABOVE HAND SINK
ADA URINAL
ADA WC
ADA SINK
60" x 60" CLEAR SPACE
30" x 48"
CLEAR SPACE
48" x 30"
CLEAR SPACE
ADA WC
ADA SINK
48" x 30"
CLEAR SPACE
60" x 60" CLEAR SPACE
SCALE: 1/2" = 1'-0"
ADA URINAL ADA WC
RESTROOM INTERIOR ELEVATIONS
SCALE: 1/2" = 1'-0"
RESTROOM DETAIL FLOOR PLAN
7'-6"4 3/4"6'-3"4 3/4"
COOLER WALLS
SEE SPECIFICATIONS
7'-10"3/0 x 7/0 HM FRAME
FLUSH WOOD
DOOR
ACCESSIBILITY REQUIREMENTS:
MIRRORS:
MIRRORS SHALL BE FLAT AGAINST THE WALL, WITH THE BOTTOM
OF THE MIRROR SURFACE NO MORE THAN 40 INCHES ABOVE
FINISH FLOOR. THE TOP EDGE OF THE MIRROR SURFACE SHALL
BE A MINIMUM OF 74 INCHES ABOVE FINISH FLOOR.
LAVATORIES AND SINKS:
WATER SUPPLY AND DRAINPIPES UNDER LAVATORIES AND SINKS
SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE
SURFACES UNDER LAVATORIES AND SINKS.
ACCESSIBLE TOILET WATER CLOSETS:
CENTERLINE OF WATER CLOSET SHALL BE 16” MINIMUM TO 18”
MAXIMUM FROM THE SIDEWALL OR PARTITION.
CONTRACTOR SHALL CONFIRM IN THE FIELD THAT THE
CLEARANCES IN A WATER CLOSET STALL SHALL BE 60 INCHES
MINIMUM MEASURED PERPENDICULAR FROM THE SIDEWALL AND
REAR WALL. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
NOTIFY ARCHITECT IMMEDIATELY IF AN OBSTRUCTION
CONFLICTS WITH THE ABOVE REQUIREMENTS.
HEIGHT: THE HEIGHT OF ACCESSIBLE WATER CLOSETS SHALL BE
17 INCHES MINIMUM TO 19 INCHES MAXIMUM MEASURED TO THE
TOP OF THE TOILET SEAT. SEATS SHALL NOT BE SPRUNG TO
RETURN TO A LIFTED POSITION.
FLUSH CONTROLS SHALL BE LOCATED ON THE TRANSFER SIDE
OF THE WATER CLOSET.
ACCESSIBLE URINALS:
URINALS SHALL BE WALL-HUNG TYPE WITH THE RIM 17 INCHES
MAXIMUM ABOVE FINISH FLOOR. URINALS SHALL PROVIDE A
MINIMUM DEPTH OF 13 1/3 INCHES MEASURED FROM THE OUTER
FACE OF THE URINAL RIM TO THE BACK OF THE FIXTURE.
CONFIRM THAT THERE IS CLEAR FLOOR SPACE OF 48 INCHES
PERPENDICULAR FROM REAR WALL OF URINAL, AND 30 INCHES
CENTERED ON ACCESSIBLE URINAL. IF A CONFLICT IS PRESENT,
NOTIFY ARCHITECT.
GRAB BARS:
GRAB BARS SHALL BE INSTALLED STRICTLY ACCORDING TO
ARCHITECT’S DRAWING SHOWING ACCESSIBILITY DIMENSIONS
OR THE LATEST ADA REQUIREMENTS, WHICHEVER IS STRICTER.
WHERE WALL SPACE PERMITS, A 36 LONG GRAB BAR SHALL BE
INSTALLED ON THE REAR WALL OF THE WATER CLOSET AREA,
WITH THE ADDITIONAL LENGTH ON THE TRANSFER SIDE OF THE
WATER CLOSET.
GENERAL TOILET ROOM ELEMENTS:
IF SOAP AND TOWEL DISPENSERS ARE PROVIDED, THEY MUST BE
LOCATED WITHIN THE REACH RANGES IN ADA STANDARDS.TYPICALACCESSIBLE TOILET1'-5"2'-0"3'-0"39" - 41"ACCESSIBLE TOILETTYPICAL1'-6"1'-5"2'-0"3'-0"39" - 41"1'-6"TYPICALSTANDARD TOILET1'-3"2'-0"TYPICALSTANDARD TOILET2'-0"TYPICALACCESSIBLE URINAL1'-6"TYPICALSTANDARD URINAL2'-0"TYPICALACCESSIBLE LAVATORY2'-10" MAX.3'-4" MAX TO BOTTOM OF MIRRORTYPICALSTANDARD LAVATORY2'-10"3'-4" MAX TO BOTTOM OF MIRROR6'-0" MIN. TO TOP OF MIRROR4'-0"FIRE EXTINGUISHERWITH CABINET4'-0"FIRE EXTINGUISHER2'-9"WATER COOLERACCESSIBLE3'-0"WATER COOLER5'-6"COAT HOOKS3'-6"PUSH PLATESHEIGHTCOUNTER3'-0"PAPER TOWEL DISPENSER1'-0"6'-8"80" AFF TO CENTERLINEHORN AND/OR STROBE4'-0"WALL SWITCHESINSTALL ALL REQUIRED BLOCKING IN WALL FOR
GRAB BARS, MIRRORS, AND ACCESSORIES
9 FT
8 FT
7 FT
6 FT
5 FT
4 FT
3 FT
2 FT
1 FT
FLOOR
LINE
5'-0"
REQUIRED CLEAR SPACE
WITH NO ENCROACHMENT
1'-6"
5'-0"
REQUIRED CLEAR SPACE
WITH NO ENCROACHMENT
1'-6"1'-3"
MIN.
1'-3"
MIN.
1'-3"
MIN.
30" x 48" CLEAR FLOOR
SPACE IN FRONT OF LAV
39" - 41"
4'-6"
1'-0"3'-6"
8"
6"3'-0"BOTTOM OF MIRROR
TO DO
A4.2
A4.2
A4.2
A4.2A4.2
1 2
3
4
ADA WC
60" MIN24"MIN30" MIM36" MIN48" MAXFOR ACCESSIBLE USE3'-0"48"18" MIN11"56" MIN WALL HUNG59" MIN FLOOR MOUNT3'-2"PUSH PLATES,HANDLES& PUSH BARS48"VIEWERS/SIGNAGE4'-0"17'-19"DEAD BOLTS5'-0"19" MIN3'-4" MAX3'-3 1/2" MAX2'-7"2'-3"9"33"-36"39"-41"33"-36"1 1/2"CLR17" MIN19" MIN3'-2 5/8"60" MIN4'-0" MAXMAXIMUM SIDE REACH1'-5"42" MIN*54" MIN4'-0"42" MIN**AT TOP OF CABINET1/4"3'-6"48" MIN48" MIN *48" MAX9" MIN.60" MIN27" MIN.34" MAX.29" MIN.40" MAX.TO BOTTOM OF5'60" MIN48" MINREFLECTING SURFACE60" MINX > 842" MIN5'-0"48"48" MIN2'-6"X > 84'-0"60" MIN48" MIN2'-4"2'-6"4'-0"15" MIN60" MIN7'-0"4'-0" MAXMAXIMUM SIDE REACH1/4" MAX.5'-0"3'-8" AT ADA STALL9"48" MAX4'-6"
MIN.
4'-0"
10"
39"-41"
1'-0"3'-6"
MIN.
CL
6"
1'-0"
MIN.
3'-0"
MIRROR
2'-6"MAX.
17"-19"
7"
4'-0"4'-0"
WC 1'-6"
WC URINAL FEC FE 8"MIN.
KNEE CLEARANCE
6"MAX
17" MIN.TOE CLEARANCE A. FORWARD REACH TO WALL
MOUNTED OBJECTS
CL
1'-6"1'-6"9"
ACCESSIBLE SIGNAGE
FOR RESTROOMS OR
TACTILE EXIT SIGN AT
EXIT LOCATIONS
8" MAX
L
CL
MIRROR
CL B.O. FRAME
CL
CL
CL
A. FORWARD REACH TO
WALL MOUNTED OBJECTS
4'-0"
BABY CHANGING TABLE
Fixture and Accessory Mounting Heights
NTS
(A-G) MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS
48" MIN 16"-18"16"-18"
(A) FRONT APPROACH
PULL SIDE
18"
MIN
(B) FRONT APPROACH
PUSH SIDE
12"
MIN*
* IF BOTH
CLOSER AND
LATCH AR
PROVIDED
(C) HINGE APPROACH
PULL SIDE
(1-2) MANEUVERING CLEARANCE AT DOORWAYS WITHOUT DOORS
(1) FRONT APPROACH (2) SIDE APPROACH
COMPRESSED CARPET
1/4" MAX. BELOW
THRESHOLD
36" MIN
1/2" MAX.
PILE
HEIGHT
TRANSITION BETWEEN FLOOR FINISHES
60" MIN CLEAR
FLOOR
SPACE
60" MIN.
CLEAR
FLOOR
SPACE
60" MIN
12"
42" MIN
60" MIN
17" MIN.
CLEAR FLOOR SPACES
(X-Z) TWO DOORS IN A SERIES
(G) LATCH APPROACH
PUSH SIDE
19" MAX.
NOTE:
12"
MIN 36" MIN
12"
MIN
PROVIDE PRIVACY DOOR LOCK WHEN IT IS A
PRIVATE TOILET OR FOR UNISEX USE.
24"
MIN
*48" MIN IF
CLOSER IS
PROVIDED
(X)
60" MIN
(Y)
DOOR
WIDTH 48" MIN
DOOR
WIDTH
(Z)
48" MIN
DOOR
WIDTH
NOTES:
1. 1/2" MAXIMUM TOTAL HEIGHT WITH 1/4" MAXIMUM VERTICAL
CHANGE AT EDGE.
2. 1:2 SLOPED BEVEL REQUIRED IF LEVEL CHANGE IS OVER
1/4" VERTICAL LEVEL CHANGE.
3. 1/4" MAXIMUM VERTICAL LEVEL CHANGE.
LEVEL CHANGES
MIN*
22"
MIN
(D) HINGE APPROACH
PULL SIDE
(E) HINGE APPROACH
PUSH SIDE * IF BOTH
CLOSER AND
LATCH ARE
PROVIDED
** 48" MIN IF
BOTH CLOSER
AND LATCH
PROVIDED
(F) LATCH APPROACH
PULL SIDE
(a) PULL SIDE
* 54" MIN IF
CLOSER IS
PROVIDED
24"
MIN
18"
MIN
(b) PUSH SIDE (c) PUSH SIDE, DOOR
PROVIDED WITH BOTH
CLOSER AND LATCH
1/2"
12"
MIN THRESHOLD
1/4"
MAX.
MAX.
THRESHOLD
FIN. FLOOR
LEVEL
Clear Floor Space
NTS
Maneuvering Clearances at Doors
NTS
Threshold Details
NTS
36"36"
DETAIL
1/4"3/4"
TYPICAL DETECTABLE
WARNING TILES @
CURB RAMPS - SEE
TYPICAL
ACCESSIBILITY
NOTES SHEET FOR
MORE INFO.
GROOVED WARNING BORDER DEPRESS
CURB 1", AS
REQ.
36"
LINE OF CURB
AS OCCURS
LINE OF FRONT
OF REQ'D
PARKING SPACE.
1:10 MAX.
SLOPE
(TYPICAL)
CURB RAMP DETAILS
Exterior Ramp Details
NTS
LINE OF
OBSTRUCTION OR
EDGE OF WALK
AREA AS OCCURS,
TYP.
36" 60"
1:12 SLOPE
MAX. TYP.
4. EXPOSED HOT WATER PIPE AND DRAIN PIPE ON LAVATORY SHALL BE INSULATED OR OTHERWISE
SURFACES UNDER THE LAVATORY.
5. FAUCETS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
PINCHING OR TWISTING OF THE WRIST . LEVER-OPERATED, PUSH TYPE AND ELECTRONICALLY
CONTROLLED ARE ACCEPTABLE. SELF CLOSING VALVES SHALL REMAIN OPEN 10 SEC. MIN.
6. G.C. IS TO PROVIDE WOOD BLOCKING IN WALL AT MOUNTING POINTS OF ACCESSORIES TYPICAL.
7. ACCESSIBLE RESTROOM SIGNAGE AND SIGNS ON DOORS PROVIDED BY GC.
General Notes
NTS
1. ALL SIGNAGE AND PICTOGRAMS SHALL COMPLY WITH CHAPTER 7 OF ANSI A117.1-2009.
2. ALL DOORS SHALL COMPLY WITH SECTION 404 OF ANSI A117.1-2009.
3. FLUSH CONTROL SHALL BE MOUNTED NO HIGHER THEN 44" A.F.F. AND SHALL BE OPERABLE WITH
ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST.
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONA4.3
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONA. Deliver materials to the project site clearly marked for proper
identification.
B. Receive, handle and store materials in conformance with the
manufacturers printed instructions.
1.
2.
as beams or trusses.
Position bundles of tubing parallel to the slope of the roof
and block prior to opening to prevent the tubing from rolling
down the roof slope when unbundled.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Design Loads: Comply with Building Code for site location and
building height.
1.
2.
Design to resist ASCE 7 - Minimum Design Loads for
Buildings and Other Structures, using the latest published
ASCE version.
Design all materials, assembly and attachments to resist
snow, wind, suction and uplift loading at any point without
damage or permanent set.
B. Structural Design: Prepare structural design calculations for
screen framing and attachment to structure including reactions at
base supports for verification of roof structure by Architect.
C. All welds to be performed by an AWS certified welder. Valid
certification to be provided.
2.2 MANUFACTURERS
A. Proposed Manufacturer: RoofScreen Mfg., which is located at:
347 Coral St.; Santa Cruz, CA 95060; Toll Free Tel: 866-766-
3727; Tel: 831-421-9230; Fax: 866-253-0738; Email: request info
(info@roofscreen.com); Web: www.roofscreen.com.
2.3 FABRICATION
A. Fit and shop assemble items in largest practical sections, for
delivery to site.
B. Fabricate items with joints tightly fitted and secured.
C. Supply components required for anchorage of fabrications.
Fabricate anchors and related components of same material and
finish as fabrication, except where specifically noted otherwise.
D. Fabricate system components so that portions of screen can be
dismantled for repairs to equipment being screened and for
future roof replacement.
E. Trim and Closures: Fabricated from 24 gauge metal and finished
with the manufacturer’s standard coating system.
PART 3 - EXECUTION
3.1 EXAMINATION
A. If preparation is the responsibility of another installer, notify
Architect of unsatisfactory preparation before proceeding.
B. Do not begin installation until conditions have been properly
prepared.
3.2 INSTALLATION
A.
B.
Install in accordance with manufacturer's instructions.
Install components plumb and level, accurately fitted, free from
distortion or defects.
C. Anchor fabrications to structure as indicated.
D. Separate dissimilar metals and use gasketed fasteners, isolation
shim, or isolation tape to eliminate possibility of corrosive or
electrolytic action between metals.
E. Exercise care when installing components so as not to damage
finish surfaces. Touch up as required to repair damaged finishes.
F.Install flashing boots at base supports as required to provide a
watertight connection. Install as recommended by the roof
membrane manufacturer.
G. Remove all protective masking from material immediately after
installation.
3.3 CLEANING AND PROTECTION
A. Replace metal wall panels and framing members that have been
damaged or have deteriorated beyond successful repair by finish
touchup or similar minor repair procedures.
A. Stand-alone roof equipment screens and supporting steel
framework. Screens shall be designed to attach to the roof
structure and not the equipment being screened.
B. Roof screen accessories.
1.2 RELATED SECTIONS
A. Roof Top HVAC Equipment.
1.3 COORDINATION
A. Coordinate Work with other operations and installation of roofing
materials to avoid damage to installed insulation and membrane
materials.
1.4 ACTION SUBMITTALS
A. Product Data: Manufacturer's data sheets on each product to be
used, including:
1.
2.
3.
Preparation instructions and recommendations.
Storage and handling requirements and recommendations.
Installation methods.
B. Shop Drawings: Layout and erection drawings showing typical
cross sections and dimensioned locations of all frames and base
supports. Include erection drawings, elevations, and details
where applicable. Indicate welded connections using standard
AWS A2.4 welding symbols. Indicate net weld lengths.
1.5 INFORMATIONAL SUBMITTALS
A. Design Calculations: 3 copies of structural design calculations for
structural components and components resisting wind loads with
seal and signature of professional engineer licensed in the State
of Indiana
B. Manufacturer's Certificates: Certify products meet or exceed
specified requirements.
C. Warranties: 3 signed copies.
1.6 DELIVERY, STORAGE, AND HANDLING
ROOF SCREENS:
A4.4
ELECTRICAL SYSTEM GROUNDING REQUIREMENTS:
STRICTLY FOLLOW NEC 250.50 AND 250.52.
INSTALL GROUNDING ELECTRODE ACCORDING TO THE FOLLOWING LIST:
WATER PIPE IF 10 FEET OR MORE OF METAL WATER PIPE IS IN CONTACT
WITH THE EARTH.
METAL FRAME OF THE BUILDING OR STRUCTURE WHERE ANY OF THE
FOLLOWING FOUR METHODS ARE USED TO MAKE AN EARTH
CONNECTION:
1. CONCRETE-ENCASED ELECTRODE IN AT LEAST 2 INCHES OF
CONCRETE LOCATED WITHIN OR NEAR THE BOTTOM OF A
CONCRETE FOUNDATION OR FOOTING THAT IS IN INDIRECT
CONTACT WITH THE EARTH.
2. GOUND RING ENCIRCLING THE BUILDING OR STRUCTURE IN
DIRECT CONTACT WITH THE EARTH.
3. ROD OR PIPE ELECTRODE NOT LESS THAN 8 FEET IN LENGTH.
4. OTHER LOCAL UNDERGROUND SYSTEMS SUCH AS PIPING,
UNDERGROUND TANKS AND UNDERGROUND WELL CASING.
COMMUNICATIONS EQUIPMENT: COMMUNICATIONS EQUIPMENT SHALL BE
GROUNDED TO BUILDING GROUNDING ELECTRODE SIMILAR TO OTHER
ELECTRICAL EQUIPMENT. FOLLOW NEC 800.100 (B).
ALL GROUNDING ELECTRODES THAT ARE PRESENT AT THIS BUILDING
STRUCTURE SHALL BE BONDED TOGETHER TO FORM THE GROUNDING
ELECTRODE SYSTEMS.
BOND ALL GROUNDING ELECTRODES THAT ARE PRESENT AT THIS
BUILDING STRUCTURE TOGETHER TO FORM THE GROUNDING
ELECTRODE SYSTEM. GROUNDING ELECTRODES THAT MAY BE PRESENT
AT THIS BUILDING INCLUDE GROUNDING ELECTRODE RODS, CONCRETE
ENCASED ELECTRODES SUCH AS BUILDING FOUNDATION REBAR,
UNDERGROUND METAL WATER PIPES, AND METAL FRAME OF THE
BUILDING INCLUDING STRUCTURAL STEEL COLUMNS.
SEE GROUNDING DETAIL THAT IS A PART OF DRAWINGS OF THIS SET.
NOT PERMITTED:
METAL UNDERGROUND GAS PIPING.
ALUMINUM ELECTRODES
MASONRY SPECIFICATION AND REQUIREMENTS:
UNIT MASONRY SPECIFICATIONS AND REQUIREMENTS:
SECTION 04810 - UNIT MASONRY ASSEMBLIES
o THIS SECTION INCLUDES UNIT MASONRY ASSEMBLIES CONSISTING
OF THE FOLLOWING:
CONCRETE MASONRY UNITS.
MORTAR AND GROUT.
REINFORCING STEEL.
MASONRY JOINT REINFORCEMENT.
TIES AND ANCHORS.
EMBEDDED FLASHING.
MISCELLANEOUS MASONRY ACCESSORIES.
QUALITY ASSURANCE:
o COMPLY WITH “SPECIFICATIONS FOR MASONRY
CONSTRUCTION” ACI 530.1/ASCE 6.88, MOST CURRENT
EDITION. CONCRETE MASONRY UNITS (CMU’S) FOR ALL
FINISHING SHALL CONFORM TO ASTM C90.
DELIVERY, STORAGE, AND HANDLING
o STORE MASONRY UNITS AND RELATED PRODUCTS ON ELEVATED
PLATFORMS IN A DRY LOCATION. IF UNITS ARE NOT STORED IN
AN ENCLOSED LOCATION, COVER TOPS AND SIDES OF STACKS
WITH WATERPROOF SHEETING, SECURELY TIED. IF UNITS
BECOME WET, DO NOT INSTALL UNTIL THEY ARE DRY.
PROJECT CONDITIONS
o PROTECTION OF MASONRY: DURING CONSTRUCTION, COVER
TOPS OF WALLS, PROJECTIONS, AND SILLS WITH WATERPROOF
SHEETING AT END OF EACH DAY'S WORK. COVER PARTIALLY
COMPLETED MASONRY WHEN CONSTRUCTION IS NOT IN
PROGRESS.
o STAIN PREVENTION: PREVENT GROUT, MORTAR, AND SOIL FROM
STAINING THE FACE OF MASONRY TO BE LEFT EXPOSED OR
PAINTED. IMMEDIATELY REMOVE GROUT, MORTAR, AND SOIL
THAT COME IN CONTACT WITH SUCH MASONRY.
o COLD-WEATHER REQUIREMENTS: DO NOT USE FROZEN
MATERIALS OR MATERIALS MIXED OR COATED WITH ICE OR
FROST. DO NOT BUILD ON FROZEN SUBSTRATES. REMOVE AND
REPLACE UNIT MASONRY DAMAGED BY FROST OR BY FREEZING
CONDITIONS. COMPLY WITH COLD-WEATHER CONSTRUCTION
REQUIREMENTS CONTAINED IN SECTION 2104.3 OF THE
UNIFORM BUILDING CODE.
o HOT-WEATHER REQUIREMENTS: PROTECT UNIT MASONRY
WORK WHEN TEMPERATURE AND HUMIDITY CONDITIONS
PRODUCE EXCESSIVE EVAPORATION OF WATER FROM MORTAR
AND GROUT. PROVIDE ARTIFICIAL SHADE AND WIND BREAKS
AND USE COOLED MATERIALS AS REQUIRED.
PRODUCTS
CONCRETE MASONRY UNITS
o GENERAL: PROVIDE SHAPES INDICATED AND AS FOLLOWS:
PROVIDE SPECIAL SHAPES FOR LINTELS, CORNERS,
JAMBS, SASH, CONTROL JOINTS, HEADERS, BONDING, AND
OTHER SPECIAL CONDITIONS.
PROVIDE CORNER UNITS FOR OUTSIDE CORNERS, UNLESS
OTHERWISE INDICATED.
o CONCRETE MASONRY UNITS: UBC STANDARD 21-4 AND AS
FOLLOWS:
EXPOSED FACES: MANUFACTURER'S STANDARD COLOR
SMOOTH FACE UNITS NOT CHIPPED OR DAMAGED.
REINFORCING STEEL
o UNCOATED STEEL REINFORCING BARS: ASTM A 615/A 615M;
ASTM A 616/A 616M, INCLUDING SUPPLEMENT 1; OR
ASTM A 617/A 617M, GRADE 60.
MASONRY JOINT REINFORCEMENT
o GENERAL: UBC STANDARD 21-10 AND AS FOLLOWS:
PROVIDE IN LENGTHS OF NOT LESS THAN 10 FEET, WITH
PREFABRICATED CORNER AND TEE UNITS WHERE
INDICATED.
TIES AND ANCHORS, GENERAL
o GENERAL: FOLLOW BEST MASONRY PRACTICES. CONSULT WITH
ARCHITECT IF NEEDED.
EMBEDDED FLASHING MATERIALS
METAL FLASHING: FOLLOW BEST MASONRY PRACTICES FOR BOTH
EXPOSED AND CONCEALED FLASHING. SUBPARAGRAPH BELOW IS AN
EXAMPLE ONLY; REVISE IF OTHER LAMINATED PRODUCTS ARE
REQUIRED. EXAMINATION
o BEFORE INSTALLATION, EXAMINE ROUGH-IN AND BUILT-IN
CONSTRUCTION TO VERIFY ACTUAL LOCATIONS OF PIPING
CONNECTIONS.
INSTALLATION, GENERAL
DRAW BLOCKS FROM MORE THAN ONE PALLET AT A TIME DURING
CONSTRUCTION. ALL EXTERIOR MORTAR SHALL INCLUDE W.R. GRACE
DRY-BLOCK WATER-REPELLANT ADDITIVE ADDED TO EACH BATCH IN
THE APPROPRIATE DOSAGE RATES FOR MORTAR BEING USED. USE
ADDITIVE STRICTLY IN CONFORMANCE WITH MANUFACTURER’S
WRITTEN INSTRUCTIONS.
LAY UNITS USING BEST MASONRY PRACTICES. LAY ALL BLOCK
LEVEL. PLUMB, AND TRUE. USE ONLY QUALITY UNITS, WITH NO
DAMAGE. UNITS SHALL HAVE UNIFORM, 3/8” JOINTS BOTH
HORIZONTALLY AND VERTICALLY ON THE FINISHED SIDE OF THE WALL.
TOOL JOINTS NEATLY AFTER THEY ARE FINGER-HARD TO MAK THEM
STRAIGHT AND UNIFORM. SIZE AND PLACE CUT PIECES
APPROXIMATELY TO MAINTAIN CONSISTENCY AND BOND. COMPLETE
MASONRY CONSTRUCTION USING PROCEDURES AND WORKMANSHIP
CONSISTENT WITH THE BEST MASONRY PRACTICES.
CONSTRUCTION TOLERANCES
o COMPLY WITH TOLERANCES IN ACI 530.1/ASCE 6/TMS 602
CONTROL AND EXPANSION JOINTS
o GENERAL: INSTALL CONTROL AND EXPANSION JOINTS IN UNIT
MASONRY WHERE INDICATED.OR WHERE REQUIRED BY BEST
MASONRY STANDARDS. BUILD-IN RELATED ITEMS AS MASONRY
PROGRESSES. DO NOT FORM A CONTINUOUS SPAN THROUGH
MOVEMENT JOINTS UNLESS PROVISIONS ARE MADE TO
PREVENT IN-PLANE RESTRAINT OF WALL OR PARTITION
MOVEMENT.
REPAIRING, POINTING, AND CLEANING
o NO CHIPPED, BROKEN, OR DEFORMED CONCRETE BLOCK SHALL
BE ACCEPTED IN EXPOSED BLOCK AREAS. CONTRACTOR SHALL
REPLACE BLOCK, WHICH DOES NOT MEET THESE
SPECIFICATIONS, AT CONTRACTOR’S
o COMPLETED WALLS WITH A DETERGENT MASONRY CLEANER STRICTLY
FOLLOWING MANUFACTURER’S WRITTEN INSTRUCTIONS, INCLUDING
THOROUGH RINSING. DO NOT USE ACIDS OR ABRASIVES ON FINISHED
SURFACES. FOR STUBBORN MASONRY STAINS OR SMEARS, A 3:1 SOLUTION OF
SURE KLEAN BURNISHED CUSTOM MASONRY CLEANER BY PROSOCO MAY BE
USED AS LONG AS WALLS RE THOROUGHLY WETTED BEFORE APPLYING THE
CLEANING SOLUTION AND THROUGHLY RINSED WITH CLEAN WATER
IMMEDIATELY AFTER WASHING. FAILURE TO FOLLOW MANUFACTURER’S
INSTRUCTIONS CAN RESULT IN PERMANENT DAMAGE TO THE FINISHED FACES
AND CAN RESULT IN CONTRACTOR-REPLACEMENT. DO NOT POWER WASH.
O PROTECTION DURING CONSTRUCTION: COVER WALLS EACH DAY AFTER
INSTALLATION TO KEEP OPEN WALLS PROTECTED AND DRY. AFTER UNITS ARE
INSTALLED THEY SHOULD BE PROTECTED FROM DAMAGE BY OTHER TRADES
PREFORMING OPERATIONS THAT CAN STAIN OR OTHERWISE DAMAGE THE
FINISHED SURFACES.
EXAMINATION
o BEFORE INSTALLATION, EXAMINE ROUGH-IN AND BUILT-IN
CONSTRUCTION TO VERIFY ACTUAL LOCATIONS OF PIPING
CONNECTIONS.
INSTALLATION, GENERAL
DRAW BLOCKS FROM MORE THAN ONE PALLET AT A TIME DURING
CONSTRUCTION. ALL EXTERIOR MORTAR SHALL INCLUDE W.R. GRACE
DRY-BLOCK WATER-REPELLANT ADDITIVE ADDED TO EACH BATCH IN
THE APPROPRIATE DOSAGE RATES FOR MORTAR BEING USED. USE
ADDITIVE STRICTLY IN CONFORMANCE WITH MANUFACTURER’S
WRITTEN INSTRUCTIONS.
LAY UNITS USING BEST MASONRY PRACTICES. LAY ALL BLOCK
LEVEL. PLUMB, AND TRUE. USE ONLY QUALITY UNITS, WITH NO
DAMAGE. UNITS SHALL HAVE UNIFORM, 3/8” JOINTS BOTH
HORIZONTALLY AND VERTICALLY ON THE FINISHED SIDE OF THE WALL.
TOOL JOINTS NEATLY AFTER THEY ARE FINGER-HARD TO MAK THEM
STRAIGHT AND UNIFORM. SIZE AND PLACE CUT PIECES
APPROXIMATELY TO MAINTAIN CONSISTENCY AND BOND. COMPLETE
MASONRY CONSTRUCTION USING PROCEDURES AND WORKMANSHIP
CONSISTENT WITH THE BEST MASONRY PRACTICES.
CONSTRUCTION TOLERANCES
o COMPLY WITH TOLERANCES IN ACI 530.1/ASCE 6/TMS 602
CONTROL AND EXPANSION JOINTS
o GENERAL: INSTALL CONTROL AND EXPANSION JOINTS IN UNIT
MASONRY WHERE INDICATED.OR WHERE REQUIRED BY BEST
MASONRY STANDARDS. BUILD-IN RELATED ITEMS AS MASONRY
PROGRESSES. DO NOT FORM A CONTINUOUS SPAN THROUGH
MOVEMENT JOINTS UNLESS PROVISIONS ARE MADE TO
PREVENT IN-PLANE RESTRAINT OF WALL OR PARTITION
MOVEMENT.
REPAIRING, POINTING, AND CLEANING
o NO CHIPPED, BROKEN, OR DEFORMED CONCRETE BLOCK SHALL
BE ACCEPTED IN EXPOSED BLOCK AREAS. CONTRACTOR SHALL
REPLACE BLOCK, WHICH DOES NOT MEET THESE
SPECIFICATIONS, AT CONTRACTOR’S
o COMPLETED WALLS WITH A DETERGENT MASONRY CLEANER STRICTLY
FOLLOWING MANUFACTURER’S WRITTEN INSTRUCTIONS, INCLUDING
THOROUGH RINSING. DO NOT USE ACIDS OR ABRASIVES ON FINISHED
SURFACES. FOR STUBBORN MASONRY STAINS OR SMEARS, A 3:1 SOLUTION OF
SURE KLEAN BURNISHED CUSTOM MASONRY CLEANER BY PROSOCO MAY BE
USED AS LONG AS WALLS RE THOROUGHLY WETTED BEFORE APPLYING THE
CLEANING SOLUTION AND THROUGHLY RINSED WITH CLEAN WATER
IMMEDIATELY AFTER WASHING. FAILURE TO FOLLOW MANUFACTURER’S
INSTRUCTIONS CAN RESULT IN PERMANENT DAMAGE TO THE FINISHED FACES
AND CAN RESULT IN CONTRACTOR-REPLACEMENT. DO NOT POWER WASH.
O PROTECTION DURING CONSTRUCTION: COVER WALLS EACH DAY AFTER
INSTALLATION TO KEEP OPEN WALLS PROTECTED AND DRY. AFTER UNITS ARE
INSTALLED THEY SHOULD BE PROTECTED FROM DAMAGE BY OTHER TRADES
PREFORMING OPERATIONS THAT CAN STAIN OR OTHERWISE DAMAGE THE
FINISHED SURFACES.
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONMAIN SERVICE GROUNDING
MAIN BONDING JUMPER
#2/0 BARE COPPER
CONDUCION PER NEC 250.28
CADWELD
4 BARE COPPER GROUNDING
ELECTRODE CONDUCTOR
(NEC 250.66)
MINIMUM OF 20'-0" OF 1/2" REGAR
NEC 250.52(A)(3)
IN BUILDING WALL FOOTING.
BONDING JUMPER TO
ENCLOSURE. SIZE PER
NEC 250.102(C)
COMMUNICATIONS EQUIPMENT
BONDED TO ELECTRICAL SYSTEM
ELECTRODE PER 800.100 (B).
3/4" DIAMETER x 10 FEET LONG
COPPERCLAD GROUND RODS,
MINIMUM 20 FEET APART.
NEW 250.52
GROUNDING BUS
ONE #6 TO PHONE BOARD
PER NEC 800.40(D)
BUILDING STRUCTURAL
STEEL, NEC 250.52(A)(2)
CADWELD
VALVE,
METER,
OR UNION
COLD WATER SERVICE
ENTRANCE (PROVIDE SIMILAR
CONNECTION TO FIRE
PROTECTION WATER SERVICE
ENTRANCE) NEC 250.53(D)
SUPPLY SIDE
PIPE CLAMP (TYPICAL)
JUMPER
GROUNDING NOTES:
ALL GROUNDING SHALL BE INSTALLED IN
ACCORDANCE WITH ARTICLE 250.50 OF THE
NATIONAL ELECTRIC CODE.
ALL GROUNDING CABLES SHALL BE 4AWG COPPER
OR LARGER UNLESS NOTED OTHERWISE.
COMMUNICATIONS GROUNDING SHALL BE IN
ACCORDANCE WITH ARTICLE 800.100 (B)CADWELDA4.5
CONCRETE REQUIREMENTS AND SPECIFICATIONS:
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE
SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.
SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS
CONFLICT WITH THESE STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH
EACH OTHER, THE STRICTEST PROVISIONS SHALL GOVERN.
GOVERNING CODES: INTERNATIONAL BUILDING CODE, 2008, WITH CURRENT
INDIANA AMENDMENTS.
FOUNDATIONS:
NOTIFY THE ARCHITECT AS SOON AS POSSIBLE OF ANY UNUSUAL SOIL
CONDITIONS, SUCH AS UNEXPECTED SPRING OR SEEPAGE WATER, OR SOIL OF
QUESTIONABLE BEARING CAPACITY.
ALL FOOTINGS SHALL BEAR ON FIRM UNDISTURBED SOIL OR ENGINEERED FILL
WITH AN ALLOWABLE BEARING CAPACITY OF 2,000 POUNDS PER SQUARE FOOT.
PERIMETER FOOTINGS SHALL BEAR A MINIMUM OF 3'-0" BELOW EXTERIOR
GRADE. STEP FOOTINGS AS REQUIRED. WHERE UNDERGROUND UTILITIES
ENTER OR EXIT THE BUILDING, STEP TOPS OF ALL FOOTINGS BELOW UTILITY
INVERT ELEVATIONS.
DESIGN NET SOIL PRESSURES
SPREAD FOOTINGS:
CONTINUOUS FOOTERS
2,000 PSI
1,500 PSI.
BACKFILL AND FILL MATERIALS: PROVIDE SATISFACTORY SOIL MATERIALS FOR
BACKFILL AND FILL, FREE OF CLAY, DEBRIS, WASTE, FROZEN MATERIALS,
VEGETABLE AND OTHER DELETERIOUS MATTER.
REINFORCED CONCRETE:
ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318-95, "BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE".
SPECIFICATIONS: IN GENERAL, COMPLY WITH ACI 301-96, "STANDARD
SPECIFICATIONS FOR STRUCTURAL CONCRETE".
PLACEMENT AND CURING OF CONCRETE SHALL CONFORM TO ACI 305 "HOT
WEATHER CONCRETING" AND ACI 306 "COLD WEATHER CONCRETING".
ALL REINFORCING DETAILS SHALL CONFORM TO ACI 315-86, "MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES"
UNLESS DETAILED OTHERWISE ON THE STRUCTURAL DRAWINGS.
ALL DEFORMED REINFORCING BARS: ASTM A615, GRADE 60
ALL WELDED WIRE FABRIC:ASTM A185, DELIVERED IN FLAT SHEETS
REINFORCING SUPPLIER SHALL PROVIDE ALL BAR ACCESSORIES, CHAIRS, AND
SUPPORTS NECESSARY TO SECURE STEEL IN ACCORDANCE WITH "ACT CODE
OF STANDARD PRACTICE".
WHERE ANY STEPS IN FALL FOOTING ELEVATIONS OCCUR, PROVIDE MAXIMUM
STEP OF ONE VERTICAL TO TWO HORIZONTAL.
CONCRETE COVER: UNLESS OTHERWISE NOTED, DETAIL REINFORCING TO
PROVIDE MINIMUM COVER AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:3
INCHES
CONCRETE EXPOSED TO EARTH OR WEATHER, #5 RE-BARS OR SMALLER:
1/2 INCHES
ALL OTHER:2 INCHES
1
CONCRETE CONTRACTOR SHALL VERIFY SOIL BEARING PRIOR TO CONCRETE
PLACEMENT. REPORT DEVIATIONS TO GENERAL CONTRACTOR AND
ARCHITECT.
CONCRETE IN THE FOLLOWING AREAS SHALL CONSIST OF NATURAL SAND FINE
AGGREGATE AND NORMAL WEIGHT COARSE AGGREGATES CONFORMING TO
ASTM C33, TYPE 1 PORTLAND CEMENT CONFORMING TO ASTM C150, AND SHALL
HAVE THE FOLLOWING COMPRESSIVE STRENGTH AT 28 DAYS:
FOOTINGS AND PADS:
SLABS-ON-GRADE
AND PIERS:
3,000 PSI
4,000 PSI
RETAINING WALLS, CURBS, SIDEWALKS, AND SLABS EXPOSED TO DE-
ICERS.
4,000 PSI (6% + 1% ENTRAINED AIR BY
VOLUME)
NO PART OF THE STRUCTURE SHALL BE PLACED ON FROZEN OR WET SOIL.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING THE
FOUNDATION AND SOIL WITHIN THE BUILDING AREA FROM FREEZING DURING
WINTER CONSTRUCTION.
FOOTINGS AND PIERS:
DOWELS IN FOOTINGS SHALL MATCH VERTICAL PIER REINFORCING.
PROVIDE CORNER BARS AT FOOTING CORNERS TO MATCH HORIZONTAL
REINFORCING. MINIMUM LENGTHS OF EACH LEG TO BE 45 BAR DIAMETERS.
BACKFILL AGAINST BOTH SIDES OF WALLS EQUALLY UNTIL THE LOWER
ELEVATION IS ATTAINED. BRACE ALL FOUNDATION WALLS BEFORE
BACKFILLING AND COMPACTING.
PROVIDE LEAN CONCRETE (CLASS IV) UNDER FOUNDATIONS FOR ACCIDENTAL
OVER-EXCAVATION, SOFT SPOTS, AND TRENCHES.
BUILT-IN WORK:
INSTALL ALL ANCHORS, INSERTS, NOSINGS, REGLETS AND LIKE ITEMS
FURNISHED BY OTHER TRADES FOR INSTALLATION IN CONCRETE WORK. ALL
BUILT-IN ITEMS SHALL BE IN PROPER
LOCATION AND SHALL BE SO MAINTAINED DURING THE PERFORMANCE OF
CONCRETE WORK.
SLEEVES, CONDUITS, PIPES AND LIKE ITEMS PASSING THROUGH FLOORS,
WALLS, OR BEAMS SHALL BE OF SUCH SIZE OR IN SUCH LOCATION AS NOT TO
IMPAIR UNDULY THE STRENGTH OF THE CONSTRUCTION.
VAPOR BARRIER PLACEMENT:
USE A CONCRETE MIXTURE WITH AN ADEQUATE CEMENT FACTOR - MINIMUM OF
5 1/2 BAGS PER CUBIC YARD. USE A SMALL AMOUNT OF AIR-ENTRAINMENT IN
THE MIXTURE TO REDUCE BLEEDING - ABOUT 3% TO 5% AIR. EXTERIOR
CONCRETE SHALL HAVE 5 1/2% AIR. PLACE CONCRETE AT LOWEST PRACTICAL
SLUMP. A WATER-REDUCING ADMIXTURE MAY BE USED TO LOWER THE MIX
WATER CONTENT, IF USED STRICTLY ACCORDING TO WRITTEN
MANUFACTURER'S INSTRUCTIONS.
PERIMETER INSULATION:
A TOTAL OF FOUR FEET WIDTH OF PERIMETER INSULATION SHALL BE PUT IN
PLACE. THIS CAN BE A COMBINATION OF HORIZONTAL AND VERTICAL RIGID
INSULATION, AS SHOWN ON DRAWINGS.
PRE-ENGINEERED METAL CANOPY
PART 1 - GENERAL
THIS SPECIFICATION INCLUDES
Freestanding, pre-engineered metal canopy including concrete foundation,
steel framing, metal roof, roof drains and leaders, fascia components, and
metal ceiling and accessories.
REFERENCES
American Institute of Steel Construction, Inc. (AISC): AISC 360 -
Specification for Structural Steel Buildings (copyrighted by AISC, ANSI
approved
American Welding Society (AWS): AWS D1.1 - Structural Welding Code -
Steel (copyrighted by AWS, ANSI approved).
ASTM International (ASTM):
1.1 ASTM A 36/A 36M - Standard Specification for Structural Steel.
National Association of Architectural Metal Manufacturers (NAAMM):
NAAMM MFM - Metal Finishes Manual.
National Fire Protection Association (NFPA): NFPA 70 - National Electrical
Code (copyrighted by NFPA, ANSI approved) - hereinafter referred to as
NEC.
PERFORMANCE REQUIREMENTS
Structural Performance: Provide pre-engineered canopies capable of
withstanding the effects of gravity loads and the following loads and stresses
within limits and under conditions indicated for the specific location where
Canopy will be installed:
1.2 Uniform pressure as indicated on drawings - minimum design wind load
per ASCE 7, CH. 6.
Thermal Movements: Provide pre-engineered canopies that allow for thermal
movements resulting from the following maximum change (range) in ambient
and surface temperatures by preventing buckling, opening of joints,
overstressing of components, failure of joint sealants, failure of connections,
and other detrimental effects. Base engineering calculation on surface
temperatures of materials due to both solar heat gain and nighttime-sky heat
loss.
1.3 Temperature Change (Range): 120 degrees F (67 degrees C), ambient;
180 degrees F (100 degrees C), material surfaces.
QUALITY ASSURANCE
Welding: Qualify procedures and personnel according to the following:
1.4 Welding shall be in accordance with AWS D1.1 (with E70XX
electrodes).
1.5 Steel shop connections shall be welded and field connections shall be
bolted (unless otherwise noted on the Drawings). Shop welds may be
changed to field welds with the approval of the project engineer.
1.6 Slag shall be cleaned from welds and inspected. Steel shall be painted
with red oxide rust-inhibitive primer.
Electrical Components, Devices, and Accessories: Listed and labeled as
defined in NEC, Article 100, by a testing agency acceptable to authorities
having jurisdiction, and marked for intended use.
Source Limitations: Obtain pre-engineered metal canopy through one source
from a single manufacturer who shall manufacture and install the canopy.
DELIVERY, STORAGE, AND HANDLING
Store products in manufacturer's unopened packaging until ready for
installation.
Protect components and accessories from corrosion, deformation, damage,
and deterioration when stored at job site. Keep materials free from dirt and
foreign matter.
PROJECT CONDITIONS
Field Measurements: The Contractor shall verify location and elevation of
footings relative to finished grade, columns, and other construction
contiguous with pre-engineered metal canopies by field measurements
before fabrication and indicate measurements on shop drawings.
1.7 Established Dimensions: The Contractor shall, where field
measurements cannot be made without delaying the work, establish
dimensions and proceed with fabricating metal canopies without field
measurements. Contractor is responsible to coordinate footer locations
and elevations with any interferences with or attachments to abutting
structures.
PART 2 -- MATERIALS
Structural Steel:
1.8 Material and work shall conform to the latest AISC 360.
1.9 Structural steel shall be painted with a rust inhibitive (red oxide) primer
(std).
1.10 Structural steel shall be hot-dip-galvanized.
Sheet Metal:
1.11 Decking: 3 inch (76 mm) by 16 inch (406 mm) by 20 gage smooth
EIGHT A325 3/4" BOLTS
FOUR GUSSETS
4" x 3" x 3/8"
FOUR GUSSETS
4" x 3" x 3/8"
3/8" WEB STIFFENERS
3" x 6" x 1/4" TS
PURLINS. FIVE REQUIRED.
COLUMNS:
W10x22
A36 STEEL
FOUR REQUIRED
TOP PLATE DETAIL
SCALE: 1" = 1'-0"
REFLECTED PLAN
2
3"x6"x1/4" TS PURLINS
SCALE: 1/8" = 1'-0"
CANOPY LONGITUDINAL SECTION
SEE TOP PLATE
DETAIL
THIS SHEET 2
COLUMNS
W10x22
A36 STEEL
EIGHT REQUIRED
3/8" WEB STIFFENERS
20 GAUGE SMOOTH
WHITE DECK PANS
CURB AT PUMPS
SEE OTHER DRAWINGS
16" x 16" x 3/4" STEEL
BASE PLATE
1/2" x 20' ANCHOR BOLTS
FOUR REQUIRED AT EACH
COLUMN
3000 PSI CONCRETE
#6 REBARS 12" O.C. EACH WAY
TOP OF FOOTER 24" BELOW GRADE.4'-0"16'-0"3'-0"2'-0"FOOTER SHALL BE MINIMUM
6'-0" NORTH-SOUTH AND 4'-0"
EAST WEST
SEE DRAINAGE PLAN
GUTTER SYSTEM
TYPICAL OF 14
3"x6"x1/4" TS PURLINS
TYPICAL OF 14
COLUMNS:
W10x22
A36 STEEL
BREAK-METAL WRAP
AROUND COLUMNS
EIGHT COLUMNS REQUIRED
W10 x 12 SUPPORT BEAMS W10 x 12 SUPPORT BEAMS W10 x 12 SUPPORT BEAMS
CANOPY STRUCTURAL PLAN
SCALE: 1/8" = 1'-0"
3"x6"x1/4" TS PURLINS
STEEL DECK
TOTAL 14
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONA6.1
3"x6"x1/4" TS PURLINS
TOTAL 14
PREFORMED GUTTER SYSTEM
FRONT OF
CANOPY FACIA
STEEL DECK
W10 x 12 SUPPORT BEAMS
20 GAUGE SMOOTH
WHITE DECK PANS
SCALE: 1" = 1'-0"
EDGE OF CANOPY DETAIL1
A6.1 A6.1
A6.1A6.1
1
CANOPY DRAINAGE PLAN NORTH
SCALE: 1/8" = 1'-0"SLOPE4" PVC DOWN
INTERNAL GUTTER SYSTEM
SLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPECOLUMNS
SEE STRUCTURAL PLAN
HIGH POINT IN GUTTERGUTTER BY FACIA SUPPLIER
HIGH POINT IN GUTTER
HIGH POINT IN GUTTER
HIGH POINT IN GUTTER
LIGHT FIXTURE
CAN-304-PS-RD
304 SERIES CANOPY LUMINAIRE - PETROLEUM SYMETRIC
RECESSED MOUNT FOR DOUBLE SKIN CANOPIES
SEE CUT SHEETS ON THIS DRAWING.
CONTROLS:
ALL CANOPY LIGHTING SHALL BE CONTROLLED BY
PHOTOCELL(S).
PROVIDE STANDARD 110V SWITCH AT CASHIER AREA
TO PROVIDE ON-OFF CAPABILITY FOR CANOPY LIGHTS.
CLEARLY LABEL SWITCH.
TYPICAL LIGHT FIXTURES
AS DESCRIBED ON THIS SHEET
SCALE: 1/8" = 1'-0"
CANOPY REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"
CANOPY SOUTH AND NORTH ELEVATION
SCALE: 1/8" = 1'-0"
CANOPY EAST AND WEST ELEVATION19'-6"16'-6"3'-0"6"16'-0"BOLLARDS (TYP.)3'-0"6"15'-616'-0"TOTAL 27 FIXTURES
104'-0"26'-0"A6.2
PIPE GUARD DETAIL 3'-2"3'-6"3'-0"3'-5"4" DIA. STEEL PIPE GUARD
FILL WITH CONCRETE
PAINT TRAFFIC YELLOW
FINISHED GRADE
CONCRETE PAVEMENT
15" DIA. CONCRETE
FOOTING (TYP.)
NOT TO SCALE REVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION6" TO PUBLIC SEWER
BACKFLOW PREVENTER
BUILDING CLEAN OUT
HAND SINK
HAND SINK
4"
2"
ADA WC
ADA WC
ADA LAV
ADA LAV
ADA UR
C.O.
2"
2"
2"
2"
FD
FD
4"
4"
2"
ENDURA XL100
M RATED GREASE
INTERCEPTOR BELOW
SLAB
3"
3"
FD
2"
2"
3"
3 COMPARTMENT
COMMERCIAL SS SINK
MOP SINK
ELECTRIC WATER HEATER
ABOVE ON STEEL RACK
3"
3"
SCALE: 1/4" = 1'-0"
SANITARY SEWER PLAN
FLOOR SINK FOR BEVERAGE
DISPENSER.
VERIFY LOCATION WITH
OWNER PRIOR TO INSTALLATION.
FLOOR SINK FOR
ICE MACHINE.
VERIFY LOCATION WITH
OWNER PRIOR TO INSTALLATION.
2"2"
2"
4"4"
4"
4"
4"
CONDENSATE FOR FREEZER
COMPRESSOR
PLUMBING – GENERAL NOTES AND SPECIFICATIONS:
PLUMBING CONTRACTOR SHALL CONFIRM SIZES OR ESTABLISH SIZES OF
WASTE, VENT AND SUPPLY AS REQUIRED TO MAKE A COMPLETE AND WORKING
SYSTEM.
THE SCOPE OF THE PLUMBING WORK INCLUDES FURNISHING, INSTALLING
TESTING AND WARRANTY OF ALL PLUMBING WORK SHOWN ON THE PLUMBING
DRAWINGS.
THE PLUMBING CONTRACTOR ACKNOWLEDGES THAT HE IS AWARE THAT
PLUMBING DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL
EQUIPMENT OR FITTINGS REQUIRED. LOCATIONS ARE DIAGRAMMATIC.
PLUMBING CONTRACTOR SHALL ADJUST LOCATION OF PIPING AS REQUIRED.
CONFIRM DETAILED LOCATIONS WITH OWNER IF CRITICAL.
THIS PROJECT SHALL BE COMPLETE, OPERATIONAL AND MEET CURRENT STATE
AND LOCAL CODES AND ORDINANCES IN EVERY WAY. THE CURRENT CODE IS
THE 2012 INDIANA PLUMBING CODE (2006 INTERNATIONAL PLUMBING CODE
WITH 2012 INDIANA AMENDMENTS)
COORDINATE WORK WITH OTHER TRADES AND CONFIRM THAT CLEARANCES
AND FITTING REQUIREMENTS ARE KEPT.
MATERIALS AND WORKMANSHIP:
ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND FIRST QUALITY.
PROVIDE ALL NECESSARY CLIPS, HANGERS, FASTENERS, AND OTHER DEVICES
REQUIRED FOR A COMPLETE JOB.
ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND SUPPORTED IN A
FIRST-CLASS AND WORKMANLIKE MANNER BY MECHANICS SKILLED IN THEIR
PARTICULAR TRADES. A LICENSED PLUMBING CONTRACTOR SHALL PERFORM
WORK.
SANITARY SEWER SYSTEMS:
PROVIDE CLEANOUTS WHERE REQUIRED, WHETHER SHOWN ON DRAWINGS OR
NOT.
PIPE IN GRADE BELOW FLOOR SLABS SHALL BE RIGID PVC SCHEDULE 40, TYPE
1, GRADE 1, COMPLYING WITH ASTM D2665 AND D-1784.
PRESSURE TEST AND REPLACE DEFECTIVE MATERIALS AND CONNECTIONS.
WASTE AND VENTS:
SOIL, WASTE AND VENT LINES SHALL BE PVC SCHEDULE 40 ASTM D1785 WITH
ASTM D2665 DWV SOCKET FITTINGS; OR, SERVICE WEIGHT CAST IRON, OR AS
REQUIRED BY LOCAL CODES. SLOPE WASTE PIPING UNIFORMLY 1/8" PER FOOT
MINIMUM. SLOPE VENT PIPING TO PREVENT CONDENSATION FROM SYSTEM.
TEST SOIL, WASTE, AND VENT PIPING SHALL BE TESTED TO A MINIMUM 10 FEET
OF HEAD MAINTAINED FOR A MINIMUM 15 MINUTES. REPLACE DEFECTIVE PIPE
AND JOINTS AT NO ADDITIONAL COST TO OWNER.
FLOOR DRAINS SHALL BE EQUAL TO SMITH 2010-A.
FLOOR CLEANOUTS SHALL BE EQUAL TO SMITH 4021 OR 4021Y.
WALL CLEANOUTS SHALL BE EQUAL TO SMITH 4710.
PROVIDE AND INSTALL ALL REQUIRED OR SHOWN BACK-FLOW PREVENTERS.
DOMESTIC WATER SYSTEM:
WATER SUPPLY LINES SHALL BE OF TYPE "L" OR "K" COPPER AS REQUIRED BY
LOCAL PLUMBING CODES. ALL WATER SUPPLY LINES SHALL BE RUN UNDER
FLOOR SLAB AND UP PLUMBING WALLS. SIZE WATER SUPPLY AS REQUIRED
FOR BUILDING USAGE.
BACKFLOW PREVENTERS SHALL BE INSTALLED IF REQUIRED BY STATE AND
LOCAL ORDINANCES.
INSTALL WARM WATER LINES ON WARM SIDE OF CEILING INSULATION.
BACKFLOW PREVENTERS SHALL BE INSTALLED IF REQUIRED BY STATE AND
LOCAL ORDINANCES.
INSTALL WARM WATER LINES ON WARM SIDE OF CEILING INSULATION.
PRESSURE TEST TO 50 PSIG ABOVE OPERATING PRESSURE (125 PSIG MIN.) AND
MAINTAIN PRESSURE FOR 15 MINUTES MINIMUM WITH NO PRESSURE LOSS.
REPLACE DEFECTIVE MATERIALS AND CONNECTIONS. CLEAN, FLUSH AND
DISINFECT ALL WATER PIPING IN ACCORDANCE WITH AWWA C601.
INSTALL PID RATED SHOCK ABSORBERS IN COLD WATER LINES WHERE
REQUIRED.
ALL WATER SUPPLY (BOTH HOT AND COLD) LINES ABOVE FLOOR SLAB SHALL BE
INSULATED WITH 3/4" ARMA FLEX TYPE INSULATION.
INSTALL DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE CONNECTED.
PLUMBING FIXTURES:
FIXTURES SHALL BE COMPLETE WHEN FULLY INSTALLED, INCLUDING TRIM,
VALVES, SUPPLIES AND ESCUTCHEONS.
TRIM SHALL BE BRASS CHROME PLATED; FIXTURES SHALL BE WHITE, UNLESS
OTHERWISE NOTED.
SEAL CRACKS AROUND EACH FIXTURE AT WALL AND FLOOR WITH
PERMANENTLY PLIABLE WHITE SILICONE SEALANT.
STRICTLY FOLLOW ACCESSIBILITY STANDARDS NOTED BELOW.
DOMESTIC WATER HEATING:
PROVIDE GAS FIRED STORAGE WATER HEATER COMPLETE WITH POWER
BURNER OR ELECTRIC WATER HEATER TO SIZE REQUIRED. TANK SHALL BE
CONSTRUCTED IN ACCORDANCE WITH ASME CODE, STAMPED AND TESTED.
TANK SHALL BE INSULATED.
THE COMPLETE WATER HEATER SHALL BE LISTED BY UL, WITH LABEL
ATTACHED.
VENTING FOR GAS WATER HEATERS: UL APPROVED TYPE B DOUBLE-WALL GAS
VENT PIPING. VENT EXTENDED 3 FEET ABOVE THE ROOF, MINIMUM TWO FEET
HIGHER THAN ANY PORTION OF BUILDING WITHIN 10 FEET.
ACCESSIBILITY STANDARDS:
STRICTLY COMPLY WITH THE REQUIREMENTS OF UNIFORM FEDERAL
ACCESSIBILITY STANDARDS (UFAS), THE ADA, AND IBC, INDIANA CODE CHAPTER
11. PROVIDE RAISED SEAT FOR THE ACCESSIBLE WATER CLOSETS, PROVIDE
FLUSH ON ACCESS SIDE OF WC'S, TRAP TIGHT TO THE WALL UNDER
LAVATORIES, INSULATE ALL WASTE AND WATER PIPING BELOW LAVATORIES, AS
WELL AS ALL OTHER ADA REQUIREMENTS.
THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY IF REQUIRED DIMENSIONS,
CLEARANCES, OR STRUCTURAL CONDITIONS EXIST THAT COULD PREVENT THE
ABOVE ACCESSIBILITY REQUIREMENTS FROM BEING STRICTLY FOLLOWED.
TESTING:
ALL PIPES SHALL BE PRESSURE TESTED PER STANDARD PRACTICE. REPLACE
ALL DEFECTIVE LINES AND CONNECTIONS AT NO ADDITIONAL COST TO OWNER.
MANUALS:
TWO COPIES OF OPERATION AND MAINTENANCE MANUALS FOR MATERIALS
INSTALLED PER WORK OF THIS SECTION SHALL BE DELIVERED TO OWNER
PRIOR TO ACCEPTANCE OF THESE SPACES FOR OCCUPANCY.
BACKFLOW PREVENTION DEVICES FOR BEVERAGE STATIONS:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND SPECIFICATIONS ON THE
DRAWINGS. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ITEMS NECESSARY
FOR THE PROPER EXECUTION OF THE WORK.
NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CITY, STATE AND LOCAL BUILDING
CODES AND NFPA CODES FOR THIS CLASS OF WORK.
REQUIREMENTS:
ALL WORK RELATED TO THE BEVERAGE DISPENSERS AND BEVERAGE AREAS SHALL BE
PROTECTED BY THE PROVISIONS OF THE INDIANA PLUMBING CODE 2012 EDITION SECTIONS
608.16.1 AND 608.16.10.
CONNECTIONS TO POTABLE WATER SYSTEM:
SPECIFICALLY BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW BY A
BACKFLOW PREVENTER CONFORMING TO ASSE 1022. THE PORTION OF THE BACKFLOW
PREVENTER DEVICE DOWNSTREAM FROM THE SECOND CHECK VALVE AND THE PIPING
DOWNSTREAM THEREFROM SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS.
COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS:
THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND NONCARBONATED BEVERAGE
DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER
CONFORMING TO ASSE 1022.
INSTALLATION:
BACKFLOW PREVENTERS SHALL BE INSTALLED STRICTLY ACCORDING TO MANUFACTURER’S
WRITTEN INSTRUCTIONS AND ACCORDING TO THE CODES REFERENCED ABOVE.
CONDENSATE LINE CONDENSATE LINE
P1.1
DOMESTIC WATER DISTRIBUTION GENERAL REQUIREMENTS:
PIPING SHALL BE SIZED TO PROVIDE A VELOCITY NOT EXCEEDING SIX FEET PER
SECOND (FPS) FOR COLD AND HOT WATER SYSTEMS.
PIPES:
UNDERGROUND: ‘K” COPPER: BRAISED JOINTS; SLEEVES THRU
CONCRETE. INSULATED IN GRAVEL BACKFILL.
ABOVE SLAB: ‘L’ COPPER TUBING; CPVC PIPING, SCHEDULE 40 WITH
SOLVENT WELDED JOINTS; PEX TUBING WITH BRASS FITTINGS.
VENTING AND DRAINAGE: SCHEDULE 40 PVC WITH SOLVENT WELDED
JOINTS.
INSULATION:
INTERIOR COLD WATER PIPING SHALL BE INSULATED TO PREVENT
CONDENSATION. INTERIOR HOT WATER PIPING SHALL BE INSULATED AS
REQUIRED BY CODE AND PER LATEST ASHRE STANDARD A90.1, TABLE
7.2.3.
WALL HYDRANTS:
PROVIDE FREEZE-PROOF WALL HYDRANTS ON EXTERIOR WALLS A
MAXIMUM OF 150 FEET APART. LOCATE APPROXIMATELY 18” ABOVE
FINISH GRADE. COORDINATE LOCATIONS WITH THE BUILDING OWNER
AND THE PROJECT ARCHITECT.
VALVES:
PROVIDE ACCESSIBLE CHECK VALVES IN THE INDIVIDUAL COLD AND HOT
WATER FIXTURE SUPPLY LINES SERVING MIXING VALVE TYPE FAUCETS
OR ASSEMBILES HAVING HOSE CONNECTION OUTLETS THAT ARE NOT
EQUIPPED WITH INTEGRAL CHECK STOPS.
PROVIDE LINE SHUT-OFF VALVES AT LOCATIONS REQUIRED FOR PROPER
OPERATION, SERVICING AND TROUBLESHOOTING OF THE DOMESTIC
WATER DISTRIBUTION SYSTEM AND CONNECTED COMPONENTS.
LOCATIONS SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: AT
EACH FIXTURE AND PIECE OF EQUIPMENT; AT EACH BRANCH TAKE-OFF
FROM MAINS; AT THE BASE OF EACH RISER; AT EACH BATTERY OF
FIXTURES; WHERE RECOMMENDED BY EQUIPMENT MANUFACTURERS
AND AT STRATEGIC LOCATIONS TO ALLOW FOR SECTIONAL ISOLATION
WHILE LIMITING DISRUPTION OF SERVICES.
ALL VALVES SHALL BE ACCESSIBLE FOR OPERATION AND SERVICING.
TRAP PRIMING DEVICES THAT RELY UPON LINE PRESSURE DIFFERENTIAL
FOR ACTIVATION ARE NOT ALLOWED.
DOMESTIC HOT WATER SYSTEMS
WATER HEATERS INSTALLED AND UTILIZED FOR FOOD WERVICE AREAS
SHALL COMPLY WITH NATIONAL SANITATION FOUNDATION (NSF)
STANDARD NUMBER 5. HOT WATER SERVING COMMERCIAL
DISHWASHERS AND POT SINKS SHALL BE 140 DEGREES F. ALL OTHER
HOT WATER SHALL BE 110 DEGREES MAXIMUM AT OUTLETS.
CONTAMINATION PROTECTION:
INSTALLATION OF DOMESTIC WATER SYSTEMS SHALL AVOID ALL CROSS
CONNECTIONS AND ELIMINATE THE POSSIBILITY OF WATER
CONTAMINATION. ON EACH WATER SUPPLY SERVING A FIXTURE WHERE
A DISCHARGE LINE PROVIDES AN OPPORTUNITY WHERE CROSS
CONTAMINATION COULD OCCUR, PROVIDE A VACUUM BREAKER OR
BACKFLOW PREVENTER.
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONNOT TO SCALE
PLUMBING ISOMETRIC
EXPAND TO 3"
THRU ROOF
2" TO ROOF
1 1/2" VENT
EXPAND TO 3"
THRU ROOF
2" TO ROOF
2" TO ROOF
GREASE INTERCEPTOR:
INSTALL GREASE INTERCEPTOR STRICTLY ACCORDING TO REQUIREMENTS OF
THE PLUMBING AND DRAINAGE INSTITUTE (PDI) STANDARD PDI-G101.
INSTALL GREASE INTERCEPTOR STRICTLY ACCORDING TO REQUIREMENTS OF
THE CITY OF CARMEL, INDIANA.
CAPACITY:PER CITY REGULATIONS
AT A MINIMUM, THE FOLLOWING FIXTURES MUST BE CONNECTED THROUGH
THIS GREASE INTERCEPTOR (“FOG” TYPE USES – FATS, OILS, GREASE):
POT SINKS
PRE-RINSE SINKS
SOUP KETTLES
SINKS INTO WHICK KETTLES ARE DRAINED
AUTOMATIC HOOD WASHING UNITS
BASIN SINKS
MOP SINK
THREE COMPARTMENT COMMERCIAL SINKS
FIXTURES THAT SHOULD NOT BE CONNECTED TO THE GREASE INTERCEPTOR
UNLESS REQUIRED BY LOCAL AUTHORITIES.
TOILET ROOM FIXTURES
HAND SINKS
FLOOR DRAINS
THE DRAWINGS ARE SCHEMATIC AND DO NOT SHOW ALL REQUIRED PARTS AND
FITTINGS.
IF INTERCEPTOR WILL BE UNDER AN AUTOMOBILE DRIVEWAY. IT SHALL BE THE
SOLE RESPONSIBILITY OF THE INSTALLER TO PROVIDE REQUIRED
INTERCEPTOR STRUCTURAL THICKNESS AND PAVING/CONCRETE COVER.
NOTIFY ARCHITECT IMMEDIATELY IF CONDITIONS ARE NOT AS EXPECTED.
STRICTLY FOLLOW WRITTEN INSTALLATION INSTRUCTIONS AND CITY
INSTRUCTIONS.
CO
N
D
E
N
S
AT
E LI
N
E CONDENSATE LINEXL 100 GREASE INTERCEPTOR
BELOW SLAB
MOP SINK
SS 3 COMP. SINK
HAND
SINK
HAND
SINK
FLOOR SINK
FLOOR SINK
BLDG
CLEANOUT
BACKFLOW
PREVENTER
FD
FD
ADA WC
ADA WC
ADA LAV
ADA LAV
ADA UR P1.2
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION300 CFM 300 CFM 300 CFM 300 CFM
200 CFM
225 CFM
225 CFM
225 CFM
225 CFM
225 CFM
225 CFM
225 CFM
225 CFM
200 CFM
250 CFM 250 CFM
200 CFM
200 CFM
200 CFM
200 CFM
250 CFM
125 CFM
125 CFM
75 CFM
EXHAUST
75 CFM
EXHAUST
EXHAUST
TO DAYLIGHT
INSTALL RAIN
AND INSECT
SCREEN
6" FLEX
6" FLEX
DAMPER ALL BRANCHES
10" FLEX 10" FLEX 10" FLEX 10" FLEX
8" FLEX 8" FLEX 8" FLEX 8" FLEX
DAMPER ALL BRANCHES DAMPER ALL BRANCHES
8" FLEX 8" FLEX 8" FLEX 8" FLEX
DAMPER ALL BRANCHES
10" ROUND
10" ROUND
8" FLEX 8" FLEX
DAMPERS
25" x 8"
8" FLEX
8" FLEX
32" x 8"
GRILLES WITH
DAMPERS
COOLER
PACKAGE
BY MFGR.
CONDENSER LINE
TO DRAIN
200 CFM
MECHANICAL SCHEDULE
SCALE: 1/4" = 1'-0"
MECHANICAL PLAN
ROOFTOP COOLING-HEATING UNITS
THE ROOFTOP UNITS SHALL BE FACTORY PACKAGED WITH
CIRCULATING FAN, GAS-FIRED HEATING SECTION AND AIR-COOLED
REFRIGERATION SECTION. UNIT SHALL BE ROOF CURB MOUNTED.
UNIT SHALL BE RATED IN ACCORDANCE WITH ARI STANDARDS 270 AND
360 AND TESTED AND CERTIFIED BY UL OR ETL TO CONFORM TO
APPLICABLE ANSI STANDARDS.
A WALL MOUNTED SPACE THERMOSTAT SHALL BE FURNISHED WITH
THE UNIT.
THE REFRIGERATION SYSTEM AND FURNACE HEAT EXCHANGERS
SHALL CARRY A FIVE-YEAR WARRANTY.
PROVIDE CONDENSATE DRAINAGE PIPING FROM THE DRAIN PAN WITH A
4” DEEP TRAP AND CLEANOUT.
THE ELECTRICAL CONTRACTOR WILL PROVIDE POWER WIRING THRU A
FUSED DISCONNECT SWITCH ON ONE SET OF POWER TERMINALS IN
EACH UNIT. ALL OTHER POWER AND CONTROL WIRING REQUIRED FOR
THE COMPLETION OF THE SYSTEM SHALL BE FURNISHED AND
INSTALLED BY THE HVAC CONTRACTOR. ALL WIRING BY ANY
CONTRACTOR SHALL MEET OR EXCEED ALL STATE AND LOCAL CODES
AND ORDINANCES.
INSTALL A LOCAL DISCONNECT WITHIN THE LINE OF SIGHT OF TO ALL
PERMANENTLY CONNECTED ROOFTOP EQUIPMENT. THIS CAN ALSO
INCLUDE CONDENSERS FOR COOLER UNITS AND HOOD INTAKE AND
EXHAUST FANS.
PROVIDE A RECEPTACLE WITHIN 25 FEET OF THE ROOFTOP UNITS. IT
SHALL BE GFIC PROTECTED. THE GFIC TESTING THE TRIPPING RESET
SHOULB BE READILY ACCESSIBLE FOR SERVICING OF ROOFTOP
EQUIPMENT. PROVIDE “WHILE-IN-USE” WEATHERPROOF COVERS FOR
RECEPTACLES INSTALLED IN A WET LOCATION SO THAT THE
RECEPTACLE REMAINS WATERTIGHT WHILE A CORD IS PLUGGED IN.
MECHANICAL SPECIFICATIONS AND GENERAL
REQUIREMENTS:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND SPECIFICATIONS ON THE
DRAWINGS. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ITEMS NECESSARY
FOR THE PROPER EXECUTION OF THE WORK.
NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CITY, STATE AND LOCAL BUILDING
CODES AND NFPA CODES FOR THIS CLASS OF WORK.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR ALL APPLICABLE PERMITS, INSPECTIONS AND
LICENSES NECESSARY TO COMPLETE THIS INSTALLATION AND THE SATISFACTORY OPERATION
OF THE SYSTEM.
MECHANICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND DIMENSIONS AT THE
JOBSITE. IF DISCREPANCIES ARE FOUND THE GENERAL CONTRACTOR SHALL BE NOTIFIED
BEFORE PROCEEDING WITH ANY WORK OR ORDERING ANY EQUIPMENT OR MATERIAL IN THE
AFFECTED AREA.
FIT AND QUANTITY OF THE MECHANICAL SYSTEMS TO BE INSTALLED, WITH THE VARIOUS
NECESSARY PARTS AND MATERIALS TO MAKE A COMPLETE AND FINISHED JOB, SHALL BE
VERIFIED AND COORDINATED PRIOR TO START OF CONSTRUCTION AND ARE THE EXCLUSIVE
RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.
THE MECHANICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES AND
VERIFY ALL POWER AND DRAINS ARE PROVIDED AND IN THE PROPER LOCATION.
ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED PER THE MANUFACTURER'S SUGGESTED
INSTALLATION REQUIREMENTS IN A NEAT AND WORKMANLIKE MANNER.
MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND MUST BE FIELD VERIFIED FOR EXACT
ROUTING AND ADDITIONAL EQUIPMENT OR DEVICES NECESSARY FOR COMPLETE JOB.
MECHANICAL CONTRACTOR SHALL PROVIDE ALL CONTACTORS, RELAYS AND THERMOSTATS.
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL SWITCHES AND DISCONNECTS.
THE MECHANICAL CONTRACTOR SHALL COMPLETE TEMPERATURE CONTROL WIRING.
PROVIDE ALL NECESSARY HANGERS, FASTENERS, CLIPS AND OTHER DEVICES REQUIRED FOR A
COMPLETE JOB.
SUPPORT:
SUSPENDED TYPE UNIT HEATERS SHALL BE SUPPORTED BY ELEMENTS THAT ARE DESIGNED
AND CONSTRUCTED TO ACCOMMODATE THE WEIGHT AND DYNAMIC LOADS. HANGERS AND
BRACKETS SHALL BE OF NONCOMBUSTIBLE MATERIAL.
USE UNISTRUT-TYPE SUPPORT MATERIALS RATED FOR WEIGHT OF THE UNITS. CONNECT TO
STRUCTURAL ELEMENTS. NO CONNECTIONS TO ROOFING MATERIALS SHALL BE ALLOWED.
GAS PIPING SPECIFICATIONS:
BLACK STEEL: 2" OR SMALLER-SCHEDULE 40, GRADE "B" ASTM A120
SCREWED 150 PSI BLACK MALLEABLE IRON FITTINGS.
VALVES: PLUG TYPE
GAS SUPPORTS SHALL BE MINIMUM OF 10'-0" O.C.
ALL HVAC UNITS SHALL BE INSTALLED COMPLETE WITH ECONOMIZERS, LOW AMBIENT KITS, AND
REQUIRED CURBS, ETC.
MANUFACTURER'S MINIMUM CLEARANCE RECOMMENDATIONS SHALL BE MAINTAINED ON ALL
EQUIPMENT AND DUCTWORK.
ALL EXHAUST DUCTWORK SHALL BE METAL ROUND DUCTWORK. NO FLEXIBLE ROUND
DUCTWORK SHALL BE USED.
ALL MAIN DUCTS SHALL BE GALVANIZED STEEL WRAPPED WITH FOIL-BACK INSULATION OR
DUCT BOARD. INSTALL PER SMACNA STANDARDS. TURNING VANES SHALL BE INSTALLED AT
ELBOWS LARGER THAN 12" X 12".
ALL METAL DUCTWORK SHALL BE FABRICATED FROM GALVANIZED SHEET STEEL OF GAUGES,
REINFORCEMENT COMPLYING WITH SMACNA "HVAC DUCTWORK CONSTRUCTION STANDARDS."
THE ARCHITECT SHALL HAVE ACCESS TO THE CONSTRUCTION SITE AND HAVE THE RIGHT TO
REJECT ANY WORK (AFTER CONSULTATION WITH THE GENERAL CONTRACTOR) THAT DOES NOT
CONFORM TO THE DRAWINGS, SPECIFICATIONS, CODES OR WORK THAT HAS NOT BEEN
EXECUTED IN A WORKMANLIKE MANNER.
CONTRACTOR SHALL BE RESPONSIBLE FOR NOTICE TO THE INSPECTING AUTHORITIES,
ARCHITECT, OR GENERAL CONTRACTOR, SO THAT WORK CAN BE INSPECTED OR APPROVED
BEFORE COVERING. THIS PROCEDURE SHALL OCCUR WITHOUT AFFECTING CONSTRUCTION
PROGRESS AND COMPLETION.
THE INTENTION OF THESE DOCUMENTS IS TO PROVIDE THE OWNER WITH A BUILDING
COMPLETE IN ITS ENTIRETY AT THE TIME OF OCCUPANCY. IT IS THE SUB-CONTRACTOR'S
RESPONSIBILITY TO CONTRACT THE GENERAL CONTRACTOR DURING THE BIDDING/PRICING
PHASE OF ANY DETAILS MISSING, VAGUE, ORE INCOMPLETE SO THAT AN APPROPRIATE
ADDENDUM OR CLARIFICATION CAN BE ISSUED. THE SELECTED CONTRACTOR SHALL PROVIDE
ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, AND SERVICES NECESSARY FOR A COMPLETE,
FUNCTIONAL, AND OPERATIONAL FACILITY.
TWO COPIES OF OPERATION AND MAINTENANCE MANUALS FOR MATERIALS INSTALLED PER
WORK OF THIS SECTION SHALL BE DELIVERED TO OWNER PRIOR TO ACCEPTANCE OF THESE
SPACES FOR OCCUPANCY.
RTU #1 RTU #2
4 TON 6 TON
BEVERAGE COOLER COOLING BY MANUFACTURER
PROVIDE CONDENSATE LINE TO APPROPRIATE
DRAIN LOCATION
FREEZER. COOLED BY
MANUFACTURER
M1.1
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTIONSSS SSSSSS333
3S3E1.1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
B
B
C C C C
C
C
C
D
D
D
D
A
A
A
A
D D EEEEE
E
E
E
E
FREEZER BY OTHERSCOOLER BY OTHERS
SCALE: 1/4" = 1'-0"
ELECTRICAL LIGHTING PLAN
SYMBOLS
24" x 24" LAY-IN LED PANEL
24" x 48" LAY-IN LED PANEL
A
B
C
LINEAR 96" SUSPENDED
LED FIXTURE
D
E
LED CAN LIGHT AT BEVERAGE
AND FOOD COUNTERS
COOLER AND FREEZER LIGHTS PROVIDED
AND INSTALLED BY COOLER MFGR.
MINIMUM 24" x 30"
ATTIC ACCESS
F F
F F
F
SURFACE MOUNTED ART DECO FIXTURE
MODERN FORMS SKYSCRAPER
SEE CUT SHEET AT LEFT
SCALE: 1/4" = 1'-0"
I
I
IREVISIONS:DRAWING COMPLETION DATE:4820 Buttonwood CrescentARCHITECT AIAGORDON CLARKIndianapolis, Indiana 46228Phone: 317 255-2546317 252-5573Fax: GClark4820@aol.comCONVENIENCE STORE / FOOD MARTVILLAGE OF WEST CLAYCARMEL, INDIANASOUTHWEST CORNER OFHARLESTON STREET AND TOWNE ROADOCTOBER 14, 2021
FOR PERMITTING AND CONSTRUCTION220V
GFI
GFI
GFI
GFI
HIGH FOR SIGN AND/OR SHOW WINDOWS
POS
POS
DED
DED
DED
GFI
GFI
GFI
GFI
DRAWING NOTES:
1.
2.
3.
4.
5.
MINIMUM WIRE SIZE TO BE #12 AWG COPPER
INSTALLATION TO MEET ALL STATE AND LOCAL CODES.
ALL WIREING TO BE INSTALLED IN METAL RACEWAYS
OR MC CABLE WHERE PERMITTED BY CODE.
MAXIMUM LOAD OF 1,600 WATTS FOR 20 AMP BRANCH CIRCUITS.
FINAL LOCATIONS OF ALL DEVICES AND EQUIPMENT
CONNECTIONS TO BE VERIFIED BY THE OWNER.
ELECTRICAL RISER
DIAGRAM
2-1
2" PVC CONDUIT WITH (4) 4
0 AL AND (1) #2 GROUND WIRE
NOT TO SCALE
SUPPLY FAN:
USE CIRCUIT 20
115 V
1/2 HP
4.80 AMPS
EXHAUST FAN:
USE CIRCUIT 22
115 V
3/4 HP
13.80 AMPS
CONDENSER
USE CIRCUIT 24
20 AMP
2 POLE
EVAPORATOR
USE CIRCUIT 26
15 AMP
2 POLE
FOR HOOD SYSTEM (FUTURE)
GROUND ROD
TO
#6 THHN
#4 THHN TO THE
BUILDING STEEL
DISCONNECT
200 AMP
3 PHASE
42 SPACE
PANEL
GROUND ROD
TO
#6 THHN
#4 THHN TO THE
BUILDING STEEL
DISCONNECT
200 AMP
3 PHASE
42 SPACE
PANEL
METER BASE
AS REQUIRED
#4 THHN TO THE
BUILDING STEEL
SUB-PANEL
GROUND ROD
TO
#6 THHN
FOR FUEL SYSTEMS100 AMP
SINGLE PHASE
USE DUAL RATED THHN WIRE
4 WIRE PER CABLE
FOR COOLERS AND FREEZER
DISCONNECT
20A/2P CIRCUIT FOR CONDENSER
IN COOLER AND FREEZER
15A/2P CIRCUIT FOR LIGHTS
200 AMP 200 AMP 100 AMP
400 AMP CT CABINET
TWO 200 AMP DISCONNECTS
METER BASE FEED FROM PUBLIC SERVICE
LOCATE PER LOCAL UTILITY REQUIREMENTS
UNDERGROUND SERVICE
DRIVEWAY RATED
SODA
ON ONE CIRCUIT
2 RECEPT.
GFI
GFI GFI GFI GFI GFI GFI GFIGFI
15A/2P CIRCUIT FOR EVAPORATOR
ENTIRE BEVERAGE AREA
11 RECEPTACLES ON 8 CIRCUITS
COUNTS SODA INDICATED
ALL GFI PROTECTED
FOOD SERVICE AREA
5 RECEPTICLES ON 2 CIRCUITS
GFI
GFI
GFI
GFI
GFI
GFI
ELECTRICAL POWER PLAN
POS
FREEZER SIMILAR
TO COOLER REQUIREMENTS
110V DUPLEX RECEPTICAL
GFI 110 V RECEPTICAL GF PROTECTED
DED 110 V RECEPTICAL, DEDICATED
220 B RECEPTICAL220V
PHONE / DATA OUTLET
SYMBOLS
ELECTRICAL SPECIFICATIONS AND GENERAL REQUIREMENTS:
THE CONTRACT DOCUMENTS CONSIST OF THE DRAWINGS AND
SPECIFICATIONS ON THE DRAWINGS. THE INTENT OF THE CONTRACT
DOCUMENTS IS TO INCLUDE ITEMS NECESSARY FOR THE PROPER EXECUTION
OF THE WORK.
BUILDING CODES: NEW CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE
CITY, STATE AND LOCAL BUILDING CODES FOR THIS CLASS OF WORK.
ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND
DIMENSIONS AT THE JOBSITE. IF DISCREPANCIES ARE FOUND THE GENERAL
CONTRACTOR SHALL BE NOTIFIES BEFORE PROCEEDING WITH ANY WORK OR
ORDERING ANY EQUIPMENT OR MATERIAL IN THE AFFECTED AREA.
FIT AND QUANTITY OF THE WIRING, ELECTRICAL EQUIPMENT, THE VARIOUS
NECESSARY PARTS AND MATERIALS TO MAKE A COMPLETE AND FINISHED JOB
SHALL BE VERIFIED AND COORDINATED PRIOR TO START OF CONSTRUCTION
AND ARE THE EXCLUSIVE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
LOCAL UTILITY COORDINATION: ELECTRICAL CONTRACTOR SHALL
COORDINATE TRANSFORMERS AND SERVICE REQUIREMENTS WITH THE LOCAL
UTILITY COMPANY. THE E.C. SHALL CONSULT WITH THE LOCAL UTILITY TO
ESTABLISH REQUIRED kACI RATINGS.
ALL FIXTURES, EQUIPMENT AND MATERIALS SHALL BE INSTALLED PER THE
MANUFACTURER'S SUGGESTED INSTALLATION REQUIREMENTS IN A NEAT AND
WORKMANLIKE MANNER.
UL LABELING: ALL ELECTRICAL EQUIPMENT SHALL HAVE "UL" LABELS.
WIRING DEVICES SHALL BE SPECIFICATION GRADE.
PROVIDE ALL DISCONNECTS REQUIRED PER NATIONAL AND LOCAL ELECTRICAL
CODES RATED TO UTILITY SUPPLIED kAIC LIMITS, OR, IF NOT SUPPLIED, TO NEC
MINIMUMS.
ALL EXPOSED WIRE AND WIRING BELOW CONCRETE SLABS SHALL BE IN
CONDUIT.
WIRE: ALL WIRE SHALL BE COPPER, MINIMUM SIZE #12 AWG. ALL
CONDUCTORS SHALL HAVE TYPE "THHN" INSULATION. CONDUCTORS #10 AND
SMALLER MAY BE SOLID. GROUNDING CABLES SHALL BE NO SMALLER THAN 4
COPPER.
BREAKER PANELS: FURNISH AND INSTALL A BREAKER PANEL AS
MANUFACTURED BY SQUARE D OR ITE. INSTALL PANEL SO TOP BREAKER IS NO
HIGHER THAN 6'-0".
FURNISH AND INSTALL TYPEWRITTEN DIRECTORY. IDENTIFY AND LABEL ALL
ELECTRICAL SERVICE EQUIPMENT.
GROUNDING: GROUNDING SHALL BE DONE STRICTLY ACCORDING TO SECTION
250.52 OF THE NATIONAL ELECTRIC CODE USING ACCEPTABLE ELECTRODES
AND CONNECTIONS.
SWITCHES: ALL SWITCHES SHALL BE RATED 20 AMP, 125 VOLT AND SHALL BE
MOUNTED 4'-6" AFF, UNLESS NOTED OTHERWISE.
RECEPTICALS: ALL RECEPTACLES TO BE 15 AMP, 125 VOLT, GROUNDING TYPE
AND SHALL BE MOUNTED 18" AFF, UNLESS NOTED OTHERWISE.
PROVIDE TEMPORARY POWER REQUIRED BY THE GENERAL CONTRACTOR AND
OTHER TRADES. COORDINATE POWER REQUIREMENTS WITH GC PRIOR TO
INSTALLATION.
LIGHTING FIXTURES: LIGHTING FIXTURES TO BE FURNISHED AND INSTALLED
COMPLETE WITH LAMPS AS DETAILED ON THE PLANS OR AS INTENDED. SEE
REFLECTED CEILING PLAN AND/OR LIGHTING PLAN FOR THE EXACT LOCATION
OF THE CEILING GRID, LIGHT FIXTURES, OR THE GENERAL INTENT OF THE
DRAWINGS.
SEE THE ELECTRICAL DRAWING(S) FOR THE FIXTURE SCHEDULE, NOTES AND
OTHER SPECIFICATION REQUIREMENTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR NOTICE TO THE INSPECTING
AUTHORITIES, ARCHITECT, OR GENERAL CONTRACTOR, SO THAT WORK CAN BE
INSPECTED OR APPROVED BEFORE COVERING. THIS PROCEDURE SHALL
OCCUR WITHOUT AFFECTING CONSTRUCTION PROGRESS AND COMPLETION.
THE INTENTION OF THESE DOCUMENTS IS TO PROVIDE THE OWNER WITH A
BUILDING COMPLETE IN ITS ENTIRETY AT THE TIME OF OCCUPANCY. IT IS THE
SUB-CONTRACTOR'S RESPONSIBILITY TO CONTACT THE GENERAL
CONTRACTOR DURING THE BIDDING/PRICING PHASE OF ANY DETAILS MISSING,
VAGUE, OR INCOMPLETE SO THAT AN APPROPRIATE ADDENDUM OR
CLARIFICATION CAN BE ISSUED. THE SELECTED CONTRACTOR SHALL PROVIDE
ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, AND SERVICES NECESSARY FOR A
COMPLETE, FUNCTIONAL, AND OPERATIONAL FACILITY.
E1.2