HomeMy WebLinkAboutLS100.0 - Life Safety Plan, South CollegeUP UPUP UPCHEM
LAB
164
964 SF
x
STORAGE
163
8'-3"9'-8"
x
STG
165
8'-3"9'-8"
A+P
LAB
162
1126 SF
NURSINGLAB
146
1107 SF
CLASSROOM
167
906 SF
x
STG
147
13'-1"6'-0"
x
STG
149
6'-0"13'-1"
x
EXAM
150
11'-9"9'-5"
x
EXAM
153
10'-0"7'-10"
ASSESSMENT
LAB
148
1295 SF
x
CONF
128
20'-6"12'-6"
RADIOLOGY
LAB
166
734 SF
OPEN OFFICE20 STATIONS
126
ULTRASOUND
LAB
159
1051 SF
x
OFFICE
118
9'-7"13'-10"
x
OFFICE
117
13'-10"9'-7"
x
OFFICE
106
10'-0"12'-0"
x
OFFICE
102
10'-0"12'-0"
x
OFFICE
105
10'-0"12'-0"
x
OFFICE
104
10'-0"12'-0"
x
OFFICE
103
10'-0"12'-0"
x
OFFICE
115
9'-7"13'-10"
x
OFFICE
114
9'-7"13'-10"
x
OFFICE
113
9'-7"13'-10"
x
OFFICE
112
9'-7"13'-10"
x
OFFICE
116
9'-7"13'-10"
ENTRY
101
x
TESTING
109
21'-0"6'-2"
COPY
107
CLASSROOM
139
1397 SF
CLASSROOM
138
1467 SF
STUDY
144
125 SF
STAFF BREAK
132
x
IT STG
160
11'-7"9'-1"
x
SERVER
161
11'-7"7'-4"
x
STORAGE / IT
140
11'-2"12'-7"
CLASSROOM
154
678 SF
x
EXAM
152
10'-0"7'-10"
x
EXAM
151
11'-9"7'-10"
6x8
6x8
6x8
6x8
x
OFFICE
119
9'-7"13'-10"
x
OFFICE
120
9'-7"13'-10"
x
OFFICE
121
9'-7"13'-10"
x
OFFICE
122
12'-2"13'-10"
x
CONFERENCE
123
17'-0"14'-7"
6x8
6x8
6x8
6x8
6x8
COMPUTER LAB
170
594 SF
ENTRY
169
LIBRARY /RESOURCE LAB
168
431 SFREFRIGBYTENANTVEND. x
STUDY
155
12'-10"17'-2"
STUDENT CENTER
141
1443 SF
6x8
6x8
6x8
6x8
6x8
6x8
6x8
6x8
6x8
x
FIRE-RATEDFILES
137
7'-6"12'-1"
OFFICE
111
144 SF
x
OFFICE
110
11'-7"14'-1"
x
TESTING
108
21'-0"6'-2"
x
OFFICE
124
13'-0"16'-6"
STUDY
145
143 SF
(45 OCCUPANTS
AT 20 SF/PERSON)
STUDY
143
123 SF
STUDY
142
148 SF
VEND. VEND.VEND. VEND.x
OFFICE
130
8'-1"11'-5"
SIM LAB
156
349 SF
SIM
LAB
158
350 SF
x
CONTROLROOM
157
9'-0"22'-4"
x
OFFICE
136
9'-0"10'-0"
x
OFFICE
135
9'-0"10'-0"
x
OFFICE
134
9'-0"10'-0"6x86x86x8x
OFFICE
131
18'-3"14'-8"
OPEN OFFICE3 STATIONS
133
ENTRY
127
RR
129
(15 OCCUPANTS
AT 50 SF/PERSON)
(20 OCCUPANTS
AT 50 SF/PERSON)
(23 OCCUPANTS
AT 50 SF/PERSON)
(22 OCCUPANTS
AT 50 SF/PERSON)
(30 OCCUPANTS
AT 20 SF/PERSON)
(7 OCCUPANTS
AT 50 SF/PERSON)
(7 OCCUPANTS
AT 50 SF/PERSON)
(26 OCCUPANTS
AT 50 SF/PERSON)
(23 OCCUPANTS
AT 50 SF/PERSON)
(34 OCCUPANTS
AT 20 SF/PERSON)
(74 OCCUPANTS
AT 20 SF/PERSON)
(70 OCCUPANTS
AT 20 SF/PERSON)
EXIT
DISCHARGE
171
ELELHALL
172
EL
EL
CLOSET
125
ELNELNELN
ELNELNELN ELNELNELNELNELN
ELNE
L
NEL EL
FEFEFEFE
FEFEFEFEFEFEELN ELNELNELNELNELNELN
FE
ELN
REF
RI
GBYTENANT
LIFE SAFETY
PLAN
L100LIFE SAFETY PLAN
DESCRIPTIONDATE
ISSUE
05.05.21 REVIEW SET
05.14.21 PERMIT SET
06.08.21 CONSTRUCTION SET
REVISIONS
DESCRIPTIONMARK DATE DB
06.08.21 AS REV 1
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.
PROJECT NUMBER
DRAWN BYPROJ. MGR 450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comSOUTH COLLEGEPENN ON PKWY | 1ST FLOOR301 PENNSYLVANIA PKWY, INDIANAPOLIS, IN 46280AS/EHAS
2020.325
N
LIFE SAFETY NOTES GENERAL NOTES
1ST FLOOR
AREA NOT IN CONTRACT
AREA OF WORK
SCOPE OF WORK NURSING INSTRUCTION FOR HIGHER ED (ABOVE 12TH GRADE) +
ADMINISTRATIVE OFFICE BUILD OUT OF PREVIOUS OFFICE BUILDOUT
TOTAL BUILDING AREA
TOTAL PROJECT AREA
CHANGE OF OCCUPANCY CLASS?
OCCUPANCY CALCULATIONS SPACE TYPE AREA SF PER OCCUPANT OCCUP LOAD
NO
OCCUPANCY CLASSIFICATION B(USINESS)
OFFICE SF
CLASSROOM 138 + 139
STUDENT CENTER 141
100
20
15
2,864
1,443
SF
SF
SPRINKLER SYSTEM (YES/NO) YES - EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES 1,443
TOTAL AREA ON THE FLOOR
SF
SF/FLOOR X STORIES SF
SF
33,592 SF
ACCESSORY AREA EXCEEDS 10% NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
EXISTING TO REMAIN + NEW AS REQUIRED AT EXIT DISCHARGE
(SEE PLAN)
=
TOTAL OCCUPANTS IN PROJECT AREA 484
144
97
CODE SUMMARY
PREVIOUS USE OF SPACE B(USINESS)
ASHRAE 90.1 SUMMARY EXEMPT (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 1978? NO
24,280
28,587
33,592 4 134,368
243
BUILDING CONSTRUCTION TYPE II-B
L1. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DETAILS.
L2. EXISTING EXIT SIGNS, FIRE PULLS, FIRE EXTINGUISHERS, ALARM
NOTIFICATION APPLIANCES TO REMAIN. RELOCATE EXISTING EXIT
SIGNS, FIRE PULLS, FIRE EXTINGUISHERS AND ALARM NOTIFICATIONS AS
REQUIRED TO MEET ALL LOCAL AND STATE CODES.
EXISTING ELECTRICAL PANEL LOCATION
EXISTING EXIT
EP
EX
LEGEND
FIRE EXTINGUISHER
EXIT SIGN
FE
EMERGENCY LIGHT
FE
TRAVEL DISTANCE
NUMBER OF EXITS REQUIRED: 2 PROVIDED: 4
- LED EDGE LIT
NOTES: - CLASSROOMS + LABS WILL BE UTILIZED FOR STUDENTS ABOVE GRADE 12 AND CLASSIFIED AS BUSINESS GROUP (B)
PER IBC2012 SECTION 304.1.
- CLASSROOMS + LABS UNDER 50 OCCUPANTS ARE CLASSIFIED AS (B) OCCUPANCY PER IBC2012 SECTION 303.1.2
1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
4. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
5. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
NOT TO SCALE
EX
EX
EX EX
EX
EP
TRAVEL DISTANCE = 130'TRAVEL DISTANCE = 120'
TRAVEL DISTANCE = 190'
NEW WALLS AT EXIT DISCHARGE
TO BE RATED ASSEMBLIES
TO MATCH ADJACENT WALLS
FIRE RATED ASSEMBLY TO MATCH
NEW WALLS AT
EXIT DISCHARGE
TO BE RATED
ASSEMBLIES TO
MATCH ADJACENT
WALLS
ADJACENT WALL CONSTRUCTION
01/11/22