HomeMy WebLinkAboutE100.2 - Electrical Plan-South, South CollegeUP UP UPCHEM
LAB
164
STORAGE
163
STG
165
A+P
LAB
162
NURSING
LAB
146
CLASSROOM
167
STG
147
STG
149
EXAM
150
EXAM
153
ASSESSMENT
LAB
148
RADIOLOGY
LAB
166
ULTRASOUND
LAB
159
STUDY
144
IT STG
160
SERVER
161
CLASSROOM
154
EXAM
152
EXAM
151
COMPUTER LAB
170
ENTRY
169
LIBRARY /
RESOURCE LAB
168
STUDY
155
STUDY
145 SIM LAB
156
SIM
LAB
158
CONTROL
ROOM
157 +60"+48"+48"+60"+48"+48"+60"+48"+48"+60"+48"+48"+48"+48"+48"+42"GFCI+24" +42"
+42"
GFCI
+42" +42"GFCI
+42"GFCI
+42"GFCI
GFCI
+42"
GFCI
+42"+42" +42" +42" GFCI
+4 2"
+42 "
+42"
+42"
GFCI
GF CI
GFCI
GFCI GFCI
GFCI
+42"
+42"
GFCI
+42"
+42"GFCI
+42"GFCI
+42"GFCI
+44"
+44"DEDGFCI
+TBD
+TBD
GFCI
GF CI
+42"
+42"
+42"
+42 "+42"+42"
+42"
+42"
+44"
+44"REFRIGBYTEN
ANTDED
ELECTRICAL PLAN
E112ELECTRICAL PLAN
DESCRIPTIONDATE
ISSUE
05.05.21 REVIEW SET
05.14.21 PERMIT SET
06.08.21 CONSTRUCTION SET
REVISIONS
DESCRIPTIONMARK DATE DB
06.08.21 AS REV 1
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.
PROJECT NUMBER
DRAWN BYPROJ. MGR 450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comSOUTH COLLEGEPENN ON PKWY | 1ST FLOOR301 PENNSYLVANIA PKWY, INDIANAPOLIS, IN 46280AS/EHAS
2020.325
N
0 2' 4' 8' 16'
LEGEND
DED
POWER OUTLET, DUPLEX
NEW CONSTRUCTION EXISTING TO REMAIN
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
POWER OUTLET, DUPLEX
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
BOX, BLANK COVER PLATE BOX, BLANK COVER PLATE
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
DEDICATED CIRCUIT
DATA/COMMUNICATION
OUTLET (PROVIDE BOX
AND PULL STRING ONLY)
DATA/COMMUNICATION
OUTLET
GFCI GROUND FAULT CIRCUIT
INTERRUPT OUTLET
HEIGHT OF ELECTRICAL
OR DATA DEVICE
CEILING MOUNTED
JUNCTION BOX
CEILING MOUNTED
JUNCTION BOX
J
B
J
+42"
PROVIDE POWER AS REQUIRED AT DOOR FOR CARD READER
(CARD READER BY TENANT). COORDINATE WITH TENANT'S
SECURITY CONTRACTOR. SEE DOOR SCHEDULE FOR MORE
DETAILS.
COORDINATE COPIER RECEPTACLE WITH TENANT. PROVIDE
DEDICATED RECEPTACLE AS REQUIRED.
PROVIDE JUNCTION BOX AND DATA FOR TENANT'S FURNITURE
SYSTEM. COORDINATE EXACT LOCATION WITH TENANT'S
FURNITURE VENDOR.
PROVIDE DEDICATED POWER OUTLET IN RECESSED BOX INSET
INTO CABINET/ WALL FOR TENANT'S MICROWAVE, CENTERED AT
HEIGHT NOTED ON PLANS.
PROVIDE JUNCTION BOX ABOVE CEILING FOR TENANT PROVIDED
CEILING MOUNTED PROJECTOR. COORDINATE WITH TENANT ON
EXACT REQUIREMENTS AND ALL AV CONNECTION POINTS.
COORDINATE EXACT LOCATIONS AND REQUIREMENTS FOR ALL
POWER/DATA/AV CONNECTIONS WITH TENANT'S EQUIPMENT
VENDOR.
PROVIDE ABOVE COUNTER POWER AT THESE LOCATIONS;
COORDINATE FINAL HEIGHTS WITH COUNTERTOP.
NO NEW ELECTRICAL WORK IN THIS AREA.
PROVIDE FLUSH MOUNT FLOOR CORE WITH POKE THRU DEVICE
FOR ELECTRICAL AND DATA. COORDINATE WITH TENANTS
FURNITURE VENDOR ON EXACT LOCATION. PROVIDE POKE THRU
DEVICE SUBMITTAL TO TENANT FOR APPROVAL PRIOR TO
ORDERING.
CONFIRM POWER FOR EXISTING CARD READER SYSTEM IS
SUFFICIENT FOR TENANT'S NEW SYSTEM (CARD READY BY TENANT).
PROVIDE NEW AS REQUIRED; COORDINATE WITH TENANT'
SECURITY CONTRACTOR.
PROVIDE POWER AND DATA AT HEIGHT NOTED ON PLAN FOR
TENANT'S WALL MOUNTED TELEVISION. COORDINATE EXACT
LOCATION WITH TENANT.
PLAN NOTES
1. TENANT'S FURNITURE VENDOR IS RESPONSIBLE FOR
INSTALLATION OF FURNITURE AND FIELD VERIFICATION OF
ALL CRITICAL DIMENSIONS.
2. ALL OUTLETS ARE TO INSTALLED 18" MIN. A.F.F. TO THE
CENTER OF THE DEVICE PER ADA GUIDELINES UNLESS
NOTED OTHERWISE. ALL NEW DEVICES AND FACE PLATES
TO MATCH EXISTING.
3. REFER TO DOOR SCHEDULE AND COORDINATE WITH
TENANT/OWNER REGARDING POWER LOCATIONS TO
ACCOMMODATE ELECTRIC STRIKES, CARD READERS
AND/OR MAG-LOCKS. CARD READERS ARE TYPICALLY
INSTALLED BY THE TENANT'S SECURITY CONTRACTOR AND
NOT SPECIFIED BY SDI.
4. CONTRACTOR TO PROVIDE GFCI OUTLET FOR WATER
HEATER AND AUTOMATIC SHUTOFF VALVES AS REQUIRED.
5. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE
AND IS OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL
WORK IS LIMITED TO ADDITIONS OR RELOCATIONS OF
ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO
NOT EXCEED THE CAPACITY OF THE EXISTING ELECTRICAL
SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS
REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED
AND MUST COMPLY WITH ALL APPLICABLE CODES.
6. ALL WIRING IN PATIENT CARE AREAS (I.E. SELF CARE UNIT
AREAS, TREATMENT ROOMS, ETC.) SHALL COMPLY WITH
NEC ARTICLE 517-13. ALL RECEPTACLES SHALL BE
HOSPITAL GRADE TYPE RECEPTACLES.
7. ALL RECEPTACLES IN TREATMENT/EXAM AREAS SHALL BE
GROUNDED PER NFPA 70, (NATIONAL ELECTRIC CODE,
2017) SECTION 517-13.
8. ALL MEDICAL AND X-RAY EQUIPMENT SHALL BE INSTALLED
BY SUPPLIER AND CONNECTED BY ELECTRICAL
CONTRACTOR. GENERAL CONTRACTOR SHALL
COORDINATE INSTALLATION AND EXACT POWER
REQUIREMENTS WITH MEDICAL EQUIPMENT
MANUFACTURER PRIOR TO INSTALLATION.
GENERAL NOTES
NOTE: NOT ALL PLAN NOTES ARE USED ON EACH SHEET.
J
TENANT'S DATA VENDOR TO PROVIDE WIRELESS ACCESS
POINT IN CEILING AT THIS LOCATION. COORDINATE ALL
FINAL REQUIREMENTS WITH VENDOR AND TENANT.
TENANT'S DATA/AV VENDOR TO PROVIDE CAMERA AT
THIS LOCATION. COORDINATE ALL FINAL REQUIREMENTS
WITH VENDOR AND TENANT.
PROVIDE CONDUIT CONNECTION BETWEEN SERVER 161
AND STORAGE/IT 140 FOR IT CABLING. COORDINATE
EXACT REQUIREMENTS WITH TENANT.
PROVIDE REQUIRED POWER/DATA FOR TENANT'S XRAY
EQUIPMENT AT THIS LOCATION.
1ST FLOOR - S
AREA NOT IN CONTRACT
AREA OF WORK
01/11/22