HomeMy WebLinkAboutMerchants First Floor TI_ELECOHE OHE OHE UGE UGE UGE T T T PIV PS WF VS SYMBOLS, ABBREVIATIONS, AND GENERAL SPECIFICATIONSSOME SYMBOLS AND/OR ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT -ADDITIONAL SYMBOLS MAY BE USED WHERE NEEDEDSTANDARD ABBREVIATIONS A AMPERES AC ALTERNATING CURRENT AF AMPERE FUSE AFC ABOVE FINISHED CEILING AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM ARCH ARCHITECT(URAL) ATS AUTOMATIC TRANSFER SWITCH AUTO AUTOMATIC AVG AVERAGE BFC BELOW FINISHED CEILING BFG BELOW FINISHED GRADE BHP BRAKE HORSEPOWER BPS BOOSTER POWER SUPPLY BTM BOTTOM C CONDUIT CB CIRCUIT BREAKER C/C CENTER TO CENTER CCTV CLOSED CIRCUIT TELEVISION CF CUBIC FEET CKT CIRCUIT CL CENTERLINE CLG CEILING COMM COMMUNICATIONS COMP COMPRESSOR CONT CONTINUOUS CR CRITICAL LOAD CT CURRENT TRANSFORMER CU COPPER DC DIRECT CURRENT DP DISTRIBUTION PANEL DPST DOUBLE POLE, SINGLE THROW DWG DRAWING DWH DOMESTIC WATER HEATER EC ELECTRICAL CONTRACTOR EF EXHAUST FAN EGC EQUIPMENT GROUNDING CONDUCTOR EM EMERGENCY (LOAD) EPO EMERGENCY POWER OFF EQUIP EQUIPMENT EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EX EXIT EXH EXHAUST EXP EXPLOSIONPROOF EXT EXTERIOR FA FIRE ALARM FAAP FA ANNUNCIATOR PANEL FACP FA CONTROL PANEL FC FLAT CABLE FCU FAN COIL UNIT FFC FOOD FACILITY CONTRACTOR FFS FOOD FACILITY SUPPLIER FHC FIRE HOSE CABINET FIXT FIXTURE FLUOR FLUORESCENT FPC FIRE PROTECTION CONTRACTOR FSS FUSED SAFETY SWITCH FTG FOOTING FTL FEED THROUGH LUGS FV FULL VOLTAGE G, GND GROUND GALV GALVANIZED GC GENERAL CONTRACTOR GEC GROUNDING ELECTRODE CONDUCTOR GEN GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTOR GFP GROUND FAULT PROTECTION GTB GENERATOR TAP BOX H, HV HIGH VOLTAGE HID HIGH INTENSITY DISCHARGE HO HAND OPERATED HOA HAND-OFF-AUTO HP HORSEPOWER HPS HIGH PRESSURE SODIUM HTR HEATER Hz HERTZ IC INTERCOM ID INSIDE DIAMETER ISG ISOLATED GROUND J, JB JUNCTION BOX KEC KITCHEN EQUIPMENT CONTRACTOR kV KILOVOLTS kVA KILOVOLT-AMPERES kVAR KILOVOLT-AMPERES REACTIVE kW KILOWATTS L or LV LOW VOLTAGE LB POUND LCP LIGHTING CONTROL PANEL LF LINEAR FEET LP LIGHTING PANEL LS LIFE SAFETY LOAD LT LIGHT LTG LIGHTING MAX MAXIMUM MC MECHANICAL CONTRACTOR MCB MAIN CIRCUIT BREAKER MCCB MOLDED CASE CIRCUIT BREAKER MDP MAIN DISTRIBUTION PANEL MECH MECHANICAL MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MSB MAIN SWITCHBOARD NIC NOT IN CONTRACT OCP OVERCURRENT PROTECTION OD OUTSIDE DIAMETER OF/CI OWNER FURNISHED, CONTRACTOR INSTALLED OF/OI OWNER FURNISHED, OWNER INSTALLED OR OPERATING ROOM P POLE PB PUSH BUTTON PC PLUMBING CONTRACTOR PF POWER FACTOR PH, Φ, Ø PHASE PIV POST INDICATOR VALVE PL PILOT LIGHT PNL PANELBOARD PREFAB PREFABRICATED PT PNEUMATIC TUBE PTS PNEUMATIC TUBE STATION PTZ PAN-TILT-ZOOM PW PART WINDING PWR POWER RCPT RECEPTACLE REF REFRIGERATOR RM ROOM RP RECEPTACLE PANEL RPM REVOLUTIONS PER MINUTE SCCR SHORT CIRCUIT CURRENT RATING SG SURGE GUARD SN SOLID NEUTRAL SPEC SPECIFICATIONS SQ FT SQUARE FEET SS SAFETY SWITCH SSBJ SUPPLY SIDE BONDING JUMPER STD STANDARD STN STATION STR STRUCTUR(E),(AL) SUSP SUSPENDED SW SWITCH SWBD SWITCHBOARD SWGR SWITCHGEAR TCC TEMPERATURE CONTROL (CONTRACTOR), (CABINET) TELE TELECOMMUNICATION TEMP TEMPORARY TV TELEVISION TYP TYPICAL UCR UNDER COUNTER REFRIGERATOR UG UNDERGROUND UH UNIT HEATER UNO UNLESS NOTED OTHERWISE V VOLT VFD VARIABLE FREQUENCY DRIVE VP VAPORPROOF W/ WITH W/O WITHOUT WP WEATHERPROOF WTR WATER Z IMPEDANCE ADA ACCESSIBLE ROOM - ALL OPERABLE DEVICES SHALL BE MOUNTED BETWEEN 18" AFF TO BOTTOM AND 48" AFF TO TOP OF DEVICE. HEARING IMPAIRED COMMUNICATIONS FEATURE ROOM - VISUAL NOTIFICATION REQUIRED FOR AS SHOWN ON PLANS. KEYED DEMOLITION PLAN NOTE KEYED NEW WORK PLAN NOTE 01 01 SECTION VIEW REFERENCE VIEW REFERENCE, INCLUDING DETAILS & ENLARGED PLANS 1 E-301 1 E-501 1 / E-301 VIEW REFERENCE TAG GENERAL DRAWING ANNOTATIONS 15. ALL WIRING SHALL BE INSTALLED PARALLEL & PERPINDICULAR TO THE BUILDING STRUCTURAL MEMBERS, EXCEPT WHERE INSTALLED UNDERGROUND. 16. A DEDICATED COPPER OR ALUMINUM EGC SHALL BE INSTALLED IN ALL RACEWAYS, EXCEPT IN SERVICE ENTRANCE CONDUITS. PARTICULAR CARE SHALL BE TAKEN TO ELIMINATE OBJECTIONAL CURRENT, SEE GROUNDING & BONDING DETAILS FOR SITE SPECIFIC REQUIREMENTS. 17. IT SHALL BE THE EC'S RESPONSIBILITY TO REVIEW CONDUIT SIZES AND WIRE AMPACITY PRIOR TO INSTALLATION, TO ENSURE A CODE-COMPLIANT INSTALLATION. 18. IT SHALL BE THE EC'S RESPONSIBILITY TO CONTACT THE DESIGNER WITH ANY QUESTIONS, CONCERNS, OR PROPOSED CHANGES BEFORE COMMENCING WORK. 19. CIRCUITS MAY BE COMBINED IN CONDUITS, CABLES, OR RACEWAYS, PROVIDED THAT THE CONDUCTORS ARE PROPERLY DERATED & ALL RACEWAYS ARE SIZED PER THE NEC. NO MORE THAN (9) CURRENT- CARRYING CONDUCTORS ARE ALLOWED PER RACEWAY. 20. CIRCUITS ARE SIZED FOR VOLTAGE DROP BASED ON ESTIMATED ROUTING. THE EC SHALL VERIFY THAT THE ACTUAL ROUTING CHOSEN COMPENSATES FOR VOLTAGE DROP AS FOLLOWS: A. ALL CONDUCTORS SHALL BE SIZED TO PREVENT EXCESSIVE VOLTAGE DROP. FEEDERS SHALL NOT EXCEED 2% VOLTAGE DROP & BRANCH CIRCUITS SHALL NOT EXCEED 3% VOLTAGE DROP. B. IN GENERAL, CONDUCTORS SHALL NOT BE REQUIRED TO INCREASE MORE THAN TWO (2) SIZES FOR THIS PURPOSE, UNLESS NOTED OTHERWISE. C. THE EGC SHALL INCREASE PROPORTIONALLY FROM THE SIZE REQUIRED BY THE NEC, AS REQUIRED BY NEC 250.122(B). 21. WIRES SHALL BE COLOR CODED AS FOLLOWS, OR AS REQUIRED BY THE AHJ: A. 240/120V SYSTEMS = BLACK (L1), RED (L2), WHITE (N) B. 208Y/120V SYSTEMS = BLACK (A), RED (B), BLUE (C), WHITE (N) C. 240D/120V SYSTEMS = BLACK (A), ORANGE (B), BLUE (C), WHITE (N) D. 480Y/277V SYSTEMS = BROWN (A), ORANGE OR PURPLE (B), YELLOW (C), GRAY (N) 22. ALL PANELBOARDS, SWITCHBOARDS, AND SWITCHGEAR SHALL HAVE A PERMANENT LEGEND SHOWING THE DESIGNATED CONDUCTOR COLORS, AS REQUIRED BY NEC 210.5(C). 23. WIRING SHALL BE #12 AWG COPPER, UNO. IN ALL CASES, THE EC SHALL VERIFY THE CORRECT SIZE WIRING IS INSTALLED, FOR A CODE-COMPLIANT INSTALLATION. 24. CONDUCTOR SIZES SHOWN ARE BASED ON 75° C RATED TERMINATIONS PER NEC 110.14(C), UNO. EC SHALL FIELD VERIFY TERMINATIONS TO CONFIRM PRIOR TO TERMINATING CONDUCTORS. 01. ALL MATERIAL & WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, AND ACCEPTED INDUSTRY STANDARDS. 02. THIS PROJECT CONSISTS OF TWO PARTS: THE CONTRACT DRAWINGS & THE PROJECT SPECIFICATIONS. WHERE THESE DOCUMENTS ARE NOT IN AGREEMENT, THE MOST STRINGENT CONDITION SHALL APPLY. IN ALL CASES, THE EC SHALL REQUEST WRITTEN CLARIFICATION. 03. ALTHOUGH NOT ALL BRANCH WIRING & CONDUIT ARE SHOWN ON THESE DRAWINGS, IT IS THE INTENT OF THESE DOCUMENTS THAT A COMPLETE AND FUNCTIONING BRANCH WIRING SYSTEM BE INSTALLED. 04. ALL CONDUITS, CABINETS, CABLES, AND BOXES SHALL BE SECURELY FASTENED AND SUPPORTED PER THE NEC. 05. ALL DIMENSIONS SHALL BE OBTAINED FROM ARCHITECTURAL AND CIVIL SITE PLANS. IN NO CASE SHALL THE ELECTRICAL DRAWINGS BE SCALED. 06. ALL DIMENSIONS SHOWN SHALL BE TO THE CENTERLINE OF THE EQUIPMENT OR DEVICE BOX, UNLESS NOTED OTHERWISE. 07. VERIFY ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT PROVIDED BY OTHERS & CONNECTED BY ELECTRICAL CONTRACTOR, PRIOR TO INSTALLATION OF WIRING, INCLUDING RECEIVING & REVIEWING APPROVED SUBMITTALS FOR EQUIPMENT PROVIDED BY OTHER BUILDING TRADES. 08. THE ENTIRE SET OF PROJECT DRAWINGS HAS INFORMATION PERTAINING TO THE CONSTRUCTION OF THE BUILDING, AND THE ELECTRICAL CONTRACTOR SHALL REVIEW ALL DRAWINGS TO COORDINATE THE INSTALLATION OF ELECTRICAL SYSTEMS. 09. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR COORDINATION OF LIGHTING FIXTURES & EQUIPMENT FURNISHED OR PROVIDED BY OTHERS. EC SHALL TAKE PARTICULAR CARE TO COORDINATE WITH THE FPC, PC, AND THE MC. 10. REFER TO ARCHITECTURAL PLANS & INTERIOR ELEVATIONS TO COORDINATE ALL WALL MOUNTED DEVICES WITH CABINETRY & CASEWORK. ENSURE THAT ALL DEVICE PLATES AND OTHER EQUIPMENT WILL NOT CONFLICT WITH COUNTERTOPS, BACKSPLASHES, WALL TILE, TRIM, ETC. 11. ALL DEVICES MOUNTED ABOVE A COUNTERTOP OR BACKSPLASH SHALL BE INSTALLED AT THE SAME HEIGHT. 12. DEVICES INSTALLED IN BLOCK OR TILED WALLS SHALL BE INSTALLED WITH THE BOX SET ON TOP OF NEAREST COURSE, WITH THE OPENING FOR THE BOX CUT INTO THE COURSE ABOVE. ALL DEVICE BOXES SHALL BE INSTALLED ON TOP OF THE COURSE NEAREST TO THE SCHEDULED MOUNTING HEIGHT. 13. WHERE MULTIPLE DEVICES OF THE SAME VOLTAGE ARE INSTALLED IN CLOSE PROXIMITY, THEY SHALL BE GANGED TOGETHER IN A COMMON BOX AND COVER PLATE. 14. COORDINATE ALL FASTENERS USED WITH WALL, CEILING, AND STRUCTURAL SYSTEMS. EC SHALL TAKE PARTICULAR CARE NOT TO USE FASTENERS IN A METHOD WHICH VIOLATES MANUFACTURER'S INSTALLATION INSTRUCTIONS. GENERAL PROJECT NOTES / SPECIFICATIONS DEVICE TYPE: "X" INDICATES THE TYPES LISTED BELOW, UNO: BLANK = NORMAL POWER / STANDARD RECEPTACLE IG = NORMAL POWER / ISOLATED GROUND RECEPTACLE TR = NORMAL POWER / TAMPERPROOF RECEPTACLE WP = NORMAL POWER / WEATHER RESISTANT RECEPTACLE WITH WEATHERPROOF IN-USE COVER EM = EMERGENCY POWER / STANDARD RECEPTACLE WITH RED BODY USB = NORMAL POWER / STANDARD RECEPTACLE WITH (2) INTEGRAL USB CHARGING PORTS AND 5V POWER SUPPLY OC = INSTALL AT 8" ABOVE COUNTERTOP HEIGHT -COORDINATE WITH ANY BACKSPLASH OR TILED FINISHES RECEPTACLES / ELECTRICAL DEVICES SIMPLEX RECEPTACLE, WALL MOUNTED.X X DUPLEX RECEPTACLE, WALL MOUNTED SOLID CENTER INDICATES DEDICATED CIRCUIT.X SPLIT WIRED DUPLEX RECEPTACLE, WALL MOUNTED. DOUBLE DUPLEX (QUAD) RECEPTACLES, WALL MOUNTED. SOLID CENTER INDICATES DUAL DEDICATED CIRCUITS. X GFCI RATED RECEPTACLE, WALL MOUNTED SOLID CENTER INDICATES DEDICATED CIRCUIT. X SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED ON PLANS, WALL MOUNTED. X DESCRIPTIONSYMBOL MOUNTING HEIGHT +18" AFF +18" AFF +18" AFF +18" AFF +18" AFF +18" AFF DUPLEX RECEPTACLE, CEILING MOUNTED.X N/A JUNCTION BOX X SEE PLANS MULTI-SERVICE CEILING OUTLET, CONFIGURATION AS NOTED ON PLANS, CEILING MOUNTED. X N/A MULTI-SERVICE FLOORBOX OR POKE THRU, CONFIGURATION AS NOTED ON PLANS, FLOOR MOUNTED. X N/A J JUNCTION BOX WITH FLEXIBLE EQUIPMENT CONNECTION, (6) FEET MAX LENGTH.SEE PLANSJ DOUBLE DUPLEX (QUAD) RECEPTACLES, CEILING MOUNTED.N/A MULTI-SERVICE POWER POLE, CONFIGURATION NOTED ON PLANS.N/A PUSHBUTTON, TYPE AND QUANTITY OF BUTTONS AS NOTED ON PLANS.SEE PLANS X X X TTHERMOSTAT, FURNISHED BY OTHERS UNO. SEE MECHANICAL SCHEDULES FOR DETAILS.+44" AFF ABORT SWITCH / EMERGENCY POWER OFF SWITCH, SEE PLANS FOR DETAILS +44" AFFEPO POWER DISTRIBUTION MAIN SWITCHBOARD, MAY BE SWITCHBOARD OR SWITCHGEAR CONSTRUCTION, SEE PLANS FOR DETAILS. FLOOR MOUNTED, FREE STANDING. DASHED LINES REPRESENT CODE REQUIRED CLEARANCES. DESCRIPTIONSYMBOL MSB-A SURFACE MOUNTED DISTRIBUTION PANELBOARD. DASHED LINES REPRESENT CODE REQUIRED CLEARANCES. SURFACE MOUNTED BRANCH PANELBOARD. DASHED LINES REPRESENT CODE REQUIRED CLEARANCES. FLUSH MOUNTED BRANCH PANELBOARD. DASHED LINES REPRESENT CODE REQUIRED CLEARANCES. HV-1 HV-1 T-1 DRY TYPE TRANSFORMER, 15kVA OR LARGER. T DRY TYPE TRANSFORMER, LESS THAN 15kVA. SEE PLANS FOR DETAILS. SEGB SERVICE ENTRANCE GROUNDING BUS. SEE PLANS FOR DETAILS. NF DISCONNECT SWITCH, NON-FUSED. MOUNT AT 48" AFF, UNO. DISCONNECT SWITCH, FUSIBLE. FUSE RATING SHOWN. MOUNT AT 48" AFF, UNO. COMBINATION MOTOR STARTER / FUSIBLE DISCONNECT. NEMA STARTER SIZE AND FUSE RATING SHOWN. MOUNT AT 48" AFF, UNO. 60A N1/60A ELECTRIC MOTOR, NUMBER INDICATES HORSEPOWER. NOT DRAWN TO SCALE.500 25,769 A AVAILABLE BOLTED FAULT CURRENT FEEDER TAG, SEE SCHEDULE FOR DETAILS.F0500NG-CU ~150', 1.5% VD LIGHTING FIXTURES / DEVICES FIXTURE TYPES AND/OR SWITCHING ARE INDICATED AS LISTED BELOW, UNO: # = FIXTURE TYPE MARK, REFER TO FIXTURE SCHEDULES. NL = "NIGHT LIGHT" FIXTURE, WIRED FOR 24 HOUR OPERATION. a,b = INDICATES SWITCH GROUP WITHIN ROOM OR AREA SHADING INDICATES FIXTURE EITHER CONTAINS AN INTEGRAL BATTERY OPERATED EMERGENCY INVERTER OR IS CONNECTED TO AN EMERGENCY POWER SUPPLY SYSTEM. REFER TO PLANS FOR DETAILS. DESCRIPTIONSYMBOL MOUNTING HEIGHT RECESSED FIXTURE NL # a,b a,b # SURFACE MOUNTED FIXTURE # a,b LINEAR FIXTURE, SUSPENDED. RECESSED DOWNLIGHT. ARROW INDICATES DIRECTION OF WALL WASH LENS, WHERE USED. # a,b # a,b WALL MOUNTED FIXTURES # NL a,b SURFACE MOUNTED STRIP FIXTURES # # # # EMERGENCY EXIT SIGN. SHADING INDICATES FACES USED, ARROWS INDICATE EGRESS PATH. MAY BE CEILING MOUNTED, NOT EXCEEDING +12'-0" AFF. WALL MOUNTED EMERGENCY LIGHTING UNIT SEE SCHEDULES SEE SCHEDULES SEE SCHEDULES SEE SCHEDULES SEE SCHEDULES SEE SCHEDULES +8'-0" AFF +8'-0" AFFEMERGENCY LIGHTING REMOTE HEAD, MOUNT +12" ABOVE DOOR FRAMES OR AS NOTED. WALL = +8'-0" AFF X a DEVICE TYPE: "X" INDICATES THE TYPES LISTED BELOW, UNO: BLANK = SINGLE POLE TOGGLE SWITCH 2 = DOUBLE POLE TOGGLE SWITCH 3 = THREE WAY TOGGLE SWITCH 4 = FOUR WAY TOGGLE SWITCH M = MOTOR RATED SWITCH LV = DIGITAL LOW VOLTAGE SWITCH D = DIMMING SWITCH T = TIMER SWITCH WP = WEATHERPROOF SWITCH K = KEY OPERATED SWITCH OS = OCCUPANCY SENSOR SWITCH +48" AFF OS a SEE SCHEDULES OCCUPANCY SENSOR, TYPE AS INDICATED IN SCHEDULES. PC a SEE SCHEDULES PHOTOCELL, TYPE AS INDICATED IN SCHEDULES. PP a SEE SCHEDULES LIGHTING CONTROL RELAY, TYPE AS INDICATED IN SCHEDULES. DEVICE TYPE: "X" INDICATES THE TYPES LISTED BELOW, UNO: BLANK = STANDARD OUTLET, SINGLE PORT FOR EACH SYSTEM TYPE PRESENT # (2,4..) = NUMBER OF PORTS FOR TYPE OF SYSTEM PRESENT W = WALL MOUNTED AT 44", UNO OC = INSTALL AT 8" ABOVE COUNTERTOP HEIGHT -COORDINATE WITH ANY BACKSPLASH OR TILED FINISHES WAP = WIRELESS ACCESS POINT TELECOMMUNICATIONS / AUDIO-VISUAL DATA OUTLET, WALL MOUNTEDX X COMBINATION DATA / TELEPHONE OUTLET, WALL MOUNTEDX TELEPHONE OUTLET, WALL MOUNTED DESCRIPTIONSYMBOL MOUNTING HEIGHT +18" AFF +18" AFF +18" AFF INTERCOM STATION, SEE PLANS FOR TYPE +42" AFF DATA OUTLET, CEILING MOUNTEDX N/A SINGLE-LINE DIAGRAM DESCRIPTIONSYMBOL 400AT 400AF LSI CIRCUIT BREAKER -TRIP RATING / FRAME SIZE, AND/OR NUMBER OF POLES. SETTINGS AND OTHER ACCESSORIES AS NOTED ON PLANS. 400AT 400AF LSIG EB DRAWOUT CIRCUIT BREAKER -TRIP RATING / FRAME SIZE, AND/OR NUMBER OF POLES. SETTINGS AND OTHER ACCESSORIES AS NOTED ON PLANS. TRANSFORMER - VOLTAGE CONFIGURATION, KVA RATING, WIRING CONFIGURATION. SEE PLANS FOR OTHER DETAILS AND REQUIREMENTS. T-1 2,500 kVA 480D-208Y/120V 3000-5 CURRENT TRANSFORMER -RATIO OF PRIMARY TO SECONDARY WINDINGS. 480-120 75 VA POTENTIAL TRANSFORMER -RATIO OF PRIMARY VOLTAGE TO SECONDARY VOLTAGE, HEAT RATING. 1000A BPS DISCONNECT SWITCH - FRAME SIZE. "BPS" INDICATES BOLTED PRESSURE SWITCH. 1000A CLASS J FUSE - TRIP RATING, FUSE CLASS. ELECTRONIC BREAKER OPERATORS: EB = MOTOR OPERATED CLOSE / OPEN GF = GROUND FAULT TRIP UNIT ST = SHUNT TRIP OPEN UV = UNDERVOLTAGE RELEASE 400AT 400AF LSIG GF GROUND CONNECTION N E TRANSFER SWITCH, SEE PLANS FOR TYPE AND OTHER DETAILS. ARC INDICATES CLOSED TRANSITION. SPD SURGE PROTECTIVE DEVICE, SEE PLANS. ELECTRONIC METER, SEE PLANS FOR TYPE. KEYED INTERLOCK, SEE PLANS FOR DETAILS. PROTECTIVE RELAY, SEE PLANS FOR DETAILS. M K1 R1 ELECTRICAL CONNECTION, BOLT / LUG / SCREW. CIRCUITS PHASE CONDUCTORS GROUND CONDUCTOR (IF TWO ARE SHOWN, THE SECOND SHALL BE AN ISOLATED GROUND) NEUTRAL CONDUCTOR CONDUITS DESCRIPTIONSYMBOL CONDUIT / RACEWAY, SEE PLANS FOR TYPE. CONDUIT / RACEWAY, UNDERGROUND, SEE PLANS FOR TYPE. CONDUIT TRANSITIONSDOWN UP CONDUIT / RACEWAY, CAPPED AND SEALED. OVERHEAD ELECTRICAL CONDUCTORS UNDERGROUND ELECTRICAL RACEWAY TELECOM SERVICE, UNDERGROUND DEMOLITION / NEW CONSTRUCTION DESCRIPTION SYMBOL XXa NL # a,b DASHED LINES INDICATE DEVICE TO BE REMOVED / DEMOLISHED.XXa NL # a,b THIN LINES INDICATE DEVICE FROM PREVIOUS PHASE / EXISTING CONDITIONS.XXa NL # a,b SOLID, HEAVY LINES INDICATE DEVICE TO BE INSTALLED DURING PHASE SHOWN / NEW WORK. ELECTRONIC SECURITY KEYPAD, WALL MOUNTED. DESCRIPTIONSYMBOL MOUNTING HEIGHT +54" AFF CARD READER, WALL MOUNTED.+42" AFF BIOMETRIC ACCESS CONTROL SEE PLANS PUSH BUTTON, SEE PLANS FOR TYPE SEE PLANS CONTACT SWITCH, SEE PLANS FOR TYPE SEE PLANS CONTROL PANEL +60" AFF SECURITY CAMERA, SEE PLANS FOR TYPE SEE PLANS AUDIO DEVICE, SEE PLANS FOR TYPE SEE PLANS DETECTOR, SEE PLANS FOR TYPE SEE PLANS GLASS BREAK SENSOR SEE PLANS ELECTRONIC LOCK, SEE PLANS FOR TYPE SEE PLANS VEHICLE GROUND LOOP SENSOR N/A ADDRESSABLE OUTPUT RELAY N/A FIRE ALARM / DETECTION FACP DESCRIPTIONSYMBOL MOUNTING HEIGHT FIRE ALARM CONTROL PANEL, WALL MOUNTED +60" AFF, TOP NAC FIRE ALARM NAC PANEL, WALL MOUNTED +60" AFF, TOP FAA FIRE ALARM ANNUNCIATOR, WALL MOUNTED +48" AFF F MANUAL PULL STATION / FIRE ALARM BOX, WALL MOUNTED +48" AFF, TOP FIRE SERVICE PHONE STATION, WALL MOUNTED +48" AFF, TOP VISIBLE (STROBE) NOTIFICATION DEVICE, WALL OR CEILING MOUNTED SEE PLANScd AUDIBLE/VISIBLE (HORN/STROBE) NOTIFICATION DEVICE, WALL OR CEILING MOUNTED SEE PLANScd cd AUDIBLE (HORN) NOTIFICATION DEVICE, WALL OR CEILING MOUNTED SEE PLANSF S x AUTOMATIC SMOKE DETECTOR, CEILING OR WALL MOUNTED. DEVICE TYPE: "X" INDICATES TYPES LISTED BELOW, UNO: AS = AIR SAMPLING I = IONIZATION P = PHOTOELECTRIC R = RELAY MODULE BASE SB = SOUNDER BASE (520 Hz OPTIONAL) IM = ISOLATOR MODULE BASE SS = SINGLE/MULTIPLE STATION SMOKE ALARM SEE PLANS AUTOMATIC SMOKE DETECTOR, PHOTOELECTRIC TYPE DETECTION, DUCT MOUNTED IN DUCT S P AUTOMATIC HEAT DETECTOR, CEILING OR WALL MOUNTED. DEVICE TYPE: "X" INDICATES TYPES LISTED BELOW, UNO: F = FIXED TEMPERATURE R = RATE OF RISE R/F = COMBINATION RISE/FIXED TEMP R/C = RATE COMPENSATED SEE PLANSH x ADDRESSABLE INPUT MODULE, "X" INDICATES NUMBER OF INPUTS SEE PLANSAIM x ADDRESSABLE OUTPUT MODULE, "X" INDICATES NUMBER OF OUTPUTS SEE PLANSAOM x POST INDICATOR VALVE SUPERVISORY SWITCH SEE PLANS PRESSURE SWITCH SUPERVISORY DEVICE SEE PLANS WATER FLOW SUPERVISORY SWITCH SEE PLANS VALVE (TAMPER) SUPERVISORY SWITCH SEE PLANS MAGNETIC DOOR HOLDER SEE PLANSDH No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:43 AM 1 /8" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032SYMBOLS &ABBREVIATIONSMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-001 JLS 1 2/1 3/2021 21 083 ELECTRICAL SHEET INDEX SHEET No. SHEET NAME REV No. REV DATE E-001 SYMBOLS & ABBREVIATIONS 1 01/17/2022 E-100 ELECTRICAL DEMOLITION PLAN 1 01/17/2022 E-101 POWER & SYSTEM PLAN 1 01/17/2022 E-102 LIGHTING PLAN 1 01/17/2022 E-501 ONE-LINE DIAGRAM 1 01/17/2022 E-601 SCHEDULES 1 01/17/2022 E-701 DETAILS 1 01/17/2022 E-702 DETAILS 1 01/17/2022 REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:48 AM 1 /8" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032ELECTRICAL DEMOLITIONPLANMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-100 JLS 1 2/1 3/2021 21 083 DEMOLITION - GENERAL NOTES A DEMOLISH / MAKE SAFE ALL ELECTRICAL DEVICES AND FIXTURES WITHIN THE SCOPE OF WORK, AS INDICATED ON THE DRAWINGS. ALL EXISTING HOME RUNS ARE TO BE MADE SAFE AND COILED UP NEAR THE CEILING, TO BE REUSED FOR NEW CONSTRUCTION. B PROVIDE TEMPORARY CONSTRUCTION LIGHTING AND POWER, IF REQUIRED BY THE CONTRACT. ALL TEMPORARY CIRCUITS SHALL BE GFCI PROTECTED. C REMOVE AND SALVAGE EXISTING FIRE ALARM SYSTEM DEVICES ONLY WITHIN THE SCOPE OF THE PROJECT, AND IN COORDINATION WITH THE FIRE ALARM SYSTEM MONITORING COMPANY. REWORK FIRE ALARM SYSTEM CIRCUITS AS NECESSARY TO KEEP THE SYSTEM FULLY FUNCTIONING DURING CONSTRUCTION. 1/8" = 1'-0"2 ELECTRICAL DEMOLITIOM PLAN SHEET E-100 - KEYED NOTES 01 REMOVE AND RELOCATE EXISTING LIGHT FIXTURES IN THIS AREA. 01 01 N REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 30/72E30/72E30/72E30/72E30/60E 30/60E30/60E 30/60E30/72E30/72E24/84 24/9636/7224/84 24/9636/7224/84 24/9636/7224/84 24/9636/7220/6620/6620/6620/6624/84 24/9636/7224/84 24/9636/72UP UP VAN 2 3 2 3 2 3 2 3 2 3 2 3 23 2 23 2 1 25 W/FT ELECTRIC BASEBOARD HEAT BELOW EXTERIOR GLAZING (TYP.) 1.83-8 480 CFM 1.9 3-8475 CFM 1.10 3-8650 CFM 1.115-1 21 500CFM J J J J J J RAMP 01 1ELP-2 TX-1 1ERP-2 1ERP-2#2 1ERP-2#2 1ERP-2#2 1ERP-2#5 1ERP-2#5 1ERP-2#5 1ERP-2#3 1ERP-2#3 1ERP-2#3 1ERP-2#1 1ERP-2#1 1ERP-2#1 1ERP-2#3 1ERP-2#3 1ERP-2#3 1ERP-2#11ERP-2#1 1ERP-2#1 1ERP-2#4 1ERP-2#4 1ERP-2#41ERP-2#4 1ERP-2#21ERP-2#2 1ERP-2#7 1ERP-2#7 1ERP-2#7 1ERP-2#7 1ERP-2#6 1ERP-2#6 1ERP-2#6 1ERP-2#61ERP-2#41ERP-2#4 1ERP-2#4 1ERP-2#41ERP-2#21ERP-2#2 1ERP-2#7 1ERP-2#7 1ERP-2#71ERP-2#7 1ERP-2#5 1ERP-2#5 1ERP-2#6 1ERP-2#9 1ERP-2#9 1ERP-2#11 1ERP-2#101ERP-2#8 1ERP-2#11 1ERP-2#9 1ERP-2#9 1ERP-2#12 1ERP-2#13 1ERP-2#13 1ERP-2#12 1ERP-2#13 1ERP-2#12 1ELP-2#1,3,5 (3#10,#10G) 1ELP-2#141ELP-2#16 02 02 03 04 EXISTING VAV BOXES 1LPA-25,27,291LPA-20,22,24 1LPA-26,28,30 (1) 2"C FROM EXISTING SERVICE (1) 2"C TO NEW 200A, 480V, 3P PANEL IN STORAGE ROOM 1ELP-2#8,10,12 02 02 02 02 1ELP-2#15 1ELP-2#17 1ELP-2#18 1ELP-2#19 1ERP-2#15 1ERP-2#17 05 05 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:50 AM 1 /8" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032POWER & SYSTEM PLANMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-101 JLS 1 2/1 3/2021 21 083 1/8" = 1'-0" 1 POWER & SYSTEMS PLAN POWER - GENERAL NOTES A EXPOSED CABLES INSTALLED IN A PLENUM SPACE SHALL BE PLENUM RATED AND CONFORM TO THE CURRENT NEC. (NEC ART. 300.22(C)) B ALL RECEPTACLES MOUNTED AT OR ABOVE COUNTERS, SHELVES, ETC., SHALL BE VERIFIED WITH THE OWNER PRIOR TO ROUGH-IN. C ALL RECEPTACLES MOUNTED WITHIN 6' OF A SINK, OR AS NOTED IN THE NEC, SHALL BE GFCI PROTECTED. (NEC ART. 210.8) D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER. E ALL UNDERGROUND CONDUITS SHALL BE WATERTIGHT AND CLEAR OF ANY DEBRIS PRIOR TO THE INSTALLATION OF CABLES / CONDUCTORS. SEAL BOTH ENDS WITH AN APPROVED SEALENT ONCE INSTALLATION IS COMPLETE, TO PREVENT THE ENTRANCE OF WATER OR AIR. (NEC ART. 225.27) F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC. G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A)) H ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY. J MINIMIZE ROOF PENETRATIONS BY MOUNTING DISCONNECTS TO THE ROOFTOP EQUIPMENT IT SERVES. SHEET E-101 - KEYED NOTES 01 PROVIDE (2) 1" CONDUITS TO FLOOR RECEPT/DATA BOX UNDER CONFERENCE ROOM TABLE. STUB CONDUIT UP NEAREST WALL TO ABOVE CEILING. 02 PROVIDE JUNCTION BOX FOR BASEBOARD HEAT CONNECTION. 03 RELOCATED VAV BOX. EXTEND EXISTING CIRCUIT AND RECONNECT. 04 NEW VAV BOX. PROVIDE NEW 3P, 20A CIRCUIT. 05 PROVIDE SINGLE GANG BOX FOR TOUCHSCREEN WALL CONTROL. VERIFY LOCATION WITH DOOR INSTALLER. N REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 TBW24/72 TBW24/36 TBW24/72TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 TBW24/72 TBW24/36 30/72E30/72E30/72E30/72E30/60E 30/60E30/60E 30/60E30/72E30/72EC1 BF C1 BF C1 BF C1 BF C1 BF C1 BF 24/84 24/9636/7224/84 24/9636/7224/84 24/9636/7224/84 24/9636/7220/6620/6620/6620/6624/84 24/9636/7224/84 24/9636/72UP UP FIRST FLOOR EL: -2' - 0" FIRST FLOOR EL: 0' - 0"2 3 2 3 2 3 2 3 2 3 2 3 OSOSOSOSOSOSDOS OSOSD D OS OSPP OS OS OS1023 OS OS OSPP SW2 OS PP PP PP OS OS PP PP PP OS OS RAMP L1 1ELP-2#7 L1 1ELP-2#7 L1 1ELP-2#7 L1 1ELP-2#7L1 1ELP-2#7 L1 1ELP-2#7 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#13 L1 1ELP-2#11 L1L1 1ELP-2#11L1L1 1ELP-2#11 L1 1ELP-2#11L1L1 1ELP-2#11 L1 1ELP-2#11 L1 1ELP-2#11 L1 1ELP-2#11 L1 1ELP-2#11 L1 L1 1ELP-2#11 1ERP-21ELP-2 TX-1 01 01 01 L2 L2 L2 03 02 X1 EXL3 EXL3 EXL3 EXL3 EXL3 EXL3 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 EXL4 1ELP-2#9 L5 L5 L5 L5 L5 L5L5 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 L4 1ELP-2#9 02 02 02 02 L6 1ELP-2#13 EXL3 L2 X1 02 02 X1 01 04 04 ETS ETS ETS ETS ETS 1/8" = 1'-0" 1 LIGHTING PLAN LIGHTING - GENERAL NOTES A REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT PLACEMENT OF ALL LIGHTING FIXTURES. VERIFY CEILING CONSTRUCTION AND PROVIDE LIGHTING FIXTURES WITH ALL NECESSARY MOUNTING HARDWARE. B RECESSED FIXTURES SHALL BE PROVIDED WITH STRUCTURAL SUPPORTS, AS REQUIRED BY THE AHJ. IF REQUIRED, REFER TO DETAIL SHEETS FOR INSTALLATION REQUIREMENTS. C RECESSED FIXTURES LOCATED IN A FIRE RATED CEILING SHALL BE PROVIDED WITH A FIVE SIDED ENCLOSURE, WITH A FIRE RATING GREATER THAN OR EQUAL TO THE RATING OF THE CEILING ASSEMBLY. THE ENCLOSURE SHALL MEET ALL NEC AND MANUFACTURER REQUIRED CLEARANCES. D ALL WORK SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE BUILDING STRUCTURE, WHERE EXPOSED. ALL EXPOSED WIRING SHALL BE IN CONDUIT, UNLESS OTHERWISE APPROVED BY OWNER. E ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROPERLY SEALED WITH AN APPROVED FIRE STOP SYSTEM GREATER THAN OR EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY. F RACEWAYS SHALL NOT BE PERMITTED TO SERVE AS AN EGC. G ALL EXTERIOR PENETRATIONS, AND / OR PENETRATIONS THROUGH A THERMAL ENVELOPE, SHALL BE SEALED WITH AN APPROVED SEALANT TO PREVENT THE ENTRANCE OF AIR OR WATER. (NEC ART. 300.7(A)) H EMERGENCY LIGHTING WITH INDIVIDUAL BATTERY BACKUP SHALL BE FED FROM THE SAME CIRCUIT AS THE LIGHTING IN THE AREA WHICH IT SERVES. (NEC ART. 700.12(F)) No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:54 AM 1 /8" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032LIGHTING PLANMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-102 JLS 1 2/1 3/2021 21 083 SHEET E-102 - KEYED NOTES 01 RELOCATE DEMOED 'L3' TYPE LIGHT FIXTURES IN THE AREA. 02 WIRE NEW EXIT/EMERGENCY LIGHTING TO THE CLOSEST EXISTING EMERGENCY LIGHTING CIRCUIT 1ELP-3. 03 RELOCATE DEMOED LIGHT FIXTURES IN THE AREA 04 SEE DETAILS FOR LIGHTING CONTROLS IN THIS AREA ON SHEET E-701. N REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:54 AM410 MONON TRAIL, CARMEL, IN 46032ONE-LINE DIAGRAMMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-501 JLS 1 2/1 3/2021 21 083 T-1 30 kVA 480D-208Y/120V 1ELP-2 200A 480/277V 3PH-4W 1ERP-2 100A 208/120V 3PH-4W MDP SHEET E-501 - KEYED NOTES DISTRIBUTION - GENERAL NOTES A CONDUIT SIZES ARE MINIMUM GUIDELINES, AND MAY NOT COVER ALL INSTALLATIONS. IT IS ACCEPTABLE TO ADJUST CONDUIT SIZE BASED ON RACEWAY TYPE, PER NEC REQUIREMENTS. B EACH PARALLEL RUN SHALL BE ELECTRICALLY SIMILAR, AND CONTAIN THE SAME NUMBER OF CONDUCTORS / CABLES. COMPLY WITH ALL NEC REQUIREMENTS FOR PARALLEL INSTALLATIONS. (NEC ART. 310.10(H)) C SEPARATELY DERIVED SYSTEMS SHALL HAVE A SUPPLY SIDE BONDING JUMPER INSTALLED PER NEC ART. 250.102(C), WHERE APPLICABLE. (NEC ART. 250.30(A)(2)) D EC SHALL COORDINATE THE AIC RATINGS OF ALL EQUIPMENT AND VERIFY THAT IT IS CORRECT, PRIOR TO PURCHASE / INSTALLATION OF EQUIPMENT. SERIES RATINGS SHALL NOT BE ALLOWED FOR EQUIPMENT SERVING MOTOR LOADS. (NEC ART. 240.86(C)) E EMERGENCY SYSTEMS SHALL BE ISOLATED AND MARKED AS REQUIRED BY CODE. (NEC ART. 700.7(A) & NEC ART. 700.10) F WHERE GROUND FAULT PROTECTION IS REQUIRED, A FUNCTIONAL PERFORMANCE VERIFICATION TEST SHALL BE PERFORMED AFTER THE EQUIPMENT IS INSTALLED, PRIOR TO BEING ENERGIZED BY THE SOURCE. UTILIZING THE "PUSH TO TRIP" FEATURE IS NOT ALLOWED. TESTING SHALL BE PERFORMED UTILIZING A PRIMARY CURRENT INJECTION TEST SET. THE TESTING RESULTS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD AND BE MADE AVAILABLE UPON REQUEST TO THE AHJ. IT IS THE RESPONSIBILITY OF THE EC TO DETERMINE IF THIRD PARTY TESTING IS REQUIRED BY THE AHJ. (NEC ART. 230.95) NOTES: 1. SIZING IS BASED ON THHN/THWN-2 OR XHHW WIRING, EMT/IMC/GRC/FMC/ SCH. 40 PVC CONDUIT, 75C TERMINATIONS PER NEC ART. 110.14(C). MOTOR EQUIPMENT GROUNDING CONDUCTORS BASED ON 250% x FLA OVERCURRENT PROTECTION. 2. DESIGNATION DEFINITIONS: (F0000NG-AL) "F" = FEEDER "M" = MOTOR FEEDER / BRANCH CIRCUIT "T" = TRANSFORMER SECONDARY CONDUCTORS "0000" = INDICATES FEEDER ID NUMBER, GROUPED BY AMPACITY "N" = PROVIDE NEUTRAL / GROUNDED CONDUCTOR "G" = PROVIDE GROUND CONDUCTOR "-AL" OR "-CU" = INDICATES ALUMINUM OR COPPER CONDUCTORS 3. SOME FEEDERS MAY NOT BE USED ON THIS PROJECT. FEEDER SCHEDULE FEEDER ID CONDUCTOR SIZE AND QUANTITY PER CONDUIT / RUN (AWG OR KCMIL) CONDUIT SIZE AND TOTAL QUANTITY PHASE NEUTRAL GROUND SIZE No. OF RUNS F0030G-CU (3) 10 -- (1) 10 3/4"1 F0050G-CU (3) 8 -- (1) 10 3/4"1 F0200NG-AL (3) 4/0 (1) 4/0 (1) 4 2"1 T0100NG-CU (3) 1 (1) 1 (1) 6 1-1/2"1 A/C UNIT F0200NG-AL F0050G-CU T0100NG-CU F0030G-CU REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:54 AM410 MONON TRAIL, CARMEL, IN 46032SCHEDULESMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-601 JLS 1 2/1 3/2021 21 083 LIGHTING FIXTURE SCHEDULE MARK QTY. DESCRIPTION MANUFACTURER MODEL FIXTURE DATA COMMENTS / MOUNTING INSTRUCTIONSLAMP CCT LUMENS ELEC. DATA EFFICACY EXL3 7 EXISTING 6" DOWNLIGHT FIXTURE RELOCATED FROM DEMO. Acuity Brands Lighting LDN6 35/20 L06AR LSS MVOLT GZ10 LED 3500 K 0 lm 277 V/1-0 VA EXL4 12 EXISTING 48" STRIPLIGHT, MVOLT OR 347V, 0-10 DIMMING, 3500K 80CRI, WHITE, RELOCATED FROM DEMO. Acuity Brands Lighting CDS L48 MVOLT DM 35K 80CRI WH LED 3500 K 0 lm 277 V/1-0 VA L1 36 BLT 2X4, 4000 NOMINAL LUMENS, CURVED LINEAR PRISMATIC LENS, 3500K CCT Acuity Brands Lighting 2BLT4 40L ADP LP835 LED 3500 K 0 lm 277 V/1-0 VA L2 5 EXTRUDED ALLUMINUM HOUSING, DIE CAST ALUMINUM END PLATES, EXTRUDED ASYMMETRIC OPTICS. THE LIGHTING QUOTIENT S410-M24C-X-13-M-00-0-835-ZX (LIGHTING THE CEILING.) LED 3500 K 41778 lm 277 V/1-0 VA L4 10 EXISTING 48" STRIPLIGHT, MVOLT OR 347V, 0-10 DIMMING, 3500K 80CRI, WHITE, RELOCATED FROM DEMO. Acuity Brands Lighting CDS L48 MVOLT DM 35K 80CRI WH LED 3500 K 0 lm 277 V/1-0 VA L5 7 6" LDN CYLINDER, 3500K, 3000LM, CLEAR, SEMI-SPECULAR REFLECTOR, CRI80 Acuity Brands Lighting LDN6CYL 35/30 LO6AR LSS LED 3500 K 0 lm 277 V/1-35 VA 0 lm/W L6 1 Round Luminaire Prudential Lighting P3950-LED35 MO FWA YSTM D1 SC UNV 3/4RPM48" X1 DM01 Biax 3500 K 11400 lm 277 V/1-78 VA 146 lm/W X1 3 EXIT LIGHT, GREEN EDGE LIT, DOUBLE FACE Acuity Brands Lighting ELT-FT AC G 1C BA MRC AU LED 277 V/1-5 VA EST. DEMAND AMPS: 4 A CONNECTED AMPS: 4 A EST. DEMAND LOAD: 3.1 kVA Lighting 78 VA 125.00% 98 VA CONNECTED LOAD: 3.1 kVA Power 3000 VA 100.00% 3000 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR EST. DEMAND LOAD PANEL TOTALS 1 = BREAKER LOCK-ON DEVICE | 2 = PADLOCKABLE LOCKOUT DEVICE | 3 = FIRE ALARM | 4 = 6mA GFCI | 5 = 30mA GFCI 6 = SHUNT TRIP | 7 = COMBINATION AFCI/GFCI ACCESSORIES LEGEND: TOTAL CONNECTED AMPS: 4 A 4 A 4 A TOTAL CONNECTED LOAD (kVA): 1.1 kVA 1.0 1.0 41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26 23 24 21 22 19 BASEBOARD HEATER 20 A 1 2 A / 0 A 20 17 BASEBOARD HEATER 20 A 1 2 A / 2 A 1 20 A BASEBOARD HEATER 18 15 BASEBOARD HEATER 20 A 1 2 A / 2 A 1 20 A BASEBOARD HEATER 16 13 LIGHTING 20 A 1 0 A / 2 A 1 20 A BASEBOARD HEATER 14 11 LIGHTING 20 A 1 0 A / 0 A 12 9 LIGHTING 20 A 1 0 A / 0 A 10 7 LIGHTING 20 A 1 0 A / 0 A 3 20 A VAV BOX 8 5 0 A / 0 A 6 3 0 A / 0 A 4 1 A/C UNIT 30 A 3 0 A / 0 A 3 20 A TX-1 2 CKT DESCRIPTION ACC. TRIP # A B C # TRIP ACC. DESCRIPTION CKT NOTES: TOP OR BOTTOM FEED:SE Rated: BUS / MCB RATING: 200 A NEMA ENCLOSURE RATING: Type 1 MAINS TYPE: MOUNTING: Surface No. OF WIRES: 4 SERIES A.I.C. RATING: SUPPLY FROM:No. OF PHASES: 3 A.I.C. RATING: LOCATION:VOLTAGE: 480Y/277 V MAX. FAULT (Isc) : PANELBOARD:1ELP-2 EST. DEMAND AMPS: 39 A CONNECTED AMPS: 43 A EST. DEMAND LOAD: 14.0 kVA Receptacle 13500 VA 87.04% 11750 VA CONNECTED LOAD: 15.5 kVA Motor 2024 VA 112.50% 2277 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR EST. DEMAND LOAD PANEL TOTALS 1 = BREAKER LOCK-ON DEVICE | 2 = PADLOCKABLE LOCKOUT DEVICE | 3 = FIRE ALARM | 4 = 6mA GFCI | 5 = 30mA GFCI 6 = SHUNT TRIP | 7 = COMBINATION AFCI/GFCI ACCESSORIES LEGEND: TOTAL CONNECTED AMPS: 53 A 48 A 32 A TOTAL CONNECTED LOAD (kVA): 6.1 kVA 5.5 3.9 41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26 23 24 21 22 19 20 17 OVERHEAD DOOR...20 A 1 8 A / 0 A 18 15 OVERHEAD DOOR...20 A 1 8 A / 0 A 16 13 RECEPTACLE 20 A 1 5 A / 0 A 14 11 RECEPTACLE 20 A 1 3 A / 5 A 1 20 A RECEPTACLE 12 9 RECEPTACLE 20 A 1 6 A / 2 A 1 20 A RECEPTACLE 10 7 RECEPTACLE 20 A 1 18 A / 2 A 1 20 A RECEPTACLE 8 5 RECEPTACLE 20 A 1 9 A / 8 A 1 20 A RECEPTACLE 6 3 RECEPTACLE 20 A 1 12 A / 18 A 1 20 A RECEPTACLE 4 1 RECEPTACLE 20 A 1 12 A / 15 A 1 20 A RECEPTACLE 2 CKT DESCRIPTION ACC. TRIP # A B C # TRIP ACC. DESCRIPTION CKT NOTES: TOP OR BOTTOM FEED:SE Rated: BUS / MCB RATING: 100 A NEMA ENCLOSURE RATING: Type 1 MAINS TYPE: MOUNTING: Surface No. OF WIRES: 4 SERIES A.I.C. RATING: SUPPLY FROM:No. OF PHASES: 3 A.I.C. RATING: LOCATION:VOLTAGE: 208Y/120 V MAX. FAULT (Isc) : PANELBOARD:1ERP-2 REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:54 AM 1 2" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032DETAILSMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-701 JLS 1 2/1 3/2021 21 083 12" = 1'-0"1 NIGHT LIGHT EMERGENCY WIRING DIAGRAMS REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22 No. 1 2000739 STATE OF JA R E D RICHEY RE G I STERED INDIAN APROFESSIONAL E N GINEER DRAWING No. :PROJECT NAME :DRAWING TITLE :ORIGINAL DRAWING IS : 30"x42" DEEM MECHANICAL & ELECTRICAL, LLC. RESERVES THE RIGHT TO REVISE THE DESIGN OF THE ELECTRICAL AND/OR MECHANICAL SYSTEMS PROVIDING THE CHANGES MEET THE DESIGN/BUILD SPECIFICATIONS FOR THIS PROJECT. 1 A 2 3 4 5 6 1 2 3 4 5 6 B C D E A B C D E DRAWN BY : DATE : SCALE : PROJECT No. : 1 /1 7/2022 1 0:1 2:54 AM 1 2" = 1 '-0"410 MONON TRAIL, CARMEL, IN 46032DETAILSMERCHANTS CORPORATECENTER OFFICE ANDSOCIAL HUB TIE-702 Author 1 2/1 3/2021 21 083REVISION SCHEDULENo. DESCRIPTION DATE1 STATESUBMISSIONS01/17/202201/31/22