DESIGN NO. U305 GENERIC 1 HOUR FIRE 56 STC - SOUND
16" O.C.
THICKNESS: 4-3/4"
PROJECT USE: 2X4 & 2x6 INTERIOR WALLS AND PARTITIONS (1 HOUR RATED LOAD BEARING WALLS)
GYPSUM WALLBOARD, WOOD STUDS (LOAD BEARING)
NOMINAL 2 BY 4 IN. FRAMING SPACED 16IN. O.C. MAX., EFFECTIVELY FIRESTOPPED. 5/8 IN. THICK PAPER OR VINYL SURFACED, WITH BEVELED,
SQUARE, OR TAPERED EDGES, APPLIED EITHER HORIZONTALLY OR VERTICALLY TO BOTH SIDES OF THE WALL. GYPSUM PANELS FASTENED TO
FRAMING WITH 1-1/4 IN. LONG TYPE W COURSE THREAD GYPSUM PANEL STEEL SCREWS SPACED AT MAX. 8 IN. O.C. WITH LAST SCREW 1 IN. FROM
EDGE OF BOARD. WHEN USED IN WIDTHS OF OTHER THAN 48 IN., GYPSUM PANELS ARE TO BE INSTALLED HORIZONTALLY. JOINTS COVERED
WITH JOINT COMPOUND AND PAPER TAPE. JOINT COMPOUND AND TAPE CAN BE OMITTED WHEN SQUARE EDGE BOARDS ARE USED. AS AN
ALTERNATE, NOMINAL 3/32 IN. THICK GYPSUM VENEER PLASTER MAY BE APPLIED TO THE ENTIRE SURFACE OF CLASSIFIED VENEER
BASEBOARD WITH THE JOINTS REINFORCED WITH PAPER TAPE. NAILHEADS EXPOSED OR COVERED WITH JOINT COMPOUND.
BATTS AND BLANKETS
3 IN. THICK MINERAL WOOL BATTS, FRICTION-FITTED TO FILL INTERIOR OF WALL, OR 3 IN. THICK GLASS FIBER BATTS BEARING THE UL
CLASSIFICATION MARKING AS TO SURFACE BURNING AND/OR FIRE RESISTANCE, FRICTION-FITTED TO FILL THE INTERIOR OF THE WALL, OR
GLASS FIBER INSULATION, MIN. DENSITY OF 0.80 PCF, WITH A FLAME SPREAD OF 25 OR LESS AND A SMOKE DEVELOPED OF 50 OR LESS,
FRICTION-FITTED TO COMPLETELY FILL THE STUD CAVITIES.
NON-BEARING WALL PARTITION INTERSECTION
TWO NOMINAL 2 BY 4 IN. STUDS OR NOMINAL 2 BY 6 IN. STUDS NAILED TOGETHER WITH TWO 3 IN. LONG 10D NAILS SPACED A MAX. 16 IN. O.C.
VERTICALLY. INTERSECTION BETWEEN PARTITION WOOD STUDS TO BE FLUSH WITH THE 2 BY 4 IN. STUDS. THE WALL PARTITION WOOD STUDS
ARE TO BE FRAMED BY WITH A SECOND 2 BY 4 IN. WOOD STUD FASTENED WITH 3 IN. LONG 10D NAILS SPACED AT MAX. 16 IN. O.C. VERTICALLY.
MAXIMUM ONE NON-BEARING WALL PARTITION INTERSECTION PER STUD CAVITY. NON-BEARING WALL PARTITION STUD DEPTH SHALL BE AT A
MINIMUM EQUAL TO THE DEPTH OF THE BEARING WALL.
PROPRIETARY GYPSUM BOARD
AMERICAN GYPSUM COMPANY - TYPES AGX-1, M-GLASS, LIGHTROC, AG-C
CERTAINTEED GYPSUM INC. - TYPES C, X, OR X-1
CGC INC - TYPES AR, C, IPC-AR, WRC, WRX
NATIONAL GYPSUM COMPANY - TYPE FSW
UNITED STATES GYPSUM CO. - TYPES AR, SCX, SGX, C, WRX, WRC
USG BORAL DRYWALL SFZ LLC - TYPES C, SCX, SGX
WALL MODIFICATIONS PER ANSI/UL 263:
GENERAL: INSTALL WATER-RESISTANT GYPSUM BOARD AROUND PLUMBING FIXTURES. INSTALL UL LISTED SEALANT BETWEEN GYPSUM AND
FLOOR. INSTALL R-15 UNFACED GLASS FIBER INSULATION FRICTION FIT IN STUD CAVITIES.
TYPE L2: USE 2X6 WOOD STUDS AT 16" O.C.
ASSEMBLY:
FLOOR 3/8"
THICKNESS
BASE AS SCHEDULED
2X SILL PLATE, USE
TREATED LUMBER AT ALL
FIRST FLOOR WALLS
5/8" TYPE X GYP. BD. EACH
SIDE, SMOOTH FINISH
2X4 OR 2X6 STUDS AT 16" O.C.
5/8" 3 1/2" 5/8"
4 3/4"
ALTERNATE 5/8" TYPE X WATER-
RESISTANT GYP. BD. ON
BATHROOM/PLUMBING FIXTURE SIDE
SOUND BATT INSULATION
VERTICAL ASSEMBLY:
2X4
2X6
16" O.C.
1. EACH PROPRIETARY SYSTEM LISTS SPECIFIC PRODUCTS THAT ARE ACCEPTABLE FOR USE IN THE SPECIFIC SYSTEM IN WHICH THEY ARE
LISTED. CONTACT THE MANUFACTURER FOR MORE DETAILED INFORMATION ON PROPRIETARY PRODUCTS.
2. UNLESS OTHERWISE SPECIFIED THE FACE LAYERS OF ALL SYSTEMS, EXCEPT THOSE PRE-DECORATED OR METAL COVERED SURFACES, SHALL
HAVE JOINTS TAPED (MIN. LEVEL 1).
3. METAL STUDS AND RUNNERS ARE NOMINAL 25 GAUGE UNLESS OTHERWISE SPECIFIED.
4. SPECIFIED FLOORS -CEILING AND ROOF -CEILING FRAMING SIZES OR TRUSS DIMENSIONS ARE MINIMUMS. GREATER JOIST OR TRUSS SIZES
(DEPTHS) SHALL BE PERMITTED TO BE USED IN METAL -OR WOOD-FRAMED SYSTEMS. INDICATED JOIST AND TRUSS SPACINGS ARE
MAXIMUMS.
5. SYSTEMS TESTED WITH METAL FURRING CHANNELS ATTACHED DIRECTLY TO THE BOTTOM CHORDS OF STEEL BEAMS, BAR JOISTS, OR WOOD
TRUSSES OR FRAMING SHALL BE PERMITTED TO BE SUSPENDED. GENERALLY, FURRING CHANNELS ARE ATTACHED TO 1-1/2 INCH COLD
ROLLED CARRYING CHANNELS 48" O.C. SUSPENDED FROM JOISTS BY 8 GAGE WIRE HANGERS SPACED NOT GREATER THAN 48" O.C.
6. ADDITIONAL LAYERS OF TYPE 'X' OR REGULAR GYPSUM BOARD SHALL BE PERMITTED TO BE ADDED TO ANY SYSTEM.
7. SCREWS MEETING ASTM C 1002 SHALL BE PERMITTED TO BE SUBSTITUTED FOR THE PRESCRIBED NAILS, ONE FOR ONE, WHEN THE LENGTH
AND HEAD DIAMETER OF THE SCREWS EQUAL OR EXCEED THOSE OF THE NAILS SPECIFIED IN THE TEST SYSTEM AND THE SCREW SPACING
DOES NOT EXCEED THE SPACING SPECIFIED FOR THE NAILS IN THE TESTED SYSTEM.
8. GREATER STUD SIZES (DEPTHS) SHALL BE PERMITTED TO BE USED IN METAL -OR WOOD-STUD SYSTEMS. METAL STUDS OF HEAVIER GAGE
THAN THOSE TESTED SHALL BE PERMITTED. THE ASSIGNED RATING OF ANY LOAD-BEARING SYSTEM SHALL ALSO APPLY TO THE SAME
SYSTEM WHEN USED AS A NON LOAD-BEARING SYSTEM. INDICATED STUD SPACINGS ARE MAXIMUMS.
9. ALL FIRE-RESISTIVE SYSTEMS SHALL BE FIRE BLOCKED IN ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS.
10. ALL PENETRATIONS IN A FIRE-RATED SYSTEM SHALL BE FILLED WITH FIRESTOPPING MATERIAL AS REQUIRED BY LOCAL CODE.
11. WHEN NOT SPECIFIED AS A COMPONENT OF A FIRE TESTED WALL OR PARTITION SYSTEM, MINERAL FIBER, GLASS FIBER, OR CELLULOSE FIBER
INSULATION OF A THICKNESS NOT EXCEEDING THAT OF THE STUD DEPTH SHALL BE PERMITTED TO BE ADDED WITHIN THE STUD CAVITY.
12. PENETRATIONS (BOTH THROUGH PENETRATIONS AND MEMBRANE PENETRATIONS) OF WALL OR FLOOR/CEILING ASSEMBLIES SHALL BE FIRE-
RATED WITH AN APPROVED ASSEMBLY OR FIRESTOP SYSTEM. EXCEPTIONS INCLUDE: A MEMBRANE PENETRATIONS OF ELECTRICAL BOXES OF
ANY MATERIAL WHICH HAVE BEEN TESTED FOR USE IN A FIRE-RATED ASSEMBLY OR NON-LISTED METAL BOXES, PROVIDED BOXES ON
OPPOSITE SIDES OF FIRE-RATED WALL ARE SEPARATED BY A HORIZONTAL DISTANCE OF 24-INCHES OR SEPARATED BY SOLID FIRE-BLOCKING
PER OR SEPARATED ACCORDING TO THE LISTING OF THE BOX.
13. THE "APPROVED PENETRATION FIRESTOP SYSTEM" MUST BE INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E814 OR UL1479 WITH A
MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER AND SHALL HAVE A FIRE-RATING NOT LESS THAN THE REQUIRED FIRE-
RESISTANCE RATING OF THE WALL PENETRATION.
14. ALTHOUGH THERE ARE MANY FIRESTOP SOLUTIONS, INCLUDING FIRE CAULK, INTUMESCENT SEALS, OR COLLAR SYSTEMS, THE SPECIFIC
SYSTEM USED IN THIS PROJECT SHALL HAVE A UL NUMBER THAT GIVES THE INSTALLATION INFORMATION AND THE RATINGS AS TESTED BY
UL. A COPY OF THE UL REPORT SHALL BE PROVIDED TO THE LOCAL FIRE MARSHALL FOR APPROVAL PRIOR TO ITS INSTALLATION.
15. THE ADDITION OF WOOD STRUCTURAL PANELS IN FIRE-RATED GYPSUM BOARD ASSEMBLIES IS PERMITTED AS DESCRIBED IN THIS SECTION.
WOOD STRUCTURAL PANELS THAT ARE 4 FT WIDE, MINIMUM 7/16" THICK ORIENTED STRAND BOARD (OSB) OR 15/32" THICK STRUCTURAL
SHEATHING (PLYWOOD) COMPLYING WITH DOC PS1 OR PS2, OR APA STANDARD PRP-108, MANUFACTURED WITH EXTERIOR GLUE, MAY BE
APPLIED HORIZONTALLY OR VERTICALLY, TO THE FRAMING MEMBERS. VERTICAL JOINTS SHOULD BE CENTERED ON STUDS, AND STAGGERED
ON STUD SPACE FROM THE GYPSUM BOARD JOINTS. THE WOOD STRUCTURAL PANELS ARE PERMITTED TO BE APPLIED EITHER AS (1) A BASE
LAYER (DIRECTLY TO THE WALL FRAMING AND UNDER THE GYPSUM BOARD), (2) IN BETWEEN GYPSUM BOARD LAYERS, OR (3) OVER THE TOP
OF THE COMPLETED GYPSUM BOARD LAYERS. WHEN WOOD STRUCTURAL PANELS ARE USED ON TOP OF THE GYPSUM BOARD LAYERS OF
EXTERIOR WALL ASSEMBLIES, THE WOOD STRUCTURAL PANEL SHOULD BE PROTECTED FROM THE EXTERIOR ENVIRONMENT EITHER AS
SPECIFIED IN THE DESIGN OR AS SPECIFIED UNDER ITEM 10, EXTERIOR WALLS, BELOW. WHEN WOOD STRUCTURAL PANELS ARE ADDED TO THE
WALL ASSEMBLY, THE LENGTH OF THE FASTENER USED FOR THE OUTERMOST LAYER (EITHER GYPSUM BOARD OR WOOD STRUCTURAL
PANEL) SHOULD BE SIZED APPROPRIATELY TO ACCOMMODATE THE ADDITIONAL THICKNESS OF THE WALL PANEL.
FIRE-RESISTANCE RATED SYSTEM NOTES
PROJECT USE: 2X4 & 2X6 INTERIOR - BEARING / SHEAR WALLS
FLOORING
BASE AS SCHEDULED
2X SILL PLATE, USE TREATED
LUMBER AT ALL FIRST FLOOR WALLS
5/8" TYPE X GYP. BD. EACH
SIDE, SMOOTH FINISH
2X4 OR 2X6 STUDS AT 16" O.C.
5/8" 3 1/2"
1/2"
5/8"
5 1/4"
1/2" OSB -SEE STRUCTURAL
SPECIFICATIONS
R-11 KRAFT FACE BATT INSULATION
VERTICAL ASSEMBLY:2X DOUBLE TOP PLATE
S1
S2
2X4
2X6
ALTERNATE 5/8" TYPE X WATER-
RESISTANT GYP. BD. ON
BATHROOM/PLUMBING FIXTURE SIDE
DESIGN NO. U305 GENERIC 1 HOUR FIRE 56 STC - SOUND
16" O.C.
THICKNESS:5 1/4"
GYPSUM WALLBOARD, WOOD STUDS (LOAD BEARING)
NOMINAL 2 BY 4 IN. FRAMING SPACED 16IN. O.C. MAX., EFFECTIVELY FIRESTOPPED. 5/8 IN. THICK PAPER OR VINYL SURFACED, WITH BEVELED,
SQUARE, OR TAPERED EDGES, APPLIED EITHER HORIZONTALLY OR VERTICALLY TO BOTH SIDES OF THE WALL. GYPSUM PANELS FASTENED TO
FRAMING WITH 1-1/4 IN. LONG TYPE W COURSE THREAD GYPSUM PANEL STEEL SCREWS SPACED AT MAX. 8 IN. O.C. WITH LAST SCREW 1 IN. FROM
EDGE OF BOARD. WHEN USED IN WIDTHS OF OTHER THAN 48 IN., GYPSUM PANELS ARE TO BE INSTALLED HORIZONTALLY. JOINTS COVERED
WITH JOINT COMPOUND AND PAPER TAPE. JOINT COMPOUND AND TAPE CAN BE OMITTED WHEN SQUARE EDGE BOARDS ARE USED. AS AN
ALTERNATE, NOMINAL 3/32 IN. THICK GYPSUM VENEER PLASTER MAY BE APPLIED TO THE ENTIRE SURFACE OF CLASSIFIED VENEER
BASEBOARD WITH THE JOINTS REINFORCED WITH PAPER TAPE. NAILHEADS EXPOSED OR COVERED WITH JOINT COMPOUND.
BATTS AND BLANKETS
3 IN. THICK MINERAL WOOL BATTS, FRICTION-FITTED TO FILL INTERIOR OF WALL, OR 3 IN. THICK GLASS FIBER BATTS BEARING THE UL
CLASSIFICATION MARKING AS TO SURFACE BURNING AND/OR FIRE RESISTANCE, FRICTION-FITTED TO FILL THE INTERIOR OF THE WALL, OR
GLASS FIBER INSULATION, MIN. DENSITY OF 0.80 PCF, WITH A FLAME SPREAD OF 25 OR LESS AND A SMOKE DEVELOPED OF 50 OR LESS,
FRICTION-FITTED TO COMPLETELY FILL THE STUD CAVITIES.
NON-BEARING WALL PARTITION INTERSECTION
TWO NOMINAL 2 BY 4 IN. STUDS OR NOMINAL 2 BY 6 IN. STUDS NAILED TOGETHER WITH TWO 3 IN. LONG 10D NAILS SPACED A MAX. 16 IN. O.C.
VERTICALLY. INTERSECTION BETWEEN PARTITION WOOD STUDS TO BE FLUSH WITH THE 2 BY 4 IN. STUDS. THE WALL PARTITION WOOD STUDS
ARE TO BE FRAMED BY WITH A SECOND 2 BY 4 IN. WOOD STUD FASTENED WITH 3 IN. LONG 10D NAILS SPACED AT MAX. 16 IN. O.C. VERTICALLY.
MAXIMUM ONE NON-BEARING WALL PARTITION INTERSECTION PER STUD CAVITY. NON-BEARING WALL PARTITION STUD DEPTH SHALL BE AT A
MINIMUM EQUAL TO THE DEPTH OF THE BEARING WALL.
PROPRIETARY GYPSUM BOARD
AMERICAN GYPSUM COMPANY - TYPES AGX-1, M-GLASS, LIGHTROC, AG-C
CERTAINTEED GYPSUM INC. - TYPES C, X, OR X-1
CGC INC - TYPES AR, C, IPC-AR, WRC, WRX
NATIONAL GYPSUM COMPANY - TYPE FSW
UNITED STATES GYPSUM CO. - TYPES AR, SCX, SGX, C, WRX, WRC
USG BORAL DRYWALL SFZ LLC - TYPES C, SCX, SGX
WALL MODIFICATIONS PER ANSI/UL 263:
GENERAL: INSTALL WATER-RESISTANT GYPSUM BOARD AROUND PLUMBING FIXTURES. INSTALL UL LISTED SEALANT BETWEEN GYPSUM AND
FLOOR. INSTALL R-15 UNFACED GLASS FIBER INSULATION FRICTION FIT IN STUD CAVITIES.
1/2" OSB FOR SHEAR WALL LOCATIONS -SEE STRUCTURAL
TYPE S2: USE 2X6 WOOD STUDS AT 16" O.C.
ASSEMBLY:
16" O.C.
GA FILE NO. WP 4230 GENERIC 2 HOUR FIRE NOT LISTED - SOUND
16" O.C.
THICKNESS: 8"
APPROX. WEIGHT: 13 PSF
FIRE TEST: ITS J20-06170.3, 12-00
PROJECT USE: STAIR ENCLOSURE - 2X6 WALLS AND INTERIOR PARTITION, WOOD FRAMED
GYPSUM BOARD:BASE - LAYER 5/8" TYPE X GYP. WALLBOARD APPLIED AT
RIGHT ANGLES TO EACH SIDE OF 2X6 WOOD STUDS 24" O.C.
WITH 2-1/4" TYPE S OR W DRYWALL SCREWS 24" O.C.
FACE - LAYER 5/8" TYPE X GYPSUM WALLBOARD APPLIED AT
RIGHT ANGLES TO EACH SIDE WITH 2-1/4" TYPE S DRYWALL
SCREWS 8" O.C. 5-1/2" MINERAL FINGER INSULATION,
NOMINAL 3 PCF, FRICTION FIT IN STUD SPACE.
WOOD STUDS:2X6 STUD SPACED 16" O.C.
* TESTED AT 5506 LBS PER STUD OR 100 PERCENT OF DESIGN LOAD. (LOAD-BEARING)
ASSEMBLY:
T1
T2
STANDARD
ADD 1 LAYER OF SHEAR WALL
SHEATHING -SEE STRUCTURAL
DESIGN NO. U348 PROPRIETARY 1 HOUR FIRE SOUND - N/A
THICKNESS:4 - 6-1/2"
FIRE TEST:ANSI/UL 263
PROJECT USE: EXTERIOR 2X4 & 2X6 LOAD BEARING & NON LOAD BEARING WALLS
INTERIOR
EXTERIOR
GYPSUM BOARD:GYPSUM BOARD - 5/8" UL CLASSIFIED GYP. BD. (4' WIDE),
APPLIED VERTICALLY AND NAILED TO STUDS AN BEARING
PLATES 7" O.C. WITH 6d CEMENT COATED NAILS, 1-7/8"
LONG, 0.0915" SHANK DIAM. AND 1/4" DIAM. HEAD. - TAPE
AND JOINT COMPOUND ALL SEAMS & NAIL HEADS
WOOD STUDS:2X4 STUDS SPACED 16" O.C. WITH TWO 2X4 TOP AND ONE
2X4 BOTTOM PLATES. AS AN OPTION, 2X6 STUDS SPACED
16" O.C. WITH TWO 2X6 TOP AND ONE 2X6 BOTTOM
PLATES MAY BE USED IN LIEU OF 2X4 STUDS
INSULATION:BATTS AND BLANKETS - FACED OR UNFACED GLASS
FIBER BATTS, 3-1/2" THICK HAVING A MIN. DENSIY OF 0.9
PCF (MIN R-13 THERMAL INSULATION RATING), PRESSURE
FIT IN THE WALL CAVITY BETWEEN STUD, PLATES AND
CROSS BRACING. IF 2X6 STUD ARE USED MIN, 5-1/2" OF
FACED OR UNFACED GLASS FIBER IS USED. *ALTERNATE
INSULATION METHODS AVAILABLE
EXTERIOR SHEATHING: LOUISIANA-PACIFIC CORP TYPE LP FLAMEBLOCK 1-SIDE
OR TYPE BLAZEGUARD 1-SIDE. SHEATHING PLACED WITH
LAMINATE FACE AGAINST, AND NAILED TO, THE WOOD
FRAMING WITH 6d NAILS, SPACED 6" O.C. ON THE
PERIMETER AND 12" O.C. IN THE FIELD.
ASSEMBLY:
2x4 or 2x6
EX1
EX2
2X4
2X6
GA FILE NO. WP 8136 PROPRIETARY 1 HOUR FIRE SOUND - N/A
THICKNESS: 4 - 3/4"
APPROX. WEIGHT: 7 PSF
FIRE TEST:UL R1319, 08CA05754,
5-14-09; 08NK23546,
6-2-08; 11NK08543,
6-17-11; UL DESIGN U305 & U327
PROJECT USE: EXTERIOR 2X4 & 2X6 LOAD BEARING & NON LOAD BEARING WALLS AT BALCONY
EXTERIOR - OR - INTERIOR
EXTERIOR
GYPSUM WALLBOARD, GLASS MAT GYPSUM SUBSTRATE, WOOD STUDS
EXTERIOR SIDE: ONE LAYER 5/8" PROPRIETARY TYPE X GYPSUM SHEATHING OR GLASS
MAT GYPSUM SUBSTRATE (SHEATHING) APPLIED PARALLEL OR AT RIGHT ANGLES TO
2X4 WOOD STUDS 16" O.C. WITH 1-5/8" TYPE S DRYWALL SCREWS 12" O.C. TO STUDS
WHEN APPLIED PARALLEL TO FRAMING OR 8" O.C. WHEN APPLIED AT RIGHT ANGLES TO
FRAMING.
*WHERE WALL IS EXTERIOR ON BOTH SIDES PROVIDE EXTERIOR RATED SHEATHING ON
BOTH SIDES.
INTERIOR SIDE: ONE LAYER 5/8" PROPRIETARY TYPE X GYPSUM WALLBOARD OR
GYPSUM VENEER BASE APPLIED PARALLEL OR AT RIGHT ANGLES TO 2X4 WOOD STUDS
6" O.C. WITH 1-5/8" TYPE S DRYWALL SCREWS 12" O.C. TO STUDS WHEN APPLIED
PARALLEL TO FRAMING OR 8" O.C. WHEN APPLIED AT RIGHT ANGLES TO FRAMING.
VERTICAL JOINTS CENTERED OVER STUDS AND STAGGERED ONE STUD CAVITY ON
OPPOSITE SIDES. HORIZONTAL JOINTS ON OPPOSITE SIDES NEED NOT BE STAGGERED.
(LOAD BEARING)
PROPRIETARY GYPSUM PANEL PRODUCT
UNITED STATES GYPSUM COMPANY... 5/8" SECUROCK GLASS -MAT SHEATHING PANELS,
5/8" SHEETROCK BRAND ULTRA LIGHT PANELS FIRECODE X
ASSEMBLY:
2x4 or 2x6
EX3
EX4
2X4
2X6
DATE
155 EAST MARKET STREETSECOND FLOOR, SUITE 200
INDIANAPOLIS, INDIANA 46204
T 317.721.2724
ROTTMANNCOLLIER.COM
SCOPE DOCUMENT
THESE DOCUMENTS INDICATE THE GENERAL
SCOPE OF THE PROJECT IN TERMS OFARCHITECTURAL DESIGN CONCEPT, DIMENSIONS
OF THE BUILDING, MAJOR ARCHITECTURALELEMENTS AND TYPE OF STRUCTURAL,
MECHANICAL AND ELECTRICAL SYSTEMS. THE
DRAWINGS DO NOT CECESSARILY INDICATE OR
DESCRIBE ALL WORK REQUIRED FOR FULLPERFORMANCE AND COMPLETION OF THE
REQUIREMENTS OF THE CONTRACT. ON THE
BASIS OF THE GENERAL SCOPE INDIACATED OR
DESCRIBED, TRADE CONTRACTOR SHALL
FURNISH ALL ITEMS REQUIRED FOR PROPER
EXECUTION AND COMPLETION OF THE WORK
SHEET
PROJECT NO.
REVISIONSMÉLANGE FLATSA NEW MULTIFAMILY RESIDENTIALBLOCK DEVELOPMENTFIREHOUSE DEVELOPMENTCARMEL, INDIANA 4603203-05-2021 OWNER REVIEW SET
08-16-2021 CONSTRUCTION SET
11-01-2021 ADDENDUM 1
T1-5
RATED WALL TYPES
03-05-2021
19112
01/31/22