* DIMENSION SUBJECT TO CHANGE22" *6"1
2
"
28
"1 2" *1 2" *
22
"
CEILING EXHAUST FAN DETAIL
NOT TO SCALE
DETAIL 'A'
FIRE DAMPER AT FIRE RATED WALL DETAIL
NOT TO SCALE
DETAIL 'A'
FIRE DAMPER AT FIRE RATED WALL DETAIL
NOT TO SCALE
GRILLE
EXHAUST
RECTANGULAR OR
BACKDRAFT
DAMPER
CEILING
MOUNT FAN TO FINISHED
CEILING FRAMING.
PROVIDE
NEOPRENE VIBRATION
ISOLATORS.
ROUND DUCTWORK
AS SPECIFIED ON
PLANS
INSTALLATION TO BE
IN COMPLIANCE WITH
MANUFACTURERS
INSTRUCTIONS
PROVIDE CLEARANCE
ON TOP & SIDES FOR
EXPANSION
FIRE RATED WALL
18 GAUGE SLEEVE
FIRE RATED WALL
SEE DETAIL 'A' WHERE
WALL IS CONSTRUCTED
OF WOOD OR STEEL
JOISTS
VERTICAL CURTAIN TYPE STATIC
FIRE DAMPER WITH UL RATING FOR
1-1/2 HR UNLESS OTHERWISE NOTED.
(SIMILAR TO RUSKIN IBD2 STYLE "A")
FASTEN DUCT TO SLEEVE
WITH 'S' SLIP ON TOP &
BOTTOM & DRIVE SLIP ON
SIDES
RETAINING ANGLES SHALL BE 2"x2"x1/8"
& SHALL BE SECURED TO 18 GA. SLEEVE
WITH 1/2" WELDS AT 6" O.C. DO NOT
SECURE ANGLES TO WALL. PROVIDE ANGLES
ON ALL FOUR SIDES OF SLEEVE &
BOTH SIDES OF WALL.
WOOD OR STEEL JOISTS
CARRY FIRE
RESISTANT
LINING ON ALL SIDES
OF OPENING
RETAINING ANGLE
18 GAUGE
SLEEVE
GRILLE
FIRE DAMPER FRAME
FUSIBLE LINK (165°F)
STEEL BLADES WITH
INTERLOCKING JOINTS
EXPAND DUCT SO THAT
FIRE DAMPER DOES NOT
REDUCE AREA OF DUCT,
EXPANSION IN WIDTH
IS ACCEPTABLE
PROVIDE SEALANT TO JOINT
ALL AROUND
DUCTWORK-SEE
PROJECT
DRAWINGS FOR SIZE
AND CONTINUATION
GRILLE
INSTALLATION TO BE
IN COMPLIANCE WITH
MANUFACTURERS
INSTRUCTIONS
PROVIDE
CLEARANCE
ON TOP & SIDES FOR
EXPANSION
FIRE RATED WALL
PROVIDE SEALANT TO JOINT
ALL AROUND ON BOTH
SIDES OF WALL
18 GAUGE COLLAR
FIRE RATED WALL
SEE DETAIL 'A' & 'B'
WHERE WALL IS CONSTRUCTED
OF WOOD OR STEEL JOISTS
VERTICAL CURTAIN TYPE
STATIC FIRE DAMPER WITH
UL RATING FOR 1-1/2 HR
UNLESS OTHERWISE NOTED.
(SIMILAR TO RUSKIN IBD2
STYLE "B")
DUCTWORK-SEE PROJECT
DRAWINGS FOR SIZE
AND CONTINUATION
DOUBLE WALL, HINGED, GASKETED
AND INSULATED ACCESS PANEL,
(LABEL "FIRE DAMPER ACCESS DOOR")
FASTEN DUCT TO SLEEVE
WITH 'S' SLIP ON TOP &
BOTTOM & DRIVE SLIP ON
SIDES
RETAINING ANGLES SHALL BE 2"x2"x1/8" & SHALL BE
SECURED TO 18 GA. COLLAR WITH 1/2" WELDS AT 6" O.C.
DO NOT SECURE ANGLES TO WALL OR FLOOR.
PROVIDE ANGLES ON ALL FOUR SIDES OF SLEEVE &
BOTH SIDES OF WALL OR FLOOR.
FIRE DAMPER FRAME
RETAINING ANGLE
WOOD OR STEEL
JOISTS
CARRY FIRE
RESISTANT
LINING ON ALL SIDES
OF OPENING
SLEEVE
FUSIBLE LINK (165°F)
STEEL BLADES WITH
INTERLOCKING JOINTS
SOUND LINING
WHERE INDICATED
METAL NOSING
OVER INTERNAL
INSULATION
CONNECTION
REFRIGERANT GAUGE
CONTROL WIRING
REFRIGERANT LIQUID LINE
WITH INSULATION
REFRIGERANT SUCTION LINE
SERVICE VALVES
CONDENSING UNIT
FAN GUARD
AIR-COOLED CONDENSING UNIT DETAIL
NOT TO SCALE TYPICAL WALL PENETRATION DETAIL
NOT TO SCALE
PIPE SLEEVE OR SHEET
METAL SLEEVE
3/4" SPACE PACKED
WITH FIBROUS
MATERIAL ALL AROUND
BUILDING WALL
OR
FLOOR
PIPE
NON-HARDENING
RESILIENT SEALANT
BOTH SIDES
DUCT
IF OPENING LIMITED TO
DESIRED 3/4" SPACE
PACK WITH FIBROUS
MATERIAL AND SEAL
BOTH SIDES WITH
RESILIENT
NON-HARDENING SEALER.
IF OPENING STRUCTURE IS
IRREGULAR AND GREATER
THAN 1", WRAP DUCT WITH
1" THICK FIBROUS MATERIAL
AND FILL REMAINING
OPENING WITH GROUT.
DUCT LINING
AS REQUIRED
FIRE DAMPER ACCESS PANEL IN CEILING
REFRIGERANT PIPING ROOF HOOD & CURB DETAIL
SCALE: NONE
(NOTE: COORDINATE CURBS & FLASHING WITH SPECIFIED ROOF CONSTRUCTION)
ELECTRIC UNIT HEATER DETAIL
NOT TO SCALE
POWER SUPPLY
JUNCTION BOX
WALL
SWITCH
DISCONNECT
NON-FUSED
EXPANSION ANCHORS
MINIMUM7'-0" A.F.F.ELECTRIC
SLAB
J
MOUNTING RODS
(4) THREADED
SUPPLY AIR
UNIT HEATER
PACK WITH FIBERGLASS INSULATION
CEILING MOUNTED SUPPLY REGISTER INSTALLATION DETAIL
NOT TO SCALE
INSULATED FLEX DUCT
CEILING
SUPPLY AIR REGISTER
WITH OPPOSED
BLADE
VOLUME DAMPER
SUPPLY DUCT
RADIATION DAMPER
AT RATED CEILINGS
MOORE ENGINEERING
SERVICES, INC.
6340 LaPas Trail
Indianapolis, IN 46268
Phone (317) 291-1052
FAX (317) 298-2729R
I
G EEIS
PE60860351
No.REENIGNELANOISSEFORPDOUGLAS.R MOO
RET R
NNDIA A
STATE OF DEDATE
SCOPE DOCUMENT
THESE DOCUMENTS INDICATE THE GENERAL
SCOPE OF THE PROJECT IN TERMS OF
ARCHITECTURAL DESIGN CONCEPT, DIMENSIONS
OF THE BUILDING, MAJOR ARCHITECTURAL
ELEMENTS AND TYPE OF STRUCTURAL,
MECHANICAL AND ELECTRICAL SYSTEMS. THE
DRAWINGS DO NOT CECESSARILY INDICATE OR
DESCRIBE ALL WORK REQUIRED FOR FULLPERFORMANCE AND COMPLETION OF THE
REQUIREMENTS OF THE CONTRACT. ON THEBASIS OF THE GENERAL SCOPE INDIACATED OR
DESCRIBED, TRADE CONTRACTOR SHALLFURNISH ALL ITEMS REQUIRED FOR PROPER
EXECUTION AND COMPLETION OF THE WORK
SHEET
ADDENDUM 1
REVISIONSMÉLANGE FLATSA NEW MULTIFAMILY RESIDENTIALBLOCK DEVELOPMENTFIREHOUSE DEVELOPMENTCARMEL, INDIANA 4603211-01-2021
M500
MECHANICAL DETAILS
AC RACK DETAIL
NOT TO SCALE
01/31/22