HomeMy WebLinkAboutMelange CDRELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 1/2
CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on: December 17, 2021
Project number Release date
423795 10/26/21
Construction type Occupancy classification
Scope of release
V-B, SPK R-3, U
Type of release
Project name
Street address
City County
SPK
Partial
Melange - Brownstone Buildings
Veteran's Way &
Monon Green Blvd
CARMEL HAMILTON
To: Owner / Architect / Engineer
Gardner Fire Protection, Inc.
John Sayer 89729
Veteran Way & Monon
Carmel IN 46032
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
10FA010
10F08331
10FA0512
10FA064621
10FA066
10FA0662
10FA0663
10F0629
10F252
14B0700
AREL
This system has been reviewed in accordance with NFPA 13R, 2010 edition (675 IAC 28-1-6).
Sprinklers utilized in light hazard occupancies shall comply with Section 8.3.3.1, NFPA 13 (675 IAC
28-1-5).
The fire department connection shall be a listed or approved device as specified in Section 5.1.2,
NFPA 13R, 2010 edition (675 IAC 28-1-6).
Sidewall sprinklers shall be positioned so that the deflectors are within 4 to 6 inches from the ceiling
in accordance with Section 6.4.6.2.1, NFPA 13R, 2010 edition (675 IAC 28-1-6).
Concealed spaces are exempt from sprinkler protection in accordance with Section 6.6, NFPA 13R,
2010 edition (675 IAC 28-1-6).
Bathrooms shall be sprinklered or shall comply with Section 6.6.2, NFPA 13R, 2010 edition (675
IAC 28-1-6).
Closets shall be sprinklered or shall comply with Section 6.6.3, NFPA 13R, 2010 edition (675 IAC
28-1-6).
A supply of spare sprinkler heads shall be maintained on the premises in accordance with Section
6.2.9, NFPA 13 (675 IAC 28-1-5).
Water-based fire-protection systems shall be inspected, tested, and maintained per NFPA 25, 2011
edition (675 IAC 28-1-12).
Fire resistive construction shall be maintained in accordance with Chapter 7, IBC (675 IAC 13-2.6).
Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from
required compliance with all applicable rules of the commission, even if noncompliant conditions
appear in the plans and specifications that have been filed with the division. The owner is
responsible for correcting any and all areas of noncompliance even if they are discovered
Indiana Department of Homeland Security
DIVISION OF FIRE & BUILDING SAFETY
PLAN REVIEW DIVISION
402 W. Washington St., Room E245
Indianapolis, IN 46204
Fax & e-mail:
SUPPORT HOOSIER SAFETY
Available At Your Local Licence Branch
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
3178948600, JaosnGardn1@aol.com
01/31/22
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 2/2
subsequent to the issuing of this design release.
This order is effective upon service. If you would like to request informal review of this order, please complete the informal review form located at
https://www.in.gov/dhs/4149.htm. Following receipt of this form, the Department may modify or reverse the order, however, a request for an informal
review does not extend the deadline for filing a petition for review with the Fire Prevention and Building Safety Commission (Commission).
Additionally, if you have any questions regarding this order, you may contact that Department at (317) 232-2222.
If you desire a formal administrative review of this order by the Commission, you must comply with the requirements of Indiana Code § 4-21.5-3-7
and file a written petition for review within 15 days of the date this order was served, however, this period is extended to 18 days if service is made by
mail. Your petition for review must state facts demonstrating that you are: (1) a person to whom the order is specifically directed; (2) aggrieved or
adversely affected by the order; or (3) entitled to review under any law. You may submit your petition by the following methods:
U.S. MAIL OR PERSONAL SERVICE ONLINE
Fire Prevention and Building Safety Commission By completing the form at
c/o Legal Counsel https://www.in.gov/dhs/4148.htm
302 W. Washington Street, Rm. E208
Indianapolis, IN 46204
For additional information about the administrative review process and applicable templates that may be used for filings, visit the following link
https://www.in.gov/dhs/appeals.htm.
Code review official
Address (name,title of local official,street,city,state and ZIP code
KEVIN HANSON
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
DEPT OF COMMUNITY SERVICE
Fax & e-mail: 3175712499, jblanchard@carmel.in.gov
Indiana State Building Commissionerkhanson@dhs.in.gov
01/31/22