HomeMy WebLinkAboutMélange Flats Elevator #1 aka Northeast SubmittalELEVATOR SUBMITTAL PACKAGE
Date Submitted: DECEMBER 10, 2021
For Project:
MELANGE FLATS
TK Elevator Job Number: 140-1739-01A
Elevator(s): 1 (SIMPLEX)
Located At:
920 VETERANS WAY
CARMEL, IN 46032
Company (Mail To):
ONYX AND EAST
1828 N. CENTRAL AVE., STE. 100
INDIANAPOLIS, IN 46202
GC Phone:
Attention:
DAVID BENNETT
REVISE AND RESUBMIT
DRAWINGS FOR APPROVAL
01/31/22
INSTRUCTIONS
Failure to complete the Contractor Verification Sheet and Approve drawings WILL result in delay of fabrication and shipping of equipment.
Q Check ALL hoistway dimensions, elevator travel (floor to floor heights), pit depth, clear over-head, machine room dimensions and entrance wall thickness. Mark-up drawings accordingly, and remit with necessary approval (i.e: approved or approved as noted) to
the Local TK Elevator Office.
Q Complete all information on the Contractor Verification Sheet.
Q Provide a firm on-site date to the Local TK Elevator Representative.
Any previously quoted manufacturing lead-times for material delivery, shall begin the date of receipt by TK Elevator of ALL approvals, confirmations, and a fully executed subcontract agreement. The installation start date cannot be any
earlier than the delivery of the material to the site and the completion of all items shown on the Pre-Installation Checklist sent to you in this submittal package.
INFORMATION
"ALL DEPICTIONS, DIMENSIONS, MEASUREMENTS AND ALL OTHER INFORMATION CONTAINED IN THESE DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY. THE CONSTRUCTION MANAGER AND/OR GENERAL CONTRACTOR BEARS FULL
RESPONSIBILITY TO PROPERLY BUILD THE NECESSARY HOISTWAYS, CONTROL-ROOMS, AND/OR MACHINE-ROOMS TO ACCOMMODATE THE ELEVATOR EQUIPMENT PURCHASED." IN NO EVENT WILL TK ELEVATOR CORPORATION BE LIABLE FOR
ANY INCIDENTAL, CONSEQUENTIAL, OR INDIRECT DAMAGES (INCLUDING BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, DELAY, BUSINESS INTERRUPTION,) ARISING OUT OF THE USE OF THESE DRAWINGS, THE INABILITY TO USE THESE
DRAWINGS (INCLUDING ANY INFORMATION CONTAINED THEREIN), OR ANY TRANSACTIONS RELATED TO THE USE OF THESE DRAWINGS. BECAUSE SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU. IN SUCH STATES, TK ELEVATOR CORPORATION'S LIABILITY IS LIMITED TO THE GREATEST EXTENT PERMITTED BY LAW.
REMITTANCE INFORMATION:
PLEASE REMIT ELECTRONIC COPY OF ALL CONFIRMATIONS AND APPROVALS TO:
TO: RICK WILHITE
EMAIL:
PHONE: 317-595-1125
PACKAGE CONTENT:
Contractor Verification Sheet
Instruction and Information Sheet
Approval/Approved Sheet
Layout Sheet
Entrance Sheet(s)
- The enclosed submittals are in compliance with conditions of TK Elevator's subcontract or supplying and installing materials and or systems for the
project referenced above.
- Enclosed drawings are for approval purposes only and not to be used for construction.
CONTACT INFORMATION:
Sales Representative: RICK WILHITE
Construction Superintendent: BRAD BOLTON
Project Manager:
317-595-1125
317-595-1125
317-595-1125
General Contractor Owner Job-Site Pre-Installation Checklist (See G.C. Site Binder)
TKE-Instruction-Information / [Border] TKE-Instruction-Information
01/31/22
Architect/GC Verification Form
ELEVATOR DESIGNATION
FACTORY JOB NUMBER:REQUIRED POWER CONFIRMATIONREQUIRED ENTRANCE INFORMATION
APPROVED BY:____________________________________________________________ DATE: _______________
FAILURE TO FULLY COMPLETE THIS SHEET MAY RESULT IN DELAY OF SCHEDULE
PLEASE CONFIRM THE FOLLOWING INFORMATION
BUILDING POWER: _________________________________ Q CONFIRMED
STARTING TYPE: _________________________
Q CORRECTED: VOLTS: _______ PHASE: _______ CYCLES: _______
MAIN EGRESS FLOOR (Fire Service):
DESCRIPTION OF SELECTED CAB FEATURES
<VLT> <PH> <CYC>
<MAINEGRESS>
FEATURES FOR YOUR FIXTURES
OILVerificationSheet
<APPROVALSHEETSIGNATURE><APPROVALSHEETDATE> Requested Elevator Material Delivery/Start Date: ____ / ____ / _____
(Delivery of all remaining material, less any early shipment)
EMERGENCY POWER VERIFICATION
MATERIAL RELEASE FORM
<MNT><DAY><YR>
CUSTOMER APPROVAL BOX
CONFIRMED CORRECTED REQUIRED
CLEAR OVERHEAD:
HOISTWAY SIZE:
HAND OF DOOR:
PIT DEPTH:
MACHINE ROOM WIDTH:
NET TRAVEL: Q
REQUIRED CAB INFORMATION
Q
MACHINE ROOM LENGTH:
***NOTE*** IF CORRECTIONS ARE REQUIRED PLEASE NOTE ON CORRESPONDING SUBMITTAL DRAWINGS BELOW
***NOTE*** (GC to provide frame size. Please reference the (x) dimension noted below for wall size)
***NOTE*** Jamb Mounted Controllers Require a Minimum wall thickness of 8 1/2" at the controller landing (Top Floor)
***NOTE*** (Elevator platform will be designed to accomodate 3/8" flooring)
***NOTE*** (Elevator flooring is by others. Not included in material order)
<ALTEGRESS>ALTERNATE FLOOR (Fire Service):
QQ CONFIRMED CORRECTED REQUIRED
QQ CONFIRMED CORRECTED REQUIRED
QQ CONFIRMED CORRECTED REQUIRED
QQ CONFIRMED CORRECTED REQUIRED
QQ CONFIRMED CORRECTED REQUIRED
QQ CONFIRMED CORRECTED REQUIRED
DEC 10 2021 8:07 AM
1
208 VOLTS A.C., 3 PHASE, 60 CYCLES
SOLID STATE STARTING
ENTRANCE WALL DETAIL
MASONRY WALL TYPE FRAME DRYWALL TYPE FRAME
Elevator
Entrance Frame
Elevator
Entrance Frame
Elevator
Entrance Frame"X""X""X"
* X = Wall thickness COMBO DRYWALL & MASONRY
MASONRY TYPE FRAMEŹŹ
ŹŹŹŹŹŹŹCAB TYPE: APPLIED PANEL
REVEALS: F-112 BLACK
CAB CEILING: 6-9 LED FIXTURES IN METAL PAN CEILING
CEILING FINISH: #4 STAINLESS STEEL
CAB DOOR: #4 STAINLESS STEEL
CAR SILLS: ALUMINUM
CAB HANDRAIL(S): (3) 1 1/2" CYLINDRICAL
HANDRAIL(S) FINISH: #4 STAINLESS STEEL
CAB PROTECTION: PAD BUTTONS PROVIDED. (1) PADS
CAB FLOORING:FINISH FLOOR WEIGHT (3/8" MAX. THICKNESS) = 111 LBS.
BY OTHERS
CAB PANEL COLOR: <PLASTICLAMINATED>
THIS ELEVATOR HAS BEEN PROVIDED WITH THE FOLLOWING
BACK UP POWER PROVISIONS:__________________ CONFIRMED
Q CORRECTED: ___________
Line 1: ***Note*** Jamb Mounted controllers have AUX contacts provided by TK Elevator.
For Machine Room applications AUX contacts are to be provided by others.
Q
<QTYELEV>
FLOOR MARKING: WALL TYPE: WALL THICKNESS (X): ENTRANCE DOOR FINISH: ENTRANCE FRAME FINISH:
4 <WALLTYPE><WALLTHK><POWDERCOAT><POWDERCOAT>
3 <WALLTYPE><WALLTHK><POWDERCOAT><POWDERCOAT>
2 <WALLTYPE><WALLTHK><POWDERCOAT><POWDERCOAT>
1 <WALLTYPE><WALLTHK><POWDERCOAT><POWDERCOAT>
10_D_O_C
POSITION INDICATOR ILLUM: BLUE
PUSH BUTTON ILLUMINATION: BLUE
01/31/22
ELEVATION VIEW
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
TK ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF TK ELEVATOR.
FOR: MELANGE FLATS
ADDRESS: 920 VETERANS WAY
CITY: CARMEL, IN 46032 4 OF 7
DATE
C
SHEETJOB NUMBER
12/10/2021
REVDRAWN
RW 140-1739-01ATK Elevator
FRONT
PIT PLAN
POSITION OF SUMP PIT OR DRAIN CANNOT BE RELOCATED
FRONT
HOISTWAY PLAN
SECTION[RH-CO]
7 9/16" 1'-0"3'-7 3/4"6'-11"HOISTWAY DEPTH4 3/4"4 3/4"
8'-8"
HOISTWAY WIDTH
4'-4"4'-4"
7'-10 7/16"
BACK TO BACK RAILS
7'-3"
DISTANCE BETWEEN RAILS
7'-10"
BETWEEN CENTERLINE OF JACKS SRAILSSJACKS5"
PIT LADDER
ŹŹ ŹSUMP PIT SIZE TO BE
DETERMINED BY
GENERAL CONTRACTOR
POWER UNIT INFORMATION
WIDTH DEPTH HEIGHT WEIGHT W/OIL (LBS)
6'-0 1/2" 1'-10 15/16" 3'-9" 2,710
ADA PHONE PROVIDED
OF TARGET HOLES =
TARGET HOLE
GUIDE RAILSTO OF TARGET
EDGE OF PLATFORM
FACE OF RAIL
1 1/2"
1 13/16"
S
S SS 7'-6 5/8"SŹ ŹŹŹ ŹHYDRAULIC ELEVATOR CONTRACT DATA
TYPE: ELEVATOR DESIGNATION:
NOTE A: OIL PIPE LINES AND FITTINGS SHALL BE PROPERLY SUPPORTED TO RELIEVE STRAIN.
NOTE B: ALL REACTIONS INCLUDE ALLOWANCE FOR IMPACT.
NOTE C: TK ELEVATOR TO BE NOTIFIED OF ANY CHANGE TO ELEVATOR
HOISTWAY OR MACHINE ROOM DESIGN.
NOTE D: ELEVATOR DESIGN & FABRICATION BASED ON ESTIMATED CAB WEIGHT SHOWN. LAYOUT APPROVAL WILL BE CONSTRUED AS FINAL CAR WEIGHT, UNLESS OTHERWISE NOTIFIED.
SPEED: CAPACITY:
CAR ENCLOSURE: DOOR HAND:
PLATFORM THICKNESS: FINISHED FLOOR:
CAR WEIGHT:
TELEPHONE:PIT LADDER:
POWER UNIT:POWER SUPPLY:
STARTING:OPERATION:
GLOJ:GLOPU:
OVER TRAVEL: BOTTOM: TOP:
JACK MODEL: PLUNGER WEIGHT:
PLUNGER WALL THK:
BETWEEN PIT FLOOR &
CAR BOLSTER ON
COMPRESSED BUFFER:
PLUNGER O.D:
NET AREA:
BOTTOM CAR RUNBY:
CAR BUFFER STROKE: EST. WORKING PRESS:
(QTY) SPRING(S) #: TOTAL SPRING(S) CAPACITY:
CAR
FRAME
S =
I =
A =A =
I =
S =S =
I =
R =
RAIL FORCES F1 F2 SEISMIC RAIL FORCES ZONE:
CAR STATION FEATURES:
CAR RIDING LANTERN:
PUSH BUTTON MARKINGS:
F1 = F2 =
FORMED
CROSSHEAD
FORMED
BOLSTER
FORMED
STILE
UPPER: LOWER:
UPPER: LOWER:
MDL:
MDL:
JACK REACTION (EA.):CAR BUFFER REACTION:
PLUNGER LENGTH: UPPER: MDL: LOWER:
CYLINDER LENGTH: CYLINDER O.D: WALL THK:
endura 35 A 1
150 FPM UP / 150 FPM DOWN 3,500 LBS
TKAP RIGHT FRONT
3 3/8" BY OTHERS
2,701.00 LBS
BY ELEVATOR COMPANY BY ELEVATOR COMPANY
EM-190, 40 HP 208 V 3 Phase 60 Cycles
SOLID STATE STARTING TAC32
6,201 LBS 7,131 LBS
1'-0"8 1/2"
2.5T III TWIN/TELE 930.00 LBS
15'-8"13'-11 9/16" 13'-9 9/16"
0.375"0.25"0.25"
2.5"3.75"5.0"
13'-9 1/16" 7 1/4"1/4"
23.693 SQ.IN.
6"
2 1/2"331 PSI
(2) 75902 20,446 LBS
3.27
9.82
1.85 7GA x 6" x 2 1/2"
5.67
23.39
2.40 7GA x 8 1/4" x 2 3/4"
1.38
2.17
1.01 10GA
567 LBS 397 LBS N/A N/A
Traditional Fixtures, T2 Buttons, Alarm Button, Telephone, Position
Indicator
1, 2, 3, 4
Strike
3'-3 7/8"
7,797.00 LBS 18,180.00 LBS
F2
F1
OMEGA RAIL
Ź ŹŹ8 1/4" SJACK GUIDE5 7/8"
(TYP)
3'-6" CLR. OPENING
6'-0" ROUGH
OPENING @ TYP. FLR.
2'-8"6 1/4"1 3/4"6'-3"PLATFORM DEPTH5'-5"MIN. CLEAR INSIDE10"10"
2" 2"
7'-0"
PLATFORM WIDTH
6'-8"
MIN. CLEAR INSIDE
SCAR2"12'-11"CLEAR OVERHEAD4'-0"REFUGE SPACE8'-11" TOP OF O.A. CABIN FULL TOP OVER TRAVEL7'-0" CLEAR OPENING HEIGHT9'-5"UNDER CROSSHEAD34'-11"NET TRAVEL7'-11"OVERALL CAB HEIGHT7'-4"CEILING HEIGHT2 1/2"OIL LINE5'-0"PIT DEPTH4'-0" MIN.PIT LADDER4'-7 3/4"
SAFETY BEAM
120 HYDRAULIC FLUID REQUIRED IN SYSTEM = GALLONS
HEAT PRODUCED BY ELEVATOR EQUIPMENT IN HOISTWAY = BTU/HR19737
Ɣ GENERAL CONTRACTOR MUST FORWARD POWER REQUIREMENTS TO THE ELECTRICAL CONTRACTOR.
NOTE: A FOURTH WIRE OF SAME SIZE AS THREE PHASE WIRES IS REQUIRED FOR GROUNDING PURPOSES TO MINIMIZE ELECTRICAL NOISE
INTERFERENCE. THE GROUNDING WIRE MUST BE CONNECTED TO THE BUILDING ELECTRICAL SYSTEM GROUND.
Ɣ A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN LINE PER POWER SUPPLY TO THE ELEVATOR PRIOR TO THE APPLICATION OF WATER
IN THE ELEVATOR HOISTWAY WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR THIS MEANS SHALL NOT BE SELF RESETTING.
Ɣ DEDICATED 120 VOLT, 15 AMP SERVICE, ALONG WITH TELEPHONE CIRCUIT WHEN REQUIRED TO TERMINALS OF EACH REQUIRED
CONTROLLER (AS LOCATED ON ENTRANCE PAGE) FOR THE FOLLOWING:
- CAR LIGHT AND ALARM CIRCUIT WITH GFCI PROTECTION PER NEC/CEC.
- GROUP CONTROL WHEN REQUIRED.
ACCESS TO THESE COMPONENTS WILL BE FROM INSIDE THE HOISTWAY. THIS WILL REQUIRE TK ELEVATOR TO BE ON SITE.
NOTE: IF STANDBY POWER IS SUPPLIED TO ELEVATOR, CAR LIGHT AND ALARM CIRCUIT AND GROUP CONTROL SERVICE MUST BE
STANDBY POWER BACKED.
Ɣ LIGHTING (MINIMUM 200LUX/19FT. CANDLES) AND SWITCH, CONVENIENCE OUTLETS WITH GFCI PROTECTION PER NEC/CEC. LIGHTING IS
REQUIRED AT THE PIT LEVEL AND THE CONTROLLER LANDING.
Ɣ A LIGHT SWITCH LOCATED 4'-0" ABOVE BOTTOM LANDING NEXT TO THE TOP RUNG OF THE LADDER.
Ɣ A LIGHT SWITCH LOCATED 4'-0" ABOVE THE CONTROLLER LANDING FLOOR.
Ɣ CONDUIT AND WIRING FROM HOISTWAY TO ELEVATOR MONITORING PANELS BY OTHERS.
Ɣ PROVIDE A POWER TRANSFER WARNING CONTACT THAT CLOSES 20 SECONDS PRIOR TO TRANSFER IN EITHER DIRECTION AND IT OPENS
WHEN TRANSFER IS COMPLETE.
Ɣ TOTAL FULL LOAD UP SPEED AMPS IS BASED ON 100% OF ELEVATOR CAPACITY, THE VALUE NEEDED FOR EMERGENCY POWER SIZING.
Ɣ THE HYDRAULIC MOTORS ARE RATED FOR INTERMITTENT DUTY (SEC. 620-13 AND 430-33). BRANCH CIRCUIT CONDUCTORS CAN BE SIZED
FOR AN AMPACITY 90% OF THE MOTORS NAMEPLATE RATING AS DETERMINED BY (SEC. 430-22 [E])
BY OTHERS
ELEVATOR
DESIGNATOR
POWER
SUPPLY
HORSE
POWER
STARTING
A.C. AMPS
TOTAL FULL LOAD
UP SPEED MOTOR
A.C. AMPS
RATED
A.C. AMPS
SHORT CIRCUITCURRENT RATINGS
(AT 600V OR LESS)
THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT
ELECTRICAL DATA
Ɣ PRIMARY FIRE SERVICE LOCATED AT FLOOR:
Ɣ ALTERNATE FIRE SERVICE LOCATION AT FLOOR:
1
Ɣ BREAKERS AND DISCONNECT PROVIDED BY TK ELEVATOR AMP CIRCUIT BREAKER PROVIDED IN CONTROLLER BY TK ELEVATOR.
1 208 40 368 176 122.5 10,000 AMPS
Ɣ A PLUMB HOISTWAY BUILT ACCORDING TO CODE AND SIZES SHOWN.
Ɣ ADEQUATE SUPPORT FOR JACK, GUIDE RAIL BRACKETS, AND BUFFERS (FOR REACTIONS SHOWN)
Ɣ HOISTWAY BARRICADES AND ALL CUTTING AND PATCHING TO INSTALL HOISTWAY ENTRANCES, SILLS, HALL FIXTURES, OIL,
AND ELECTRIC LINES.
Ɣ PIT LADDER PER CAR (ACCORDING TO CODE) NOTE: MUST BE CLEAR OF ALL ELEVATOR EQUIPMENT.
Ɣ LEAVE OFF WALL PER ROUGH OPENING DIMENSIONS WHERE ENTRANCE IS INCLUDED. SEE INSTALLATION PROCEDURES FOR
FRAME-TO-WALL INTERFACE DETAILS TO ENSURE CONFORMANCE WITH LABELED ENTRANCE INTERFACE CONSTRUCTION.
AT CONTROLLER FLOOR, LEAVE OUT ENTIRE WALL. SEE ENTRANCE DRAWING FOR DETAILS. CONTROLLER @ FLOOR:
Ɣ POCKETS IN CORRIDOR WALL FOR HALL FIXTURES. NOTE: MUST BE LOCATED AS DIRECTED BY ELEVATOR CONTRACTOR
Ɣ SMOKE SENSORS (AS REQUIRED)
Ɣ ELEVATOR MEETS ASME A17.1 2016 CODE.
Ɣ A PROPERLY VENTED HOISTWAY AND MAINTAINED BETWEEN 32F (0C) AND 104F (40C) WITH NON-CONDENSING HUMIDITY
OF 10-95% PER LOCAL BUILDING CODE.
Ɣ SUMP PIT OR DRAIN AS REQUIRED BY LOCAL CODE BY GENERAL CONTRACTOR.
GENERAL DATA
28'-3" ROUGH OPENING HEIGHT@ FLOORS
1,2,3,4
8'-8" ROUGH OPENING FOR
CONTROLLER ENTRANCE @ FLOOR 2REAR OF HOISTWAYFRONT OF HOISTWAY300
4'-1"1'-1"
N SELECTOR5" S
JACK (TYP.)
Ɣ SAFETY BEAM REQUIRED PER OSHA 1926 502 PROVIDED AND INSTALLED BY OTHERS, AS DIRECTED BY TK ELEVATOR FIELD
OFFICE DESIGN LOAD = (STATIC, NOT IMPACT)5,000 LBS
Ɣ HEAT SENSOR REQUIRED AT CONTROLLER FLOOR TO ACTIVATE SHUNT. HEAT SENSOR IS TO BE LOCATED WITHIN 2'-0" OF THE
SPRINKLER HEAD.
3"
01/31/22
"PLEASE REFERENCE ASME A17.1 (2.2.2) FOR SUMP PIT REQUIREMENTS"
REFER TO SECTION SHEET FOR CONTROLLER ENTRANCE ROUGH OPENING WIDTH
5 OF 7140-1739-01A 12/10/2021 RW C
DATE JOB NUMBER SHEETDRAWN REV THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
TK ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF TK ELEVATOR.
FOR: MELANGE FLATS
ADDRESS: 920 VETERANS WAY
CITY: CARMEL, IN 46032 TK Elevator
³WHERE DISTANCE BETWEEN FLOORS EXCEEDS THE MAXIMUM BRACKET SPAN, BRACKET SUPPORT MUST BE
PROVIDED MIDWAY. BRACKET SUPPORT WILL NEED TO BE SUPPLIED BY OTHERS TO ALLOW FOR RAIL
ATTACHMENT. INSIDE SUPPORT SHALL NOT BE RECESSED BEHIND WALL SYSTEM AND SHALL NOT BE PROUD
BY MORE THAN 1/4´ AT ANY POINT. COORDINATE WITH TK ELEVATOR SUPPORT/OPERATIONS MANAGER´
FOR ELEVATOR: 1
IF A CUT STARTER RAIL IS CALLED FOR IN THE STACK,
CONFIRM THE NUMBER OF SPLICES PRIOR TO CUTTING
8'-8"
HOISTWAY WIDTH 6'-11"HOISTWAY DEPTH4'-7 3/4"SRAILS6'-0" ROUGH OPENING
WIDTH @ TYP. FLR.
BRACKET LOCATION
DIMENSIONS
RAIL SECTION
DIMENSIONS
8'-3" ROUGH
OPENING HEIGHT2"4'-7 3/4"SAFETY BEAM5'-0"
PIT DEPTH
12'-11" CLEAR OVERHEAD
FRONT OF HOISTWAY
REAR OF HOISTWAY
34'-11" NET TRAVEL
RAIL STACK SECTION VIEW
RAILS AND BRACKETS - TOTAL QUANTITY
RAILS
BRACKETS
QTY:
RAIL TO WALL:
(7) 16 FT
SPLICES:6
LEFT HAND RIGHT HAND
5 5
4 3/4"4 3/4"4'-0"INSERT1'-6"2'-6"2'-1 3/4"12'-7 1/2"
RAIL
16'-0"
RAIL
16'-0"
RAIL
8'-0"
RAIL
11'-6" 1'-3" 10'-6" 1'-3" 10'-7" 1'-3"10'-1" 1'-3" 3'-9"
12 3 4
CAR RAIL LINE LENGTH QUANTITY (8) - PER CAR
LENGTH QUANTITY
8'-0"2
16'-0"4
12'-7 1/2"2
FLOOR TO FLOOR TRAVEL
FLOOR TO FLOOR TRAVEL
3-4 11'-9"
2-3 11'-10"
1-2 11'-4"
NET TRAVEL 34'-11"
CAR RAIL LINE BRACKETS AND INSERT LOCATIONS - PER CAR
LOCATION DESCRIPTION
15'-9"MAX. UNSUPPORTED RAIL BRACKET SPACING
11'-6"ABOVE TOP FLOOR
1'-3"BELOW 1-4
TYPICAL SURFACE
MOUNTING DETAILS
TYP
48" X 6" STEEL PLATE WELDED TO TUBESTEEL PROVIDED AND INSTALLEDBY G.C. MOUNT FLUSH WITH WALL.
48" X 6" STEEL PLATE WELDED TOSTEEL PROVIDED AND INSTALLED
BY G.C. MOUNT FLUSH WITH WALL.
AT ALL FLOOR LOCATIONS
16" BRACKET O.A.16" BRACKET O.A.
13 1/2"
TYP
48" X 6"
INSERT INSTALLED BY G.C.
MOUNT FLUSH WITH WALL &GROUT SOLID ALL AROUND.
16" BRACKET O.A.
01/31/22
ENTRANCE LEFT SIDE VIEWLOBBY SIDEENTRANCE ELEVATION VIEW AT TYPICAL FLOORÎENTRANCE PLAN VIEW
LOBBY SIDE
A
DD
R2 R1ƔƔ
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
TK ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF TK ELEVATOR.
FOR: MELANGE FLATS
ADDRESS: 920 VETERANS WAY
CITY: CARMEL, IN 46032 6 OF 7
DATE
C
SHEETJOB NUMBER
12/10/2021
REVDRAWN
RW 140-1739-01ATK Elevator
FEATURES OF ENTRANCES DATA
SILL MAXIMUM WHEEL LOADS 625 LBS
KEYHOLES TO BE INCLUDED
THIS FRAME HAS A WARNOCK HERSEY LABEL OF 2 HOURS
DUST COVERS NOT INCLUDED
FEATURES OF YOUR ENTRANCES
FEATURES FINISH LOCATION
DOOR OPEN STRUT BUMPERS:PROVIDED @1,2,3,4
KICKPLATES:__________@1,2,3,4
BINDERS:__________@1,2,3,4
SILL FINISH:ALUMINUM @1,2,3,4
TOTAL WEIGHT ELEVATOR 1 ELEVATOR
CAB AND HALL DOORS 342 LBS
NOTE "A":
8" MINIMUM STRUCTURAL
SUPPORT FOR SILL INSTALLATION
ENTRANCE CHART
M721 ENTRANCE:
CENTER OPENING AND 1 SPEED = FRAME OPENING + 1'-3"
2 SPEED = FRAME OPENING + 1'-5"
ENTRANCE TYPE : M721
FOR ELEVATOR 1
1 SPEED
RIGHT HAND FRONT ENTRANCE
FOR ELEVATOR 1
FOR ELEVATOR: 1
R2 228
R1 564
DOOR REACTION
CASE 1
SEE NOTE "A"5'-0"C/L 4.10.5 28 CFR PART 36CLEAR OPENING HEIGHT (REFER TO DOOR SCHEDULE)CLEAR OPENING HEIGHT + 2" = OVERALL FRAME HEIGHT2"0 1/8"MINIMUM FLOOR TO FLOOR HEIGHT = "SEE ENTRANCE CHART"CLEAR OPENING WIDTH
REFER TO DOOR SCHEDULE
2"
FRAME
2"
FRAME
ACTUAL
WALL SIZE
0 3/4"
ELEVATOR: 1 FRONT ENTRANCE SCHEDULE
FLOOR WALL TYPE WALL SIZE
ACTUAL OA. FRAME "B" DIM.
PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR
BUILDING LANDING MATRIX
ENTRANCE DIMS.
DIM "B"
4 7'-0" H X 3'-6" W TBD TBD TBD
3 7'-0" H X 3'-6" W TBD TBD TBD
2 7'-0" H X 3'-6" W TBD TBD TBD
1 7'-0" H X 3'-6" W TBD TBD TBD
FRONT ENTRANCE HALL FIXTURES
ITEM DESCRIPTION FLOOR
A HALL STATION TYPICAL
D HALL POSITION INDICATOR @1
HALL FIXTURES ARE FOR REPRESENTATION ONLY. FOR ACTUAL LOCATION OF
POCKETS FOR HALL FIXTURES, CONTACT ELEVATOR CONTRACTOR.
6'-0"
ROUGH OPENING WIDTH
8'-3"ROUGH OPENING HEIGHT NOTES:
GENERAL CONTRACTOR RESPONSIBLE FOR HOISTWAY REINFORCING
AT FLOOR SLAB BEFORE INSTALLATION OF ENTRANCE FRAMES.
MINIMUM OF 4" HIGH X 8" WIDE REINFORCED CONCRETE, REINFORCED
OF OPENING REQUIRED FOR ANCHORING SILL SUPPORT ASSEMBLY,
REINFORCING TO BE LOCATED WITH RESPECT TO REACTION POINTS,
REFERENCE INSTALLATION DRAWINGS ARE AVAILABLE UPON
REQUEST.
REACTIONS (LBS.) DUE TO LOADS ON DOOR PANELS, APPROX.
HORIZONTAL LOADS AND LOCATION TO BUILDINGS SHOWN PER ASME
A17.1 PART II,
THE SPECIFIED LOADS ARE CONSIDERED IMPACTED.2" BELOWEACH FLOOR5'-3" 2'-1 1/2"
01/31/22
ENTRANCE ELEVATION VIEWÎŹŹŹPHONE
BUILDING POWER
(SEE CONTROLLER KNOCK OUT DETAIL)
FIRE ALARM
WALL FINISH ŹDIM "C"
DIM "D"
120V DEDICATED CAB LIGHT CIRCUIT
ŹƔ(DIM "E") SHAFT LINER FILLER BY G.C.
LOBBY SIDE
ENTRANCE PLAN VIEW
ENTRANCE SIDE VIEWLOBBY SIDEA
R2 R1 ƔƔ
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
TK ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF TK ELEVATOR.
FOR: MELANGE FLATS
ADDRESS: 920 VETERANS WAY
CITY: CARMEL, IN 46032 7 OF 7
DATE
C
SHEETJOB NUMBER
12/10/2021
REVDRAWN
RW 140-1739-01ATK Elevator
FEATURES OF ENTRANCES DATA
SILL MAXIMUM WHEEL LOADS 625 LBS
KEYHOLES TO BE INCLUDED
THIS FRAME HAS A WARNOCK HERSEY LABEL OF 2 HOURS
DUST COVERS NOT INCLUDED
FEATURES OF YOUR ENTRANCES
FEATURES FINISH LOCATION
DOOR OPEN STRUT BUMPERS:PROVIDED @1,2,3,4
KICKPLATES:__________@1,2,3,4
BINDERS:__________@1,2,3,4
SILL FINISH:ALUMINUM @1,2,3,4
TOTAL WEIGHT ELEVATOR 1 ELEVATOR
CAB AND HALL DOORS 342 LBS
NOTE "A":
8" MINIMUM STRUCTURAL
SUPPORT FOR SILL INSTALLATION
ENTRANCE CHART
M721 ENTRANCE:
CENTER OPENING AND 1 SPEED = FRAME OPENING + 1'-3"
2 SPEED = FRAME OPENING + 1'-5"
ENTRANCE TYPE : M721
FOR ELEVATOR 1
1 SPEED
RIGHT HAND FRONT ENTRANCE
FOR ELEVATOR 1
FOR ELEVATOR: 1
R2 228
R1 564
DOOR REACTION
CASE 1ŻCONTROLLER KNOCKOUT DETAIL
5"
8 3/4"
9 3/4"
11 3/4"3"4 3/4"1'- 11"7 5/8"LOBBY SIDE
SILL
2"1"
LOBBY SIDE
EXPOSED CMU7 5/8"HOISTWAY CMU
COLUMN WIDTH(WALL SIZE + 2.25")WALL SIZESILL
FRONT WALL CONDITION FOR EXPOSED MASONRYŻŻŻCLEAR OPENING WIDTH
REFER TO DOOR SCHEDULE
2"
FRAME
2"
FRAME
ELECTRICAL CONTRACTOR NOTE:
3 PHASE POWER, 120V 15 AMP CIRCUIT, FIRE ALARM
AND PHONE TO BE ROUTED TO THE TOP OF THE
CONTROLLER AT THE CONTROLLER LANDING LEVEL.
LEAVE OFF ENTIRE WALL AT FLOOR
FOR FRAME AND CONTROLLER INSTALLATION
2
CONSTRUCTION DETAIL VIEW
FOR REPRESENTATION ONLY
SEE NOTE "A"5'-0"C/L 4.10.5 28 CFR PART 36CLEAR OPENING HEIGHT (REFER TO DOOR SCHEDULE) CLEAR OPENING HEIGHT + 2" = OVERALL FRAME HEIGHT2"0 1/8"MINIMUM FLOOR TO FLOOR HEIGHT = "SEE ENTRANCE CHART"DIM "B" SEE
ENTRANCE SCHEDULE
4 7'-0" H X 3'-6" W TBD TBD TBD
3 7'-0" H X 3'-6" W TBD TBD TBD
2 7'-0" H X 3'-6" W TBD TBD TBD
1 7'-0" H X 3'-6" W TBD TBD TBD
ELEVATOR: 1 FRONT ENTRANCE SCHEDULE
FLOOR WALL TYPE WALL SIZE
ACTUAL OA. FRAME "B" DIM.
PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR
BUILDING LANDING MATRIX
ENTRANCE DIMS.
ENTRANCE WALL DIMENSIONS
DIM "C" MIN. WALL
THK. REQUIRED
DIM "D" WALL FACE
TO FRAME FACE
DIM "E" SHAFT
LINER THICKNESS
REFER TO NOTE B3/4" 8 1/2"
NOTES:
GENERAL CONTRACTOR RESPONSIBLE FOR HOISTWAY REINFORCING
AT FLOOR SLAB BEFORE INSTALLATION OF ENTRANCE FRAMES.
MINIMUM OF 4" HIGH X 8" WIDE REINFORCED CONCRETE, REINFORCED
OF OPENING REQUIRED FOR ANCHORING SILL SUPPORT ASSEMBLY,
REINFORCING TO BE LOCATED WITH RESPECT TO REACTION POINTS,
REFERENCE INSTALLATION DRAWINGS ARE AVAILABLE UPON
REQUEST.
REACTIONS (LBS.) DUE TO LOADS ON DOOR PANELS, APPROX.
HORIZONTAL LOADS AND LOCATION TO BUILDINGS SHOWN PER ASME
A17.1 PART II,
THE SPECIFIED LOADS ARE CONSIDERED IMPACTED.
5'-3" 2'-1 1/2"2" BELOWEACH FLOORNOTE B:
SHAFT LINER THICKNESS AND TYPE TO BE DETERMINED
AND ADVISED BY G.C./ ARCHITECT TO ENSURE LOCAL
FIRE RATING IS ACHIEVED.
01/31/22