HomeMy WebLinkAboutS100 - OVERALL FOUNDATION PLANC-5
C-5
C-5 C-5
C-5 C-5
C-5
C-5
C-6
C-5
C-6C-6
C-6
WF-3 WF-3
WF-3 WF-3
WF-3 WF-3
WF-2 WF-2WF-2
WF-2WF-2WF-2F-5
F-4
F-4
F-6 F-5
F-4
F-6.5
F-6.5
F-6.5
F-4
F-6.5
F-5 F-6
F-4
F-4
F-5
3
S301
1
S301
4
S301
7
S301
5
S301
6
S301
23' - 3 3/8" 24' - 1 1/4"2' - 1 1/4" 19' - 10"11' - 11"14' - 1"11' - 6 11/16"18' - 10 1/8" 3' - 6"21' - 2" 22' - 1 1/8"
7
S301
1
S301
1
S301
5
S301
6
S301
4
S301
3
S301
1
S301
4
S301
4
S301
1
S301
1
S301
5
S301
5
S301
WF-2 WF-2
1
4
E D G A I J
14' - 6 3/4"22' - 1"4' - 5 3/4"12' - 6 1/4"14' - 6 3/4"22' - 1"4' - 5 3/4"12' - 6 1/4"OF STUD)
2 3/4" (OUTSIDE
172' - 5 3/4"OF STUD)
2 3/4" (OUTSIDE
3
F B
2
14' - 6 3/4"7' - 6 5/8"14' - 6 3/8"C-5
F-4A
C-5
F-4A
F-12 F-12
C-5
C-4 C-4
C-4
F-4
F-4AF-4
C-5
F-6
C-5
C-5
C-2
C-5 C-5
F-6
C-4
F-4
C-4
F-4A
C-4
F-4A
F-4A
C-4
C-2
TS-2
TS-3
TS-2
TS-3
TS-2
TS-2 TS-2TS-2F-4
C-4
F-4A
53' - 7 3/4"53' - 7 3/4"TS-23
S301
3
S301
3
S301
3
S301
C-6 C-6 C-6 C-6 C-6 C-6 C-6
C-6 C-6
C-6
F-4 F-6 F-4 F-4 F-6
F-4
4
S300
TYP.
TYP.
1
S300
TYP.
1
S300
TYP.
2
S301
TYP.1' - 0 11/16"1' - 0 11/16"OUTSIDE OF
STUD DIM. VERIFY
W/ ARCH.
OUTSIDE OF
STUD DIM.,
VERIFY W/ ARCH.
F-4
F-4
F-4 F-4 WF-1WF-2WF-2
WF-2
WF-3WF-3
WF-3
WF-2WF-2WF-2WF-2WF-2WF-3WF-3WF-1 WF-1
WF-2
WF-2 SLOPESLOPE
SLOPESLOPE
SLOPE
WF-2WF-2WF-2WF-2WF-2WF-2WF-3WF-3WF-3
TS-3 WF-3
WF-2
WF-2
WF-2
WF-2WF-2WF-2TS-2WF-1 WF-1
WF-1
+100.00'
FINISH FLOOR
(SHADED AREA)
+100.00'
FINISH FLOOR
(SHADED AREA)
+99.58'
FINISH FLOOR
(EDGE OF GARAGE, TYP.)
+99.58'
FINISH FLOOR
(EDGE OF GARAGE, TYP.)SLOPESLOPESLOPESLOPE
SLOPESLOPESLOPE+100.00'
T.O. STEM WALL
(SEE NOTE)
+100.00'
T.O. STEM WALL
(SEE NOTE)
2
S301
5
S400
6
S400
+98.67'
T.O. FTG (TYP.)
+98.67'
T.O. FTG (TYP.)
C H
TYP.
WF-2
WF-3
WF-2
WF-2
WF-3WF-2WF-2STEP FTG.
AS REQ'D
(TYP.)
STEP FTG.
AS REQ'D
(TYP.)WF-2WF-2WF-2STEP FTG.
AS REQ'D
(TYP.)
STEP FTG.
AS REQ'D
(TYP.)
B.O. FTG = 30" BELOW GRADE MIN.B.O. FTG = 30" BELOW GRADE MIN.
WF-2 WF-2 WF-2 WF-2 WF-3WF-2WF-29 9/16"9 5/16"EXTEND CONCRETE STEMWALL
UNDER STUD WALL, SEE ARCH.
MATCH STUD WALL WIDTH
PROVIDE 3'-0"x3'-0"
CONCRETE PIER
AT STONE COLUMN
REINFORCED WITH
(12) #7 VERT AND
#4 TIES AT 10" O.C.
1. DO NOT SCALE DRAWINGS, USE ONLY WRITTEN DIMENSIONS.
2. ALL DIMENSIONS ON THIS PLAN ARE TAKEN FROM CENTERLINE TO
CENTERLINE OF COLUMNS OR GRIDLINES UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO START OF
CONSTRUCTION, UNLESS NOTED OTHERWISE
3. THE CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL PLUMBING,
MECHANICAL, AND ELECTRICAL REQUIREMENTS AND CLEARANCES PRIOR TO
PROCEEDING WITH THE PROJECT. PENETRATIONS THROUGH THE
STRUCTURE SHALL BE SUBJECT TO APPROVAL BY THE STRUCTURAL
ENGINEER.
4. PROVIDE CONTROL JOINTS PER GENERAL NOTES. WITH OWNER APPROVAL,
CONTROL JOINTS MAY BE OMITTED IN LIEU OF CONSTRUCTION JOINTS,
HOWEVER THESE JOINTS MUST FALL ON COLUMN LINES. REFER TO SLAB
JOINT DETAILS FOR MORE INFORMATION.
5. ORIENT CONTROL JOINTS TO AVOID RE-ENTRANT CORNERS AT CORNER
JOINTS
6. TOP OF FOOTING ELEVATIONS ARE BASED ON PRELIMINARY CIVIL DRAWINGS
AND MUST BE VERIFIED BY CONTRACTOR PRIOR TO THE START OF
CONSTRUCTION
7. EXISTING SITE CONDITIONS AND EXISTING BUILDING INFORMATION IS BASED
ON LIMITED FIELD MEASUREMENTS PRELIMINARY CIVIL DRAWINGS AND MUST
BE VERIFIED BY CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. IF
EXISTING BUILDING CONDITIONS DO NOT MATCH THOSE SHOWN ON
DRAWINGS, CONTACT STRUCTURAL ENGINEER IMMEDIATELY.
SHEET NOTES
LENGTHSCHEDULED EMBEDMENT4" PROJECTIONSTEEL COLUMN,
SEE SCHEDULE
STEEL BASE PLATE,
SEE SCHEDULE
ASTM F1554 GR. 36
ANCHOR RODS, SEE
SCHEDULE FOR SIZE
TYPICAL BASE PLATE DETAIL
DAMAGE THREADS OR
TACK WELD
1-1/2" NON-SHRINK
GROUT
LEVELING NUT AT EACH
ANCHOR ROD
BASE PLATE (BP) SCHEDULE
ANCHOR
ROD DIA.
3/4"
MAX. HOLE
DIA.
1 1/16"
MINIMUM WASHER
SIZE THICKNESS
2" 1/4"
NOTES:
1. CIRCULAR OR SQUARE WASHERS MEETING THE SIZE SHOWN ARE ACCEPTABLE.
2. ADEQUATE CLEARANCE MUST BE PROVIDED FOR THE WASHER SIZE SELECTED.
BP-2 10"10"1 1/2"
7"
1 1/2"1 1/2"7"1 1/2"EQEQEQ EQ
3/4" THICK
SEE COLUMN
SCHEDULE
BP-1 8"8"1 1/2"
5"
1 1/2"1 1/2"5"1 1/2"EQEQEQ EQ
3/4" THICK
SEE COLUMN
SCHEDULE
BP-3 1' - 2"11"1 1/2"
8"
1 1/2"1 1/2"11"1 1/2"EQ EQ
3/4" THICK
SEE COLUMN
SCHEDULE
GRIDGRID
GRID GRID
GRID
GRID
DIM. "A"
COL. CL "A"LOCATION
GRID A
GRID 4
GRID J
3-1/4"
6"
3-1/4"
CAST-IN-PLACE
CONCRETE SLAB
6x6 W1.4xW1.4 WELDED WIRE
FABRIC CENTERED IN SLAB
(FLAT SHEETS ONLY)
15 MIL VAPOR BARRIER
COMPACTED SUBGRADE
NOTE: PROVIDE SAWN CONTROL JOINTS AT COLUMN LINES AND AT 10'-0" O.C.
EACH WAY (MAX.)
FLOOR SLAB CONSTRUCTION
4" (U.N.O.)6" MIN.INEGSS
LOINA E NPROF REEN o.
GRE S
DRETEI
STATE OF
NA ADNII
11100391 NNAMFFOHHPESOJ
SHEET NUMBER:
PROJECT NUMBER: DRAWN BY:PROJECT TITLE:This is an original design, created by KJG Architecture,
Inc. The concepts, ideas, plans and details are the sole
property of KJG Architecture, Inc. None of the
aforementioned shall be used by or disclosed to any
person, firm or organization for any purpose without the
prior written permission of KJG Architecture, Inc.
NO. DESCRIPTION:DATE
ISSUED:
DRAWING TITLE:
PROFESSIONAL SEAL:
PROJECT DATE:
DISCLAIMER:
KJG ENGINEERING
527 Sagamore Pkwy W., Suite 101
West Lafayette, Indiana 47906
Ph: 765.497.4598 Fx: 765.497.4599
www.kjgengineering.com
08/16/2021MÉLANGE FLATSBUILDING 12VETERANS WAY & MONON GREEN BOULEVARDCARMEL, INDIANA 4603208/16/2021
S100
OVERALL
FOUNDATION PLAN
E2020.174 KBM
1/8" = 1'-0"S100
1 FOUNDATION PLAN NCOLUMN SCHEDULE
MARK SIZE BASE PLATE TYPE ANCHOR RODS (DIA.
x EMBEDMENT)
C-1 3 1/2 x 3 1/2 PSL N/A N/A
C-2 5 1/4 x 5 1/4 PSL N/A N/A
C-3 HSS3-1/2X3-1/2X1/4 BP-1 3/4" x 10"
C-4 HSS5X5X1/4 BP-2 3/4" x 10"
C-5 HSS5X5X1/2 BP-2 3/4" x 10"
C-6 HSS12X4X3/8 BP-3 3/4" x 10"
FOOTING SCHEDULE
MARK WIDTH LENGTH THK. *
FOOTING REINFORCEMENT
(GRADE 60)
BOTTOM TOP
F-4 4' - 0" 4' - 0" 2' - 0" #5's AT 10" O.C. EW NONE
F-4A 4' - 0" 4' - 0" 1' - 0" #5's AT 10" O.C. EW NONE
F-5 5' - 0" 5' - 0" 2' - 0" #6's AT 10" O.C. EW #6's AT 10" O.C. EW
F-6 6' - 0" 6' - 0" 2' - 0" #6's AT 10" O.C. EW #6's AT 10" O.C. EW
F-6.5 6' - 6" 6' - 6" 2' - 0" #6's AT 10" O.C. EW #6's AT 10" O.C. EW
F-12 10' - 3" 12' - 0" 2' - 0" #5's AT 10" O.C. E.W. NONE
WF-1 1' - 0" CONT. 2' - 0" (2) - #5 CONT. BARS NONE
WF-2 2' - 0" CONT. 2' - 0" (3) - #5 CONT. BARS
WF-3 3' - 0" CONT. 2' - 0" (4) - #5 CONT. BARS
THICKENED SLAB SCHEDULE
MARK WIDTH THICKNESS REINFORCEMENT (GRADE 60)
BOTTOM TOP
TS-2 2' - 0"1'-0"(3) - #5 CONT. BARS NONE
TS-3 3' - 0"1'-0"(4) - #5 CONT. BARS NONE
NOTE:CONCRETE STEM WALLS SHALL BE PROVIDED AT ALL LOCATIONS WHERE
"WF" WALL FOOTINGS ARE SHOWN ON PLANS, SEE DETAILS FOR THICKNESS. ALL
CONCRETE STEM WALLS SHOULD MAINTAIN T.O. STEM WALL ELEVATION SHOWN ON
PLANS, EXCEPT AT OPENINGS, WHERE BLOCKOUTS SHOULD BE PROVIDED. T.O.
STEM WALL ELEVATION AT ALL MAN DOOR OPENINGS SHALL BE DROPPED TO
MATCH FINISH FLOOR, AND ELEVATION AT GARAGE DOORS SHALL BE DROPPED TO
MATCH B.O. GARAGE SLAB TURNDOWN ELEVATION (SEE DETAILS)
1 CONSTRUCTION SET 08/16/21
2 ADDENDUM 1 11/01/21
* ADJUST FOOTING THICKNESS AS REQUIRED TO MAINTAIN BOTTOM OF FOOTING
AT 30" MIN. BELOW GRADE MINIMUM AND AS REQUIRED ALONG LINE "J", SEE PLAN
BOTTOM OF FOOTING TO
BEAR -6'-0" BELOW GRADE
ALONG LINE "J"
01/31/22