Loading...
HomeMy WebLinkAboutE106_Roof Power Plan1 DISCONNECT SWITCH PROVIDED WITH RTU AND WIRED BY ELECTRICAL CONTRACTOR. 2 480 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSE AT 15 AMPS. 3 208 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 30 AMPS. 4 208 VOLT, 2 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 25 AMPS. 5 TWO SPEED FAN DISCONNECT SWITCH IS FACTORY INSTALLED AND SHALL BE WIRED BY ELECTRICAL CONTRACTOR. SEE DETAIL 2/E106. 6 208 VOLT, 2 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 15 AMPS. 7 DISCONNECT SWITCH PROVIDED WITH FAN AND WIRED BY ELECTRICAL CONTRACTOR. 8 RUN 3#12, #12 GND IN 3/4" C. TO ASSOCIATED INDOOR FAN COIL UNIT FOR POWER AND CONTROLS. INSTALL PER MANUFACTURERS INSTRUCTIONS. 9 EXHAUST FAN SHALL BE CONTROLLED VIA EMS SYSTEM TO RUN ONLY DURING OCCUPIED HOURS. SEE DETAIL 2/E113. 10 CONDENSER PROVIDED WITH WEATHER PROOF CONTROL PANEL AND DOOR ACTIVATED DISCONNECT SWITCH. 11 208 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 15 AMPS. 12 FAN SHALL BE POWERED FROM BAKERY OVEN. SEE DETAIL 3/E113. 13 FAN CIRCUIT SHALL BE RUN THROUGH TWO SPEED CONTROLLER AND MOTORIZED DAMPER CIRCUIT SHALL BE RUN THROUGH CONTACTOR, BOTH FACTORY INSTALLED IN THE POWER PLUS UNIT. SEE DETAIL 2/E106. 14 RUN 2 #12 PLUS GROUND IN SEPARATE 3/4" CONDUIT DOWN TO HOOD CONTROL PANEL FOR FAN CONTROLS. SEE HOOD DRAWINGS FOR ADDITIONAL INFORMATION ON THE HOOD REGULAR AND LOW VOLTAGE POWER REQUIREMENTS. 15 RUN CIRCUIT THROUGH THE CONTACTOR FOR THE DISHWASHER CIRCUIT TO INTERLOCK FAN OPERATION WITH THE OPERATION OF THE DISHWASHER. SEE E104 FOR ADDITIONAL INFORMATION. 16 480 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSE AT 15 AMPS. 17 EQUIPMENT IS EXISTING TO REMAIN. 18 EXISTING TO REMAIN MOTOR ROOM EXHAUST AND PURGE FANS. EXISTING CPC CONTROLS ARE ALSO TO REMAIN AND SHALL BE RECONNECTED TO NEW CPC CONTROL SYSTEM. 20 WIRE RECEPTACLE TO NEAREST EXISTING ROOF RECEPTACLE CIRCUIT, PRESUMED TO BE G-32. KEY NOTES (E) H-1,3,5 10 P-20,22,24 PF-70,72 8 6 12 7WP 17 HSB-9 P-8,10,12 10 PF-68(P) WG G-36 9 7 17 (E) (E)G-32 H-13,15,17 2 2 PF-68(P)WG 15 7 7 H-2,4,6 14 H-8,10,12 14 PA-33 PA-35 9 7 REL. FAN COIL OUTDOOR UNIT ETR RTU-2 ETR RTU-3 ETR EF-9 ETR EF-8 ETR RTU-1 (E) (E) (E) H-7,9,11 17 (E) (E) (E)G-32 H-25,27,29 18 (E)G-20 (E) (E) (E) H-2,4,6 2 H-25,27,29 WG WG (E)G-32 (E) H-14,16,18 2 2 PD-42 PD-42 20 SHEET NO. This drawing was prepared for use on a specific site contemporaneously with its issue date and it is not suitable for use on a different project site or at a later time. Use of this drawing for reference or example on another project requires the services of properly licensed architects and engineers. Reproduction of this drawing for reuse on another project is not authorized and may be contrary to the law. BRR Original printed on recycled paper COPYRIGHT NOTICE PROJECT NO. SHEET TITLE ISSUES & REVISIONS DRAWN BY: PROFESSIONAL SEAL PROJECT MANAGER: DOCUMENT DATE: CHECKED BY: PROJECT NAME PROJECT ADDRESS 1 2 3 4 5 ABCDEABCDE12 3 4 5 8131 METCALF AVENUE SUITE 300 OVERLAND PARK, KS 66204 www.brrarch.com TEL: 913-262-9095 FAX: 913-262-9044 ARCHITECT OF RECORD: 62930563 12/07/2021 THE FRESH MARKET The Centre Retail Center NO. DATE DESCRIPTION An Erdman Anthony Company 552 Fort Evans RD STE 200 Leesburg, VA 20176 703.777.5988 Leesburg@erdmananthony.com 116th St. and Rangeline Rd. Carmel, Indiana ROOF POWER PLAN E-106 BSD DSP 12/08/2021 02/07/22