HomeMy WebLinkAboutE106_Roof Power Plan1 DISCONNECT SWITCH PROVIDED WITH RTU AND WIRED BY ELECTRICAL CONTRACTOR.
2 480 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSE AT 15 AMPS.
3 208 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 30 AMPS.
4 208 VOLT, 2 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 25 AMPS.
5 TWO SPEED FAN DISCONNECT SWITCH IS FACTORY INSTALLED AND SHALL BE WIRED
BY ELECTRICAL CONTRACTOR. SEE DETAIL 2/E106.
6 208 VOLT, 2 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 15 AMPS.
7 DISCONNECT SWITCH PROVIDED WITH FAN AND WIRED BY ELECTRICAL CONTRACTOR.
8 RUN 3#12, #12 GND IN 3/4" C. TO ASSOCIATED INDOOR FAN COIL UNIT FOR POWER AND
CONTROLS. INSTALL PER MANUFACTURERS INSTRUCTIONS.
9 EXHAUST FAN SHALL BE CONTROLLED VIA EMS SYSTEM TO RUN ONLY DURING
OCCUPIED HOURS. SEE DETAIL 2/E113.
10 CONDENSER PROVIDED WITH WEATHER PROOF CONTROL PANEL AND DOOR
ACTIVATED DISCONNECT SWITCH.
11 208 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSED AT 15 AMPS.
12 FAN SHALL BE POWERED FROM BAKERY OVEN. SEE DETAIL 3/E113.
13 FAN CIRCUIT SHALL BE RUN THROUGH TWO SPEED CONTROLLER AND MOTORIZED
DAMPER CIRCUIT SHALL BE RUN THROUGH CONTACTOR, BOTH FACTORY INSTALLED IN
THE POWER PLUS UNIT. SEE DETAIL 2/E106.
14 RUN 2 #12 PLUS GROUND IN SEPARATE 3/4" CONDUIT DOWN TO HOOD CONTROL PANEL
FOR FAN CONTROLS. SEE HOOD DRAWINGS FOR ADDITIONAL INFORMATION ON THE
HOOD REGULAR AND LOW VOLTAGE POWER REQUIREMENTS.
15 RUN CIRCUIT THROUGH THE CONTACTOR FOR THE DISHWASHER CIRCUIT TO
INTERLOCK FAN OPERATION WITH THE OPERATION OF THE DISHWASHER. SEE E104
FOR ADDITIONAL INFORMATION.
16 480 VOLT, 3 POLE, NEMA 3R, 30 AMP, FUSED SAFETY SWITCH, FUSE AT 15 AMPS.
17 EQUIPMENT IS EXISTING TO REMAIN.
18 EXISTING TO REMAIN MOTOR ROOM EXHAUST AND PURGE FANS. EXISTING CPC
CONTROLS ARE ALSO TO REMAIN AND SHALL BE RECONNECTED TO NEW CPC
CONTROL SYSTEM.
20 WIRE RECEPTACLE TO NEAREST EXISTING ROOF RECEPTACLE CIRCUIT, PRESUMED TO
BE G-32.
KEY NOTES
(E) H-1,3,5
10 P-20,22,24
PF-70,72
8
6
12
7WP
17 HSB-9
P-8,10,12
10
PF-68(P)
WG
G-36
9
7
17
(E)
(E)G-32
H-13,15,17
2
2
PF-68(P)WG
15
7
7
H-2,4,6
14
H-8,10,12
14
PA-33
PA-35
9
7
REL. FAN COIL
OUTDOOR UNIT
ETR
RTU-2 ETR
RTU-3
ETR
EF-9
ETR
EF-8
ETR RTU-1
(E)
(E)
(E) H-7,9,11
17
(E)
(E)
(E)G-32
H-25,27,29
18
(E)G-20
(E)
(E)
(E) H-2,4,6
2
H-25,27,29
WG
WG
(E)G-32
(E)
H-14,16,18
2
2
PD-42
PD-42
20
SHEET NO.
This drawing was prepared for use on a
specific site contemporaneously with its issue
date and it is not suitable for use on a
different project site or at a later time. Use of
this drawing for reference or example on
another project requires the services of
properly licensed architects and engineers.
Reproduction of this drawing for reuse on
another project is not authorized and may be
contrary to the law.
BRR Original printed on recycled paper
COPYRIGHT NOTICE
PROJECT NO.
SHEET TITLE
ISSUES & REVISIONS
DRAWN BY:
PROFESSIONAL SEAL
PROJECT MANAGER:
DOCUMENT DATE:
CHECKED BY:
PROJECT NAME
PROJECT ADDRESS
1 2 3 4 5 ABCDEABCDE12 3 4 5
8131 METCALF AVENUE
SUITE 300
OVERLAND PARK, KS 66204
www.brrarch.com
TEL: 913-262-9095
FAX: 913-262-9044
ARCHITECT OF RECORD:
62930563
12/07/2021
THE FRESH
MARKET
The Centre Retail Center
NO. DATE DESCRIPTION
An Erdman Anthony Company
552 Fort Evans RD STE 200
Leesburg, VA 20176
703.777.5988
Leesburg@erdmananthony.com
116th St. and Rangeline Rd.
Carmel, Indiana
ROOF POWER
PLAN
E-106
BSD
DSP
12/08/2021
02/07/22