HomeMy WebLinkAboutEM104_Energy Management Control DetailsSHEET NO.
This drawing was prepared for use on a
specific site contemporaneously with its issue
date and it is not suitable for use on a
different project site or at a later time. Use of
this drawing for reference or example on
another project requires the services of
properly licensed architects and engineers.
Reproduction of this drawing for reuse on
another project is not authorized and may be
contrary to the law.
BRR Original printed on recycled paper
COPYRIGHT NOTICE
PROJECT NO.
SHEET TITLE
ISSUES & REVISIONS
DRAWN BY:
PROFESSIONAL SEAL
PROJECT MANAGER:
DOCUMENT DATE:
CHECKED BY:
PROJECT NAME
PROJECT ADDRESS
1 2 3 4 5 ABCDEABCDE12 3 4 5
8131 METCALF AVENUE
SUITE 300
OVERLAND PARK, KS 66204
www.brrarch.com
TEL: 913-262-9095
FAX: 913-262-9044
ARCHITECT OF RECORD:
62930563
12/07/2021
THE FRESH
MARKET
The Centre Retail Center
NO. DATE DESCRIPTION
An Erdman Anthony Company
552 Fort Evans RD STE 200
Leesburg, VA 20176
703.777.5988
Leesburg@erdmananthony.com
116th St. and Rangeline Rd.
Carmel, Indiana
ENERGY
MANAGEMENT
CONTROL DETAILS
EM104
BSD
NGS
DEFROST
BREAKER
OR
FUSES
DEFROST
CONTACTOR
DEFROST
RELAY
DEFROST
BREAKER
OR
FUSES
DEFROST
CONTACTOR
SYSTEM
SWITCH
DEFROST
LIGHT
NOTE: VERIFY ALL
CONNECTIONS WITH
PANEL DIAGRAMS.
1 PHASE
DEFROST
(AS REQUIRED)
(ONE PER CASE)
PRE-WIRED PANEL LOCATED AT
COMPRESSOR RACK.
PRE-WIRED IN DEFROST
PANEL.
ESR VALVE
(AT RACK OR REMOTE
LOCATION)
TO ESR
BOARD
LOW
VOLTAGE
TEMP PROBE FOR
DEFROST TERM.
(ONE PER CASE)
TEMP PROBE
(ONE PER CASE)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
NOTE: VERIFY ALL CONNECTIONS
WITH PANEL DIAGRAMS.
DEFROST
BREAKER
OR
FUSES
DEFROST
CONTACTOR
DEFROST
RELAY
SYSTEM
SWITCH
DEFROST
LIGHT
PRE-WIRED PANEL LOCATED IN
DEFROST PANEL.
LOW
TEMP PROBE FOR
DEFROST TERM.
(ONE PER EVAP COIL)
TEMP PROBE
(ONE PER WALK-IN)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
NOTE: VERIFY ALL CONNECTIONS
WITH PANEL DIAGRAMS.
DEFROST
HEATER
FAN
DELAY
DOOR SWITCH
TO MF168 INPUT
BOARD
DIGITAL INPUT (DI)
DEFROST
HEATER
FAN
DELAY
FAN
RELAY
FAN
BREAKER
OR
FUSES
FAN
NOTE: VERIFY ALL
CONNECTIONS WITH
CASE WIRING DIAGRAMS.
SWITCH BY E.C.
MOUNT ON UNIT COIL.
NOTE: VERIFY ALL
CONNECTIONS WITH
CASE WIRING DIAGRAMS.
NOTE: VERIFY ALL
PANEL DIAGRAMS.
BREAKER
OR
FUSES
DEFROST
CONTACTOR
DEFROST
RELAY
SYSTEM
SWITCH
DEFROST
LIGHT
PRE-WIRED PANEL LOCATED IN
DEFROST PANEL.
NOTE: VERIFY ALL CONNECTIONS
WITH PANEL DIAGRAMS.
TEMP PROBE FOR
DEFROST TERM.
(ONE PER EVAP COIL)
LOW
VOLTAGE
TEMP PROBE
(ONE PER WALK-IN)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
DEFROST
HEATER
FAN
DELAY
FAN
RELAY FAN
CONTACTOR
FAN
BREAKER
OR
FUSES
NOTE: VERIFY ALL
CASE WIRING DIAGRAMS.
CONNECTIONS WITH
PANEL DIAGRAMS.
NON-ESR VALVE
(AT RACK OR REMOTE
LOCATION)
PRE-WIRED PANEL LOCATED AT
COMPRESSOR RACK.
ESR VALVE
(AT RACK OR REMOTE
LOCATION)
TO ESR
BOARD
NON-ESR VALVE
(AT RACK OR REMOTE
LOCATION)
PRE-WIRED PANEL LOCATED AT
COMPRESSOR RACK.
TO ESR
BOARD
NON-ESR VALVE
(AT RACK OR REMOTE
LOCATION)
ESR VALVE
(AT RACK OR REMOTE
LOCATION)
1 PHASE
DEFROST
DEFROST
HEATER
FAN
DELAY
TO MF168
OUTPUT BOARD
TO MF168
OUTPUT BOARD
TO MF168
OUTPUT BOARD
2 POLE WP SERVICE
SWITCH BY E.C.
MOUNT ON UNIT COIL.
ANTI-SWEAT
HEATER
(IF REQUIRED)
TO CIRCUIT
BREAKER IN
ELECTRICAL PANEL
PRE-WIRED PANEL
LOCATED AT
COMPRESSOR RACK.
LOW
VOLTAGE
TEMP PROBE
(ONE PER CASE)
TO MF168 INPUT
BOARD
ANALOG INPUT (AI)
NOTE: VERIFY ALL
CONNECTIONS WITH
PANEL DIAGRAMS.
TO ESR
BOARD
NON-ESR VALVE
(AT RACK OR REMOTE
LOCATION)
ESR VALVE
(AT RACK OR
REMOTE LOCATION)
TO MF168
OUTPUT BOARD
NOTES:
1. HEAT TRACE CABLE, SELF LIMITING TYP FOR
FREEZER PROTECTION, WITH PARALLEL
CONNECTED HEATER ZONES, 5 WATT/FT., 120V,
SIMILAR AND EQUAL TO RAYCHEM 5XL-1.
VERIFY WITH REFRIGERATION CONTRACTOR
MODEL OF HEAT TRACE TAPE AND
INSTALLATION REQUIREMENTS.
2. 7.9" PITCH WILL REQUIRE 1.2" CABLE/FT. PIPE.
3. INSULATION TO BE INSTALLED BY
REFRIGERATION CONTRACTOR.
4 FOR USE IN ALL FREEZERS AND MEAT
COOLERS.
5 HEAT TRACE TAPE SUPPLIED AND INSTALLED
BY REFRIGERATION CONTRACTOR.
6 REFER TO SPECIFICATIONS FOR TYPICAL
ROUTING.
3/4" INSULATION
TRAP
STANDPIPE
DRAINAGE TUBE
NYLON TIES
TIE WRAP
ICE
CREAM
ICE
CREAM
ICE
CREAM
HEAT TRACE CABLE TO BE
EXTENDED FOR FULL
LENGTH OF DRAIN PIPE
POWER CONNECTION
FLEX CONDUIT (SEE RAYCHEM
INSTALLATION GUIDE).
NEMA 4X VAPOR PROOF
JUNCTION BOX.
FREEZER WALL
RIGID P.V.C. CONDUIT, INSTALL #12
GROUND WIRE WITH OTHER
CONDUCTORS. PACK CONDUIT TIGHTLY
WITH FIBERGLASS INSULATION. SEAL
BOTH ENDS WITH DUCT SEAL.
TO GFCI CIRCUIT BREAKER WITH 30mA
TRIP SETTING (TYPICAL FOR ALL HEAT
TRACE CIRCUITS).
EVAPORATOR
*PLASTIC FLUSH SWITCH BOXES AND PVC CONDUIT INSTALLED
AT FACTORY.
ALL CONDUIT TO BE INSTALLED INSIDE FREEZER.
NOTE:
1 .
FLOOR
FREEZER
DOOR
LIGHTING FIXTURE
MOUNTED INSIDE FREEZER
CONNECT TO DOOR TRIM
HEATER
120V POWER FOR
FREEZER DOOR HEATER
JUNCTION BOX MOUNTED
ON TOP OF FREEZER
* PRESS SWITCH WITH A PRESS
PILOT LIGHT.
FACTORY INSTALLED CONDUIT
CONNECT TO PRESSURE RELIEF
LOUVERS
JUNCTION BOX MOUNTED ON
TOP OF FREEZER
120V POWER SOURCE
INSULATION
DOOR SWITCH\STROBE\HORN
FLOOR
COMPRESSOR
ROOM
FROM HORN/STROBE TO
REFRIGERATION CONTROL
PANEL. SEE SHEET RC101.
VOLTAGE
SURFACE MOUNTED EMC-RLI
24V STROBE LIGHT AND HORN
PROVIDED BY REFRIGERATION
EQUIPMENT MANUFACTURER
AND INSTALLED BY RC.
RIC TO PROVIDE AND INSTALL
PARKER PARAFLEX SERIES FRPE
1/4" SENSING TUBING FROM RLDS
UNIT TO THE END OF THE
REFRIGERATION RACK CLOSEST
TO THE EXHAUST FAN.
FILTER PROVIDED WITH RLDS
UNIT.
CONTACTOR
2 POLE WP SERVICE
CONNECTIONS WITH
DEFROST
INTAKE
HOOD
EXHAUST
FAN
COMPRESSOR
RACK
FLOOR
OR PREP
DOOR
CONNECTIONS WITH
NOTE: VERIFY ALL
NOTE: EC SHALL PROVIDE
JUNCTION BOXES AND
CONDUIT PER DIRECTION OF
THE RC.
FROM DOOR SWITCH
CONTACTS TO EMS CONTROL
SYSTEM. SEE SHEET RC101.
(COOLERS, FREEZERS & PREP
ROOMS)
SURFACE MOUNTED EMC-RLI 24V
STROBE LIGHT AND HORN PROVIDED
BY REFRIGERATION EQUIPMENT
MANUFACTURER AND INSTALLED BY
RC ON PRE-INSTALLED JUNCTION
BOX CENTERED ABOVE DOOR. IF
WALK-IN OR PREP DOOR OPENS OUT
INTO A SPACE VISIBLE TO THE
PUBLIC, EMC-RLI UNIT TO BE
INSTALLED INSIDE WALK-IN/PREP
ROOM.
(FREEZERS ONLY)
SURFACE MOUNTED EMC-DMA 120V
COMBINATION DOOR
SWITCH\STROBE LIGHT AND HORN
PROVIDED BY REFRIGERATION
EQUIPMENT MANUFACTURER AND
INSTALLED BY EC.
WALK-IN
FROM HORN/STROBE TO
REFRIGERATION CONTROL
PANEL. SEE SHEET RC101.
RIC TO PROVIDE AND INSTALL
PARKER PARAFLEX SERIES FRPE
1/4" SENSING TUBING FROM RLDS
UNIT, THROUGH CONDUIT PRE
INSTALLED IN WALL OF THE
WALK-IN OR PREP ROOM.
FILTER PROVIDED WITH RLDS
UNIT AND SHALL BE LOCATED IN
PRE INSTALLED 4"X4" BOX.
PROVIDE
SEALANT
PIPING
GOOSENECK
REFRIG
INTAKE LINE FILTER
PROVIDED WITH
RLDS UNIT.
RIC TO PROVIDE AND INSTALL PARKER PARAFLEX
SERIES FRPE 1/4" SENSING TUBING FROM RLDS UNIT
UP THROUGH REFRIGERATION PIPING GOOSENECK
FOR RLDS INTAKE AND EXHAUST. SEE NOTE 7 ON
RC101.
12/08/2021
02/07/22