PROJECT NO.
SHEET TITLE
ISSUES & REVISIONS
DRAWN BY:
PROFESSIONAL SEAL
PROJECT MANAGER:
DOCUMENT DATE:
CHECKED BY:
PROJECT NAME
PROJECT ADDRESS
1 2 3 4 5 ABCDEABCDE12 3 4 5
8131 METCALF AVENUE
SUITE 300
OVERLAND PARK, KS 66204
www.brrarch.com
TEL: 913-262-9095
FAX: 913-262-9044
ARCHITECT OF RECORD:
62930563
12/07/2021
THE FRESH
MARKET
The Centre Retail Center
NO. DATE DESCRIPTION
An Erdman Anthony Company
552 Fort Evans RD STE 200
Leesburg, VA 20176
703.777.5988
Leesburg@erdmananthony.com
116th St. and Rangeline Rd.
Carmel, Indiana
MECHANICAL
NOTES AND
SCHEDULES
M101
SEE BOOK SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
1. Materials, equipment, and systems shall meet all pertinent requirements of the Underwriters Laboratory (UL), the 2012
International Mechanical Code with Indiana Amendments, the Indiana Energy Conservation Code, the 2006 International
Plumbing Code with Indiana Amendments, the American Society of Heating, Refrigeration and Air-Conditioning Engineers
(ASHRAE), Sheet Metal and Air Conditioning Contractors National Association (SMACNA), American Gas Association (AGA),
National Fire Protection Association (NFPA), and other nationally recognized agencies as well as applicable local codes.
2. Bidders shall be licensed contractors in accordance with local and state laws.
3. Bidders shall thoroughly acquaint themselves with the conditions under which the work is to be performed. They shall
examine all services, equipment, surfaces, etc., which this work is in any way dependent upon, and bring any discrepancies
determined or omissions found in the drawings to the owner's attention before submitting bid. Verify all dimensions by field
measurements.
4. The systems shown on the drawings shall be provided to serve all fixtures, equipment, and areas within the Contract Limit
Lines as set forth by the Architectural solution for the project. The bidding and contract requirements, general requirements,
and general provisions shall apply to this section. Systems shall include all equipment, appurtenances, safety devices, and
controls necessary for the intended service.
5. All permits and fees required for this work shall be secured and paid for by the mechanical contractor and included in bid
price.
6. Anything drawn or specified on these plans shall not be construed to conflict with any local, municipal or state law, regulation
or ordinance which governs the installation of any mechanical or related work. Where any portion of the systems is not
installed as in accordance with applicable laws, ordinances, regulations and codes, this contractor shall make all changes
required by the enforcing authorities in a manner approved by the owner and without additional cost to the owner. Where
plan requirements are more stringent than code, the installation shall be in accordance with the plans.
7. Where job conditions require changes from the contract documents that do not change the scope of installation or nature of
work required, the contractor shall make such changes without additional cost to the owner. No other changes may be made
without written permission of the owner.
8. All equipment shall be new and unused, UON, and shall bear the label of an approved agency. All equipment shall be
installed in strict conformance to manufacturer's instructions, except where these specifications require a higher quality
installation than recommended by manufacturer. All mechanical equipment shall be provided with installation instructions,
which shall be made available at the job site.
9. All installed systems, devices and related items shall be tested in place on site. Replace any and all defective devices, items
or systems at contractor's own expense before completion of the project.
10. Contractor shall guarantee all work for which materials are furnished, fabricated or field erected, all factory assembled
equipment for which no specific manufacturer's guarantee is furnished, and all work in connection with installing
manufacturer's guaranteed equipment. This contractor's guarantee shall exist for a period of one (1) year from the date of
final owner acceptance of the work and shall apply to defects in material and to defective workmanship of any kind.
11. Contractor shall replace at contractor's own expense any contractor-supplied materials, equipment, and related items that fail
or are found to be defective within the guarantee period.
12. Arrange for chases, slots, and openings in other building components to allow for mechanical installations. Coordinate the
installation of required supporting devices and sleeves to be set in poured in place concrete and other structural components,
as they are constructed. Coordinate the cutting and patching of building components to accommodate installation of
mechanical equipment and materials.
13. Sequence, coordinate, and integrate installations of mechanical materials and equipment for efficient flow of the Work. Give
particular attention to large equipment requiring positioning prior to closing-in the building.
14. Coordinate mechanical equipment and materials installation with other building components. Coordinate the installation of
mechanical materials and equipment above ceilings with suspension system, light fixtures, and other installations.
15. Equipment locations, roof & wall openings are approximate: verify size and coordinate with G.C., equipment supplier, and
owner. Provide steel framing around roof opening(s) where required and around wall opening(s) where required.
16. Do not endanger or damage installed Work through procedures and processes of cutting and patching. Arrange for repairs
required to restore other work, because of damage caused as a result of mechanical installations.
17. Where mounting heights are not detailed or dimensioned, install mechanical services and overhead equipment to provide the
maximum headroom possible.
18. Install mechanical equipment to facilitate maintenance and repair or replacement of equipment components. As much as
practical, connect equipment for ease of disconnecting, with minimum of interference with other installations.
19. For all air systems: adjust fans, supply register dampers, and duct volume dampers as needed to balance all systems to
match listed airflows, and provide a written summary report. Summary report shall include design, preliminary and final
airflow data, and shall include a list of deficiencies. Air balancing shall be provided by TFM and shall be performed by an
independent AABC or NEBB certified firm. Mechanical contractor shall assist the test & balance agent as required to make
changes in pulleys, belts and dampers or provide additional dampers as required for proper system balance, at no additional
cost to TFM.
20. The entire installation, including the gauges of ductwork, shall be in strict compliance with SMACNA standards, except where
these specifications require a stricter installation standard. System is 1" pressure class, UON. All ducts shall be sealed to
meet SMACNA Class B requirements minimum, and shall be supported at intervals not exceeding 10'. Sealant shall comply
with U.L. Standard 181.
21. All 90 degree turns in supply and return ductwork shall be mitered elbows with turning vanes at 2" spacing extended in the
direction of airflow, or smooth radius elbows with a radius-to-width ratio of 1.0 or greater. Mitered elbows without turning
vanes, square-throat radiused-heel elbows, and radiused-throat square-heel elbows are NOT acceptable. All duct transitions
shall be smooth (30 degree taper maximum), not abrupt.
22. Refer to the project specifications for complete and detailed duct, fitting, joint connection, hanging, and insulation
requirements. In general:
a.All exposed supply and return round or flat oval spiral ductwork and fittings in the sales area shall be uninsulated.
Exposed rectangular return duct at HVAC unit connection transitions shall be single wall with 6ft of anti-microbial internal
duct liner measured from the unit.
b.All supply and return rectangular ductwork and fittings exposed shall be single wall uninsulated unless otherwise noted.
c.All supply and return ductwork and fittings concealed above ceilings and/or in back areas shall be single wall with R-4.2
external wrap insulation.
d.All supply and return ductwork above the roof shall be single wall with minimum R-8 internal duct liner and Alumaguard
60 waterproofing and vapor barrier exterior insulation membrane.
23. Duct smoke detectors and accessories shall be UL tested and listed. Equipment and installation shall meet all pertinent
requirements of the mechanical code and NFPA 72. Duct smoke detectors located more than 10 ft above the finished floor,
or located such that the detector's alarm indicator is not visible to responding personnel, shall be provided with remote alarm
indicators. Each remote indicator shall be clearly labeled as to function and air handling unit served, with an acrylic engraved
nameplate.
24. All curtain-type fire dampers shall be UL 555 listed and dynamic rated, except that static rated fire dampers shall be
permitted where the air handling system is automatically shut down in the event of fire. Provide and install duct access panel
with acrylic engraved nameplate for each fire damper.
25. All diffusers and grilles shall be factory finished white, unless otherwise noted.
26. All mechanical equipment shall have vibration isolators, as well as flexible duct connectors. Flexible connectors shall be UL
181 tested and labeled, and shall not exceed 14' in length. Mechanical fasteners and sealants shall be used to connect ducts
to mechanical equipment.
27. All duct coverings, linings, tape and vibration isolation connectors shall have a maximum flame spread rating of 25, and a
maximum smoke generation rating of 50.
28. All duct dimensions listed on plans are inside clear dimensions.
29. Flexible ducts shall not exceed 5' in length, nor shall they be installed where they must be flattened. Flexible ducts shall be
UL 181 tested and labeled, and must be fastened per SMACNA standards. If job conditions do not permit proper installation
of flexible duct, rectangular galvanized steel duct with equal free area shall be used instead. Flexible ducts shall not be used
above drywall or plaster ceilings.
30. Provide volume dampers at each branch off of a trunk duct to a supply diffuser.
31. All air handlers, condensers, control devices and other mechanical apparatus shall be clearly marked for easy identification
and safety. Use black plastic or bakelite name plate engraved with white letters 1/4" high. Punched tape is not acceptable.
32. Mechanical contractor shall furnish record set of drawings with any deviations marked in red ink.
33. Mechanical contractor shall coordinate the start-up of all HVAC equipment.
34. Mechanical contractor shall furnish manuals for all new equipment, including, at a minimum: equipment input and output
capacity and required maintenance actions, O&M manuals, controls maintenance and calibration information (including wiring
diagrams and controls set points), and a complete written narrative of how each system is intended to operate.
35. ALL submittals MUST be sent in pdf format, highlighted or redlined to indicate equipment ID from schedules, model number,
performance data, electrical data, dimensions, weights, options and accessories, and shall be emailed to files@dwyer.com
and cc:ing the Architect.
Ducts and associated fans and hoods shown on hood drawings, see Food Service plans for details on the hoods. Comply
with the International Mechanical Code and with NFPA 96, "Standard for Installation of Equipment for the Removal of
Smoke and Grease Laden Vapors for Commercial Cooking Equipment.
Main cookline exhaust ducts shall be either factory assembled Captive Aire DW series with zero clearance to combustibles,
or 16-ga, welded carbon steel where concealed and 18 ga, welded stainless steel where exposed. All grease exhaust
ducts from hood to 18" above the roof insulation at the fan shall be wrapped with two layers of 3M Fire Barrier Duct Wrap
615+, providing zero clearance to combustibles.
Prior to use, concealment or wrapping of any portion of a grease duct system, a leakage test in the form of a light test or
other approved method shall be performed in the presence of the code official.
Provide and install sloping duct at 1/4" per foot with UL listed 16 ga grease duct access doors cleanouts as required by
code. Where access doors are located on the bottom of the duct, provide and install gasket and internal damming as
required by IMC 506.3.9. Provide and install a permanent sign for each access door "ACCESS PANEL. DO NOT
OBSTRUCT".
Combustible materials shall be kept a minimum of 18" off of hood surfaces.
1
T Thermostat
of flow and located 2" on center
Turning vanes, extended in direction
Louver, size as indicated12/6
L
Supply diffuser, CFM as noted
Galvanized steel rectangular duct
1st number is side shown [in inches]
Round flexible duct, size in inches
Manual volume damper
Duct section down, negative pressure
Duct section down, positive pressure
Duct section up, negative pressure
Duct section up, positive pressure
Return or exhaust grille, CFM as noted
275
CD
275
CG
4"
12/6
MC Mechanical Contractor
Ceiling Diffuser
Numbered Note
Ceiling Grille
Plumbing Contractor
Electrical Contractor
General Contractor
CD
CG
PC
EC
GC
Unless otherwise notedUON
EF Exhaust Fan
OA Outside Air
SD Duct Smoke DetectorAir Handling UnitAHU
AFF Above Finished Floor
CA Combustion Air
Condensing UnitCU
HSG High Sidewall Grille
Electric HeaterHTR
HSR High Sidewall Register
SDR Spiral Duct Register
AD Air Door
H
ACC Air Cooled Condenser
S
Galvanized steel flat oval duct
1st number is side shown [in inches]12/6 Ø
Galvanized steel round duct6" Ø
Fan Coil UnitFC
Ductless Split outdoor unitDS
Rooftop HVAC UnitRTU
T H Heating Only thermostat
MD Motorized Damper
Point of connection to
equipment provided and
installed by landlord
UIJ Up In Joists
Humidity sensor,
+72"AFF UON
Temperature sensor,
+72"AFF UON
IH Intake Hood
TFM The Fresh Market
Sidewall register
NOTES:
1) Calculations performed using Carrier's Hourly Analysis Program v5.1, in accordance with the Indiana Energy Conservation Code.
2) RTU-1 is sized for ASHRAE 0.4% dehumidification design point (83.7°F db/77.5°F wb). All other systems are sized for ASHRAE 0.4% cooling design point (91.3°F db/75.0°F
wb). Based on ASHRAE values from Palm Beach International Airport.
3) Systems are selected for cooling or dehumidification. Heating capacities are smallest available above minimum heating requirements.
RTU-1
Zone Description Zone Area Area OA Area OA Occupant Occupant Occupant Occupant Breathing Zone Air Zone Zone OA Zone Vent
Rate Load Rate Load OA Rate OA Zone OA Dist Eff OA Supply Air Fraction Efficiency
Az Ra Az x Ra Pz Rp Rp x Pz Vbz Ez Voz Vpz Zp Evz
(sq.ft.) (cfm/sq.ft.) (cfm) (ppl/1000 sf) (people) (cfm/pers) (cfm) (cfm) (cfm) (cfm)
Supermarket 15104 0.06 906 8 150 7.5 1125 2031 0.8 2539 10400 0.244 0.925
Market Square 1021 0.06 61 8 9 7.5 68 129 0.8 161 1800 0.089 1.079
Corridor 232 0.06 14 0 0 0 0 14 0.8 17 150 0.116 1.053
Instacart 86.5 0.06 5 5 1 5 5 10 0.8 13 500 0.025 1.143
Public Restrooms 131 0 0 0 0 0 0 0 0.8 0 100 0.000 1.169
FE Office 113 0.06 7 5 1 5 5 12 0.8 15 50 0.295 0.874
TOTAL 16687.5 993 161 1203 2196 2745 13000 0.295 0.874
Occupant Diversity D 1.00
Uncorrected OA Vou 2196 D x ∑ all zones RpPz + ∑ all zones AzRa
Average OA Fraction Xs 0.169 Per ASHRAE 62.1-2010 Appendix A
Ventilation Efficiency Ev 0.87 From 62.1-2016 Appendix A equation A-3, or 0.86 from Table 403.3.2.3.2
Ventilation Eff. Used Ev 0.87 Select the largest of the two Ev values above
TOTAL REQUIRED OA Vot 2511 cfm
RTU-2
Zone Description Zone Area Area OA Area OA Occupant Occupant Occupant Occupant Breathing Zone Air Zone Zone OA Zone Vent
Rate Load Rate Load OA Rate OA Zone OA Dist Eff OA Supply Air Fraction Efficiency
Az Ra Az x Ra Pz Rp Rp x Pz Vbz Ez Voz Vpz Zp Evz
(sq.ft.) (cfm/sq.ft.) (cfm) (ppl/1000 sf) (people) (cfm/pers) (cfm) (cfm) (cfm) (cfm)
Break Room 307 0.12 37 0 0 0 0 37 0.8 46 400 0.115 0.959
Wellness Room 63 0.06 4 5 1 5 5 9 0.8 11 175 0.063 1.011
Emp Restrooms 107 0 0 0 0 0 0 0 0.8 0 100 0.000 1.074
Employee Corridor 116 0.06 7 5 1 5 5 12 0.8 15 75 0.199 0.874
BOH 514 0.06 31 0 0 0 0 31 0.8 39 450 0.086 0.988
TOTAL 1107 78 2 10 88 111 1200 0.199 0.874
Occupant Diversity D 1.00
Uncorrected OA Vou 88 D x ∑ all zones RpPz + ∑ all zones AzRa
Average OA Fraction Xs 0.074 Per ASHRAE 62.1-2010 Appendix A
Ventilation Efficiency Ev 0.87 From 62.1-2016 Appendix A equation A-3, or 0.95 from Table 403.3.2.3.2
Ventilation Eff. Used Ev 0.95 Select the largest of the two Ev values above
TOTAL REQUIRED OA Vot 93 cfm
RTU-3
Zone Description Zone Area Area OA Area OA Occupant Occupant Occupant Occupant Breathing Zone Air Zone Zone OA Zone Vent
Rate Load Rate Load OA Rate OA Zone OA Dist Eff OA Supply Air Fraction Efficiency
Az Ra Az x Ra Pz Rp Rp x Pz Vbz Ez Voz Vpz Zp Evz
(sq.ft.) (cfm/sq.ft.) (cfm) (ppl/1000 sf) (people) (cfm/pers) (cfm) (cfm) (cfm) (cfm)
Scullery 135 0.06 8 5 1 5 5 13 0.8 16 200 0.082 1.016
BOH 1254 0.06 75 0 0 0 0 75 0.8 94 950 0.099 0.999
Receiving 816 0.12 98 0 0 0 0 98 0.8 122 750 0.163 0.934
BOH Corridor 801 0.06 48 0 0 0 0 48 0.8 60 500 0.120 0.977
TOTAL 3006 229 1 5 234 293 2400 0.163 0.934
Occupant Diversity D 1.00
Uncorrected OA Vou 234 D x ∑ all zones RpPz + ∑ all zones AzRa
Average OA Fraction Xs 0.098 Per ASHRAE 62.1-2010 Appendix A
Ventilation Efficiency Ev 0.93 From 62.1-2016 Appendix A equation A-3, or 0.99 from Table 403.3.2.3.2
Ventilation Eff. Used Ev 0.99 Select the largest of the two Ev values above
TOTAL REQUIRED OA Vot 237 cfm
Zone Description Zone Area Exhaust Min Exhaust
Rate Exhaust Provided
(sq.ft.) (cfm/sq.ft.) (cfm) (cfm)
Kitchen 221 0.7 155 2160
Bakery Prep 445 0.7 312 900
Notes
1 Bakery Prep (RTU-4) and Kitchen (RTU-5) are kitchen/cooking use per 2012 International Mechanical Code, and require no outside air.
2 Vestibule (RTU-6) requires no outside air. Vestibule meets the requirements for natural ventilation per 2012 International Mechanical
Code. 80 sq.ft. of operable doors for the 501 sq.ft. vestibule is equivalent to 15.9% of the floor area being ventilated.
RTU-1 COOLING HEATING RTU-2 COOLING HEATING RTU-3 COOLING HEATING
Outdoors 83.7°F/77.5°F 2.6°F Outdoors 91.3°F/75.0°F 2.6°F Outdoors 91.3°F/75.0°F 2.6°F
Dehumidification Temp Indoors 75 F, 50% RH 70 F Indoors 75 F, 50% RH 70 F
Indoors 75 F, 50% RH 70°F Sensible Latent Sensible Sensible Latent Sensible
Sensible Latent Sensible ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr)ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr)
ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 0 ft² 0 -- Window & Skylight Solar Loads 100 ft² 4245 - -
Window & Skylight Solar Loads 1161 ft² 50461 - - Wall Transmission 1066 ft² 6646 - 14398 Wall Transmission 4627 ft² 16340 - 38788
Wall Transmission 4166 ft² 6998 - 17753 Roof Transmission 1188 ft² 3796 - 3935 Roof Transmission 5507 ft² 17610 - 18239
Roof Transmission 17038 ft² 49455 - 56430 Window Transmission 0 ft² 0 -0 Window Transmission 100 ft² 731 - 3862
Window Transmission 1161 ft² 3524 - 44690 Skylight Transmission 0 ft² 0 - 0 Skylight Transmission 0 ft² 0 - 0
Skylight Transmission 0 ft² 0 -0 Door Loads 42 ft² 161 - 849 Door Loads 21 ft² 332 - 613
Door Loads 0 ft² 0 - 0 Floor Transmission 1188 ft² 0 - 3541 Floor Transmission 5507 ft² 0 - 15803
Floor Transmission 17038 ft² 0 - 17051 Partitions 0 ft² 0 -0 Partitions 0 ft² 0 -0
Partitions 0 ft² 0 -0 Ceiling 0 ft² 0 -0 Ceiling 0 ft² 0 -0
Ceiling 0 ft² 0 - 0 Overhead Lighting 1627 W 5550 - 0 Overhead Lighting 7023 W 23960 -0
Overhead Lighting 9956 W 33969 - 0 Task Lighting 0 W 0 - 0 Task Lighting 0 W 0 -0
Task Lighting 0 W 0 - 0 Electric Equipment 578 W 1972 - 0 Electric Equipment 2326 W 7935 -0
Electric Equipment 9144 W 31197 - 0 People 7 1750 1500 0 People 13 3535 3315 0
People 158 44204 42595 0 Infiltration - 608 770 2604 Infiltration - 2531 4313 10842
Infiltration - 0 0 0 Miscellaneous -0 0 0 Miscellaneous - 500 0 0
Miscellaneous - 27793 6840 0 Safety Factor 0% / 0% 0 0 0 Safety Factor 0% / 0% 0 0 0
Safety Factor 0% / 0% 0 0 0 >> Total Zone Loads - 20483 2270 25327 >> Total Zone Loads - 77719 7628 88147
>> Total Zone Loads - 247601 49435 135924 Zone Conditioning - 19655 2270 24852 Zone Conditioning - 72122 7628 66142
Zone Conditioning - 246245 49435 132122 Plenum Wall Load 0%0 - 0 Plenum Wall Load 0%0 -0
Plenum Wall Load 0%0 - 0 Plenum Roof Load 0%0 - 0 Plenum Roof Load 0%0 -0
Plenum Roof Load 0%0 - 0 Plenum Lighting Load 0%0 - 0 Plenum Lighting Load 0%0 -0
Plenum Lighting Load 0%0 - 0 Return Fan Load 1200 CFM 0 -0 Return Fan Load 2400 CFM 0 -0
Return Fan Load 13000 CFM 0 -0 Ventilation Load 100 CFM 1530 2091 6941 Ventilation Load 200 CFM 2994 5624 11705
Ventilation Load 4400 CFM 36606 199138 306484 Supply Fan Load 1200 CFM 667 - -667 Supply Fan Load 2400 CFM 1779 - -1779
Supply Fan Load 13000 CFM 14456 - -14456 Space Fan Coil Fans - 0 - 0 Space Fan Coil Fans - 0 - 0
Space Fan Coil Fans - 0 - 0 Duct Heat Gain / Loss 2% 410 - 507 Duct Heat Gain / Loss 2% 1034 - 2283
Duct Heat Gain / Loss 2% 3170 - 4550 >> Total System Loads - 22262 4361 31633 >> Total System Loads - 77929 13252 78351
>> Total System Loads - 300477 248573 428700 Central Cooling Coil - 22262 4361 0 Central Cooling Coil - 77929 13252 0
Central Cooling Coil - 388811 248573 0 Central Heating Coil - 0 - 31633 Central Heating Coil - 0 - 78351
Central Heating Coil - -88333 - 428700 >> Total Conditioning - 22262 4361 31633 >> Total Conditioning - 77929 13252 78351
>> Total Conditioning - 300478 248573 428700
Refrigerated case effects 0 0 0 Refrigerated case effects -26000 -8000 26000
Refrigerated case effects -91560 -39240 91560 Total Zone Conditioning 19655 2270 24852 Total Zone Conditioning 46122 -372 92142
Total Zone Conditioning 154685 10195 223682 System level loads 2607 2091 6781 System level loads 5807 5624 12209
System level loads 142565 199138 296578
Total System Loads 22262 4361 31633 Total System Loads 51929 5252 104351
Total System Loads 297250 209333 520260
Total Cooling Required 2.2 Tons Total Cooling Required 4.8 Tons
Total Cooling Required 42.2 Tons Total Heating Required 31.6 MBH Total Heating Required 104.4 MBH
Total Heating Required 520 MBH
Total Heat Reclaim Available EST. 390 MBH
RTU-4 COOLING HEATING RTU-5 COOLING HEATING RTU-6 COOLING HEATING
Outdoors 91.3°F/75.0°F 2.6°F Outdoors 91.3°F/75.0°F 2.6°F Outdoors 91.3°F/75.0°F 2.6°F
Indoors 75 F, 50% RH 70 F Indoors 75 F, 50% RH 70 F Indoors 75 F, 50% RH 70 F
Sensible Latent Sensible Sensible Latent Sensible Sensible Latent Sensible
ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr)ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr) ZONE LOADS Details (BTU/hr) (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft²0 - - Window & Skylight Solar Loads 0 ft² 0 - - Window & Skylight Solar Loads 600 ft² 39897 - -
Wall Transmission 0 ft²0 -0 Wall Transmission 0 ft² 0 - 0 Wall Transmission 1648 ft² 972 - 4503
Roof Transmission 462 ft² 1391 - 1530 Roof Transmission 251 ft² 86 - 831 Roof Transmission 572 ft² 1416 - 1894
Window Transmission 0 ft² 0 -0 Window Transmission 0 ft² 0 - 0 Window Transmission 600 ft² 1577 - 21535
Skylight Transmission 0 ft² 0 -0 Skylight Transmission 0 ft² 0 - 0 Skylight Transmission 0 ft² 0 - 0
Door Loads 0 ft² 0 -0 Door Loads 0 ft² 0 - 0 Door Loads 24 ft² 36 - 485
Floor Transmission 462 ft² 0 -0 Floor Transmission 251 ft² 0 - 1049 Floor Transmission 572 ft² 0 - 3163
Partitions 0 ft² 0 -0 Partitions 0 ft² 0 - 0 Partitions 0 ft² 0 -0
Ceiling 0 ft² 0 -0 Ceiling 0 ft² 0 - 0 Ceiling 0 ft² 0 -0
Overhead Lighting 601 W 2049 - 0 Overhead Lighting 251 W 856 - 0 Overhead Lighting 429 W 976 -0
Task Lighting 0 W 0 - 0 Task Lighting 0 W 0 - 0 Task Lighting 0 W 0 -0
Electric Equipment 231 W 788 - 0 Electric Equipment 251 W 856 - 0 Electric Equipment 0 W 0 -0
People 3 840 810 0 People 4 1120 1080 0 People 5 1400 1350 0
Infiltration - 0 0 0 Infiltration - 1710 2274 7657 Infiltration - 686 2861 8087
Miscellaneous - 8298 294 0 Miscellaneous - 12491 0 0 Miscellaneous -0 0 0
Safety Factor 0% / 0% 0 0 0 Safety Factor 0% / 0% 0 0 0 Safety Factor 0% / 0%0 0 0
>> Total Zone Loads - 13366 1104 1530 >> Total Zone Loads - 17119 3354 9537 >> Total Zone Loads - 46960 4211 39667
Zone Conditioning - 12865 1104 1557 Zone Conditioning - 15694 3354 4319 Zone Conditioning - 42955 4211 39241
Plenum Wall Load 0%0 - 0 Plenum Wall Load 0% 0 - 0 Plenum Wall Load 0%0 -0
Plenum Roof Load 0%0 - 0 Plenum Roof Load 0% 0 - 0 Plenum Roof Load 0%0 -0
Plenum Lighting Load 0%0 - 0 Plenum Lighting Load 0% 0 - 0 Plenum Lighting Load 0%0 -0
Return Fan Load 1050 CFM 0 - 0 Return Fan Load 1200 CFM 0 - 0 Return Fan Load 2000 CFM 0 -0
Ventilation Load 0 CFM 0 0 0 Ventilation Load 0 CFM 0 0 0 Ventilation Load 200 CFM 470 5001 13932
Supply Fan Load 1050 CFM 778 - -778 Supply Fan Load 1200 CFM 890 - -890 Supply Fan Load 2000 CFM 1186 - -1186
Space Fan Coil Fans - 0 -0 Space Fan Coil Fans - 0 - 0 Space Fan Coil Fans - 0 -0
Duct Heat Gain / Loss 0% 0 - 0 Duct Heat Gain / Loss 0% 0 - 0 Duct Heat Gain / Loss 0% 0 -0
>> Total System Loads - 13643 1104 779 >> Total System Loads - 16584 3354 3429 >> Total System Loads - 44611 9212 51987
Central Cooling Coil - 18719 1104 0 Central Cooling Coil - 24862 3354 0 Central Cooling Coil - 44611 9212 0
Central Heating Coil - -5075 - 779 Central Heating Coil - -8278 - 3429 Central Heating Coil - 0 - 51987
>> Total Conditioning - 13644 1104 779 >> Total Conditioning - 16584 3354 3429 >> Total Conditioning - 44611 9212 51987
Refrigerated case effects -1190 -510 1190 Refrigerated case effects -4500 -2000 4500 Refrigerated case effects 0 0 0
Total Zone Conditioning 11675 594 2747 Total Zone Conditioning 11194 1354 8819 Total Zone Conditioning 42955 4211 39241
System level loads 5853 0 -778 System level loads 9168 0 -890 System level loads 1656 5001 12746
Total System Loads 17528 594 1969 Total System Loads 20362 1354 7929 Total System Loads 44611 9212 51987
Total Cooling Required 1.5 Tons Total Cooling Required 1.8 Tons Total Cooling Required 4.5 Tons
Total Heating Required 2.0 MBH Total Heating Required 7.9 MBH Total Heating Required 52.0 MBH
12/08/2021
Digitally signed by Justin Litz
02/07/22