CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on: January 4, 2022
Project number Release date
426429 01/04/22
Construction type Occupancy classification
Scope of release
*SEE BELOW *SEE BELOW
Type of release
Project name
Street address
City County
ARCH
STR
Standard
Republic Airways Training Center & Hotel
12195 N Meridian St
CARMEL HAMILTON
To: Owner / Architect / Engineer
RATIO Design. LLC
William A Browne AR00034154
101 South Pennslyvania Street
Indianapolis IN 46204
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
14B
4G0412AE
4G0603AE
4G0603AF
14W1104A
14B1100HC
4G0603AR
**
CONSTRUCTION TYPE / OCCUPANCY:
Existing Hotel - II-B / R1, A2, EXST
Addition (Podium) - I-A / A-3, B
Addition (Hotel) - II-B / R-2
Training Center - II-B / B
**
This project has been reviewed under the 2014 Indiana Building Code.
The proposed building, addition, or remodel shall not put the existing building in noncompliance or
into further noncompliance in accordance with 675 IAC 12-4-12.
Detailed plans and specifications of the fire suppression system shall be filed with the required
application and appropriate fees in accordance with 675 IAC 12-6-3(a), 675 IAC 12-6-7(g)(17), and
675 IAC 13-1-8. (N.F.P.A. 13)
Detailed plans and specifications for the revised fire suppression system shall be filed with the
required application and appropriate fees in accordance with 675 IAC 12-6- 3(a), 675 IAC 12-6-
7(g)(17), and 675 IAC 13-1-8. (N.F.P.A. 13) NOTE: Applicable to existing hotel.
Required means of egress shall be maintained during construction and demolition, remodeling or
alterations and additions to any building, in accordance with Section 1104, IFC (675 IAC 22-2.5).
The current code for handicapped accessibility in use in the State of Indiana is Chapter 11 of the
Indiana Building Code (675 IAC 13-2.6) and ICC standard A117.1, 2009 edition (675 IAC 13-2.6).
This release does not include all scopes of construction work. Plans and specifications for adding
or remodeling other systems shall be filed as a new project or as one or more partials before
commencing work in accordance with 675 IAC 12-6-3.
Indiana Department of Homeland Security
DIVISION OF FIRE & BUILDING SAFETY
PLAN REVIEW DIVISION
402 W. Washington St., Room E245
Indianapolis, IN 46204
Fax & e-mail:
SUPPORT HOOSIER SAFETY
Available At Your Local Licence Branch
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
3176334153, wbrowne@ratiodesign.com
02/23/22
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 2/3
14B07061B
14B07037
14B07113B
14B0404
4G0603AK
14B071727
14B09072111
14B10162
A2
14B090331114
14B10186
14B10201
14B07165A
14B1008198
14B05042
One or more fire walls are being provided for the purpose of allowable area and minimum
construction type in accordance with Section 706.1, IBC (675 IAC 13-2.6).
NOTE: Fire wall continuity shall be in accordance with Sections 706.5 and 706.6, IBC.
Fire walls and vertical fire barriers shall be effectively and permanently identified with signs or
stenciling. Such identification shall: 1. Be located in accessible concealed floor, floor-ceiling or attic
spaces; 2. Be located within 15 feet of the end of each wall and at intervals not exceeding 30 feet
measured horizontally along the wall or partition; and 3. Include lettering not less than 3 inches in
height with a minimum 3/8 inch stroke in a contrasting color incorporating the suggested wording,
"FIRE WALL or FIRE BARRIER PROTECT ALL OPENINGS" or similar wording in accordance with
Section 703.7, IBC (675 IAC 13-2.6).
Floor assemblies separating mixed occupancies shall be in accordance with Section 711.3, IBC
(675 IAC 13-2.6).
NOTE: Pedestrian walkways shall meet the construction, separation and design parameters in
accordance with Section 3104, IBC.
Atriums shall be designed and constructed in accordance with Section 404, IBC (675 IAC 13-2.6).
NOTE: Enclosure of atrium shall comply with Section 404.6 IBC.
This release does not include the required fire alarm system installation. Plans and specifications for
adding or remodeling this system shall be filed as a new project or as a partial before commencing
work, in accordance with 675 IAC 12-6-3.
Fire dampers, smoke dampers, combination fire/smoke dampers, and ceiling radiation dampers
shall be provided in accordance with Section 717.2 through Section 717.7, IBC (675 IAC 13-2.6).
Smoke alarms shall be installed in Group R-1 occupancies in accordance with Section 907.2.11.1,
IBC (675 IAC 13-2.6).
NOTE: Atriums connecting more than two stories shall be provided a fire alarm system including
smoke detection thoughout the atrium, system acivated in accordance with Section 907.5, per
Section 907.2.14 IFC.
Exit access travel distance shall be in accordance with Table 1016.2, IBC (675 IAC 13-2.6).
NOTE: Travel distance shall comply with Section 404.9 IBC with regard to atrium.
An elevator installation permit shall be obtained from the Elevator Safety Division in accordance with
IESC (675 IAC 21-1-1). Please visit: http://www.in.gov/dhs/2374.htm
Non-sprinklered elevator equipment rooms and hoistways in used exclusively for the operation of
elevators and that are separated from the remainder of the building by two (2) hour fire-resistive
construction. Penetrations between machine rooms and hoistways necessary for the safe operation
of an elevator, and vents required by Section 3004 of this code need not be fire-rated in accordance
with Section 903.3.1.1.1.4, IBC (675 IAC 13-2.6).
Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be
interrupted by intervening rooms in accordance with Section 1018.6, IBC (675 IAC 13-2.6).
Once a given level of exit protection is achieved, such level of exit protection shall not be reduced
until arrival at the exit discharge, in accordance with Section 1020.1, IBC (675 IAC 13-2.6).
Openings in fire walls shall be protected assemblies in accordance with Section 716.5 and Table
716.5, IBC (675 IAC 13-2.6).
Entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1
or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2,
are permitted to be equipped with an approved entrance and egress access control system, listed in
accordance with UL 294, which shall be installed and operate in accordance with items 1 through 6,
in accordance with Section 1008.1.9.8, IBC (675 IAC 13-2.6).
Sprinklers are being provided for this project to increase the number of story levels or 20 feet above
Table 503 in accordance with Section 504.2, IBC (675 IAC 13-2.6).
NOTE: Proposed design includes a single story below podium / horizontal separation, in
02/23/22
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 3/3
4G05A
4G05
AREL
accordance with Section 510.2. No portion of this project shall exceed six stories. The proposed
building shall comply with conditions of Section 510.2 regarding horizontal building separation
allowance.
The Fire Prevention and Building Safety Commission has granted one or more variances which
apply to this project. 21-12-62. (2014 IBC 1027.1)
All conditions set forth by the Indiana Fire Prevention and Building Safety Commission on variance
submissions shall be considered part of the release documents and do not apply to future additions
or alterations of this structure in accordance with 675 IAC l2-5.
Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from
required compliance with all applicable rules of the commission, even if noncompliant conditions
appear in the plans and specifications that have been filed with the division. The owner is
responsible for correcting any and all areas of noncompliance even if they are discovered
subsequent to the issuing of this design release.
This order is effective upon service. If you would like to request informal review of this order, please complete the informal review form located at
https://www.in.gov/dhs/4149.htm. Following receipt of this form, the Department may modify or reverse the order, however, a request for an informal
review does not extend the deadline for filing a petition for review with the Fire Prevention and Building Safety Commission (Commission).
Additionally, if you have any questions regarding this order, you may contact that Department at (317) 232-2222.
If you desire a formal administrative review of this order by the Commission, you must comply with the requirements of Indiana Code § 4-21.5-3-7
and file a written petition for review within 15 days of the date this order was served, however, this period is extended to 18 days if service is made by
mail. Your petition for review must state facts demonstrating that you are: (1) a person to whom the order is specifically directed; (2) aggrieved or
adversely affected by the order; or (3) entitled to review under any law. You may submit your petition by the following methods:
U.S. MAIL OR PERSONAL SERVICE ONLINE
Fire Prevention and Building Safety Commission By completing the form at
c/o Legal Counsel https://www.in.gov/dhs/4148.htm
302 W. Washington Street, Rm. E208
Indianapolis, IN 46204
For additional information about the administrative review process and applicable templates that may be used for filings, visit the following link
https://www.in.gov/dhs/appeals.htm.
Code review official
Address (name,title of local official,street,city,state and ZIP code
LARRY DAVIS
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
DEPT OF COMMUNITY SERVICE
Fax & e-mail: 3175712499, jblanchard@carmel.in.gov
Indiana State Building Commissionerldavis2@dhs.in.gov
02/23/22