HomeMy WebLinkAboutE-000-ELECTRICAL-SYMBOLS-&-ABBREVIATIONS-Rev.8ELECTRICAL SYMBOL LEGEND
SYMBOL DESCRIPTION MOUNTING
HEIGHT SYMBOL DESCRIPTION MOUNTING
HEIGHT
2'x4' FLUORESCENT LIGHT FIXTURE
NL 2'x4' FLUORESCENT LIGHT FIXTURE-NIGHT UNSWITCHED NIGHT
LIGHT
2x2' FLUORESCENT LIGHT FIXTURE
1'x4' OR 4' FLUORESCENT LENSED FIXTURE
2' UP/DOWN FLUORESCENT FIXTURE
DATA WALL OUTLET
FLUORESCENT STRIP LIGHT FIXTURE
RECESSED DOWNLIGHT
RECESSED WALL WASHER
WALL MOUNTED FIXTURE
POLE-MTD HID LIGHT FIXTURE W/SINGLE HEAD
POLE-MTD HID LIGHT FIXTURE W/TWIN HEADS
EXIT LIGHT
EMERGENCY BATTERY LIGHT FIXTURE
EXIT/EMERGENCY LIGHT COMBINATION
PC PHOTOCELL
TC TIME CLOCK
C LIGHT CONTRACTOR
SINGLE -POLE SWITCH$
THREE - WAY SWITCH $ 3
DIMMER SWITCH$D
MOTOR RATED THERMAL SWITCH$T
+48"
+48"
+48"
+48"
SSU SWITCH IN HANDY BOX WITH FUSE $ SSU +48"
LOCKABLE SWITCH-P&S #7813 $ L +48"
PILOT LIGHT SWITCH$P +48"
DOUBLE POLE SINGLE THROW SWITCH$DPST +48"
MOTOR RATED SWITCH $ M +48"
OS DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR
WALL MOUNT MOTION SENSOR LIGHTING CONTROL SWITCH$OC
WALL MOUNT LIGHTING CONTROL OVERRIDE SWITCH$OV
PP OCCUPANCY SENSOR POWER PACK
RP OCCUPANCY SENSOR RELAY PACK
+18"
DC DOUBLE DUPLEX CORD DROP RECEPTACLE +48"
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
D DEDICATED DUPLEX RECEPTACLE
IG DUPLEX RECEPTACLE W/ISOLATED GROUND
GFI GFCI DUPLEX RECEPTACLE
D
GFI DEDICATED GFCI DUPLEX RECEPTACLE
+18"
+18"
+18"
+18"
+18"
+18"
GFI
WP GFCI DUPLEX RECEPTACLE IN WEATHERPROOF HOUSING +18"
D DEDICATED DOUBLE DUPLEX RECEPTACLE +18"
FLOOR OUTLET
SPECIAL OUTLET
W.H.WATER HEATER CONN.
+45" MOUNTING HEIGHT TO CENTER OF DEVICE
MOTOR
CR CARD READER ROUGH-IN
CCTV CAMERA
DS DOOR SWITCH
DOCK LIGHT
FURNITURE FEED WALL (POWER AND TELE/DATA)
FURNITURE FEED FLOOR (POWER AND TELE/DATA)
PT
PT
DATA FLOOR OUTLET
TELEPHONE WALL OUTLET +18"
TELEPHONE FLOOR OUTLET
TELEPHONE/DATA WALL OUTLET +18"
T/P TELE / POWER POLE
J JUNCTION BOX IN CEILING
MOUNTING HEIGHTS LISTED ARE TYPICAL UNLESS INDICATED OTHERWISE ON THE PLANS.
MOUNTING HEIGHTS LISTED ARE TO THE CENTER OF THE DEVICE UNLESS INDICATED OTHERWISE.
J JUNCTION BOX IN WALL
SYSTEM CONTROL PANEL
ELECTRICAL PANEL BOARD + 6' TO TOP
T TRANSFORMER
+ 6' TO TOP
+ 6' TO TOP
+ 6' TO TOP
DISCONNECT SWITCH
COMBINATION STARTER / DISCONNECT SWITCH
STARTER
+ 6' TO TOPMANUAL MOTOR STARTER
(HORSEPOWER RATED)
+ 6' TO TOPMETERM
T THERMOSTAT
S SOUND SYSTEM SPEAKER
UNIT HEATER
HVAC EQUIPMENT (CAMBRIDGE UNIT,ETC.)
CONDENSING UNIT
AC, MC CABLE OR CONDUIT AND WIRE (CONCEALED), CROSS LINES DENOTE
NUMBER OF CONDUCTORS. NO CROSS LINES INDICATE 2-#12 CONDUCTORS.
CONDUIT AND WIRE UNDERGROUND OR UNDERFLOOR
FACP
ANN
NAC
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM SIGNAL ZONE EXTENDER PANEL
+ 6' TO TOP
+ 6' TO TOP
+ 6' TO TOP
F
S
S
R
MANUAL ALARM STATION
SMOKE DETECTOR
SMOKE DETECTOR WITH RELAY BASE
+48"
S I IONIZATION SMOKE DETECTOR
D DUCT MOUNTED SMOKE DETECTOR
R RATE OF RISE HEAT DETECTOR
HORN/STROBE COMBINATION
HORN STROBE LIGHTL
WF
SS
SPRINKLER WATER FLOW SWITCH
SPRINKLER VALVE SUPERVISORY SWITCH
END OF LINE RESISTOR
AR ADDRESSABLE RELAY MODULE
ADDRESSABLE MONITOR MODULEM
DH DOOR HOLDER
FIRE ALARM OUTSIDE BELL
FIRE ALARM OUTSIDE BELLF
FIRE ALARM SPEAKERS
FIRE ALARM SPEAKER STROBEF
T FIRE ALARM TELEPHONE JACK
P FIRE ALARM TELEPHONE
PIV POST INDICATOR VALVE
+80"
PB PUSH BUTTON
FISHEYE CAMERA
CONDUCTOR IDENTIFICATION
480 / 277V
SYSTEM
208Y/120V
SYSTEM
120/240 DELTA
SYSTEM
A PHASE - BROWN
B PHASE - ORANGE
C PHASE - YELLOW
NEUTRAL - GRAY
A PHASE - BLACK
B PHASE - RED
C PHASE - BLUE
NEUTRAL - WHITE
A PHASE - BLACK/RED
B PHASE - ORANGE/RED
C PHASE - BLUE/RED
NEUTRAL - WHITE/RED
WHERE THE PREMISES WIRING SYSTEM HAS BRANCH CIRCUITS SUPPLIED FROM MORE
THAN ONE NOMINAL VOLTAGE SYSTEM, EACH UNGROUNDED CONDUCTOR OF A BRANCH
CIRCUIT SHALL BE IDENTIFIED BY PHASE OR LINE AND SYSTEM AT ALL TERMINATION,
CONNECTION AND SPLICE POINTS. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED
TO BE BY SEPARATE COLOR CODING, MARKING TAPE, TAGGING OR OTHER APPROVED
MEANS. THE METHOD UTILIZED FOR CONDUCTORS ORIGINATING WITHIN EACH BRANCH
CIRCUIT PANELBOARD OR SIMILAR BRANCH CIRCUIT DISTRIBUTION EQUIPMENT SHALL BE
DOCUMENTED IN A MANNER THAT IS READILY AVAILABLE ORSHALL BE PERMANENTLY
POSTED AT EACH BRANCH CIRCUIT PANELBOARD OR SIMILAR BRANCH CIRCUIT
DISTRIBUTION EQUIPMENT.
-PURSUANT TO ARTICLE 210.5(C) OF THE 2009INDIANA ELECTRICAL CODE:
-PURSUANT TO ARTICLE 200.6(A): SIZES NO. 6 AND SMALLER:
AN INSULATED GROUNDED CONDUCTOR OF NO. 6 OR SMALLER SHALL BE IDENTIFIED
BY A CONTINUOUS WHITE OR GRAY OUTER FINISH OR BY THREE CONTINUOUS WHITE
STRIPES ON OTHER THAN GREEN INSULATION ALONG ITS ENTIRE LENGTH.
-PURSUANT TO ARTICLE 200.6(B): SIZES LARGER THAN NO. 6:
AN INSULATED GROUNDED CONDUCTOR LARGER THAN NO. 6 SHALL BE IDENTIFIED
BY A CONTINUOUS WHITE OR GRAY OUTER FINISH OR BY THREE CONTINUOUS WHITE
STRIPES ON OTHER THAN GREEN INSULATION ALONG ITS ENTIRE LENGTH OR, AT THE
TIME OF INSTALLATION, BY A DISTINCTIVE WHITE OR GRAY MARKING AT ITS
TERMINATIONS. THIS MARKING SHALL ENCIRCLE THE CONDUCTOR OR INSULATION.
ELECTRICAL ABBREVIATIONS
LCP LIGHTING CONTROL PANEL DIA DIAMETER
FA FIRE ALARM E.C. ELECTRICAL CONTRACTOR
SMP SPRINKLER MONITOR PANEL FBO FURNISHED BY OTHERS
MDF MAIN DISTRIBUTION FRAME DUKE DUKE ENERGY -ELEC. UTILITY CO.
IDF INTERMEDIATE DISTRIBUTION FRAME XFMR
TRANSFORMER
AFF ABOVE FONISHED FLOOR ATS AUTOMATIC TRANSFER SWITCH
AFG ABOVE FINISH GRADE HVLS HIGH VELOCITY LOW SPEED
OH OVERHEAD
CU COPPER
AL
GRD GROUND
DED DEDICATED
HYD HYDRUALIC
HGT HEIGHT
ALUMINUM
O.C.ON CENTER
N.O.NORMALLY OPEN
N.C
MCA MINIMUM CIRCUIT AMPS
WSA WIRE SIZE AMPS
MOCP MAXIMUM OVER CURRENT PROTECTION
SPST SINGLE POLE SINGLE THROW
NORMALLY CLOSED
SHEET TITLE
SHEET NUMBER
Kite Realty Group
30 S. Meridian Street, #1100
Indianapolis, Indiana 46204
Owner
Republic Airways Holdings
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Architect
McComas/O'donnell & Naccarato
Structural Engineer
Mechanical / Plumbing Design/Builder
Civil Engineer
8909 Purdue Road, Suite 300
Indianapolis, Indiana 46268
1717 E. 116th Street, Suite 200
Carmel, Indiana 46032
317-580-0402
DEEM LLC
6831 E 32nd Street
Indianapolis, Indiana 46226
Kimley Horn
250 East 96th Street, Suite 580
Indianapolis, Indiana 46240
KEY PLAN
B
A
HOTEL
PROJECT NO.
SHEET ISSUE
SEAL | DATE
COPYRIGHT NOTICE: ENGINEERING DRAWING
IS GIVEN IN CONFIDENCE AND SHALL BE USED
ONLY PURSUANT TO THE AGREEMENT WITH
BARTH ELECTRIC. NO OTHER USE,
DISSEMINATION OR DUPLICATION MAY BE
MADE WITHOUT PRIOR WRITTEN CONSENT OF
BARTH. ALL COMMON LAW RIGHTS OF
COPYRIGHT AND OTHERWISE ARE HEREBY
SPECIFICALLY RESERVED.
TRAINING
CENTER
Electrical Design/Builder
Barth Electric Co., Inc.
1934 N. Illinois Street
Indianapolis, Indiana 46202
1/13/2022 5:24:51 PME-000
ELECTRICAL
SYMBOLS &
ABBREVIATIONS
210930
Republic Airways
Training Center
12195 N. Meridian St.
Carmel, Indiana
46032
Sheet # Sheet Name
ELECTRICAL
E-000 ELECTRICAL SYMBOLS & ABBREVIATIONS
E-100 ELECTRICAL SITE PLAN
E-100.5 PLAN ENLARGEMENTS - SITE PLAN
E-101 FIRST FLOOR LIGHTING PLAN - OVERALL
E-101.5 SIM BAY CATWALK LIGHTING PLAN
E-101A FIRST FLOOR LIGHTING PLAN - AREA A
E-101B FIRST FLOOR LIGHTING PLAN - AREA B
E-102 SECOND FLOOR LIGHTING PLAN - OVERALL
E-102A SECOND FLOOR LIGHTING PLAN - AREA A
E-102B SECOND FLOOR LIGHTING PLAN - AREA B
E-103 THIRD FLOOR LIGHTING PLAN AND LOW ROOF PLAN
E-103A THIRD FLOOR LIGHTING PLAN - AREA A
E-103B THIRD FLOOR LIGHTING PLAN - AREA B
E-106 LIGHTING SCHEDULE AND PANEL SCHEDULE
E-201 FIRST FLOOR POWER AND SYSTEM PLAN
E-201.4 UNDERGROUND CONDUIT PLAN
E-201.5 SIM BAY CATWALK POWER AND SYSTEM PLAN
E-201A FIRST FLOOR POWER AND SYSTEM PLAN - AREA A
E-201B FIRST FLOOR POWER AND SYSTEM PLAN - AREA B
E-202 SECOND FLOOR POWER AND SYSTEM PLAN
E-202A SECOND FLOOR POWER AND SYSTEM PLAN - AREA A
E-202B SECOND FLOOR POWER AND SYSTEM PLAN - AREA B
E-203 THIRD FLOOR POWER AND SYSTEM PLAN
E-203A THIRD FLOOR POWER AND SYSTEM PLAN - AREA A
E-203B THIRD FLOOR POWER AND SYSTEM PLAN - AREA B
E-500 ONE LINE DIAGRAM
E-501 DETAILS
E-502 PANEL SCHEDULE
E-503 PANEL SCHEDULE
E-504 PANEL SCHEDULE
E-505 PANEL SCHEDULE
E-506 STAIR DETAIL
E-507 DETAIL
E-508 DEATIL
1 PERMIT SET 11/30/21
2 CD SET 12/17/21
3 BULLETIN 1 1/13/22
1/13/22
02/23/22