HomeMy WebLinkAboutE-501-DETAILS-Rev.7BONDING JUMPER EQUIP. BOND TO CASE SYSTEM GROUNDING ELECTRODE CONDUCTOR (RUN TO STRUCT. STEEL) FLEXIBLE METAL CONDUIT INSULATED BUSHING WITH GROUND LUG. TYPICAL AT BOTH ENDS. EQUIP. BONDING CONDUCTOR (RUN IN FLEX. CONDUIT), ATTACH TO BUSHING AT EACH END. EQUIPMENT BOND TO STANDARD GROUND BUS ISOLATED (AND INSULATED) GROUNDING CONDUCTOR (RUN TO X0 TERMINAL) OPTIONAL ISOLATED GROUND BUS STANDARD GROUND BUS 208Y/120V. 3∅, 4W. PANELBOARD WITH MAIN BREAKER N ∅A ∅B ∅C NEUTRAL (RUN TO X0 TERMINAL) PHASE CONDUCTOR 3∅TRANSFORMER, DELTA TO WYE PANELBOARD CONNECTION DETAIL NO SCALE TRANSFORMER CONDUCTOR SCHEDULE SECONDARY CONDUCTORS, OCP, AND GROUNDING PRIMARY CONDUCTORS, OCP, AND GROUNDING XFMR RATING FLEX CONDUIT SIZE PHASE CONDUCTOR SIZE NEUTRAL CONDUCTOR SIZE ISOLATED GROUND CONDUCTOR EQUIPMENT BOND CONDUCTOR SYSTEM GRND ELECTORDE & BOND. JMPR. SECONDARY OVERCURRENT PROTECTION PHASE CONDUCTOR SIZE EQUIPMENT BOND CONDUCTOR PRIMARY OVERCURRENT PROTECTION FLEXIBLE CONDUIT SIZE 15 KVA 30 KVA 45 KVA 75 KVA 150 KVA 1" 1 1/4" 1 1/2" 2" 3 1/2" (3) #8 CU (3) #3 CU (3) #1/0 CU (3) #3/0 CU (3) #500MCM (1) #8 CU (1) #3 CU (1) #1/0 CU (1) #3/0 CU (1) #500MCM #8 CU #8 CU #6 CU #6 CU #3 CU #8 CU #8 CU #6 CU #6 CU #3 CU #8 CU #8 CU #6 CU #4 CU #1/0 CU 50A 100A 150A 200A 400A (3) #10 CU (3) #8 CU (3) #4 CU (3) #3 CU (3) #3/0 CU #10 CU #10 CU #8 CU #8 CU #6 CU 30A 50A 70A 100A 200A MC CABLE 3/4" 1" 1 1/4" 2" A N B C BUILDING FOUNDATION / SLAB TO MAIN GROUNDING BUS IN MDF ROOM #2 CU 6 GAS PIPE WATER PIPE FULL SIZE PER I.E.C.250.66 1/4" X 4" X 12" CU GROUND BUS BAR W/ STAND-OFFS PER I.E.C 250.94 #3/0 CU FULL SIZE PER I.E.C.250.66 MAIN SERVICE EQUIPMENT 1 2 3 4 5 7 10 FEEDER CONDUIT SERVICE CONDUITS 1 2 3 4 5 6 7 8 9 10 NOTES: BOND EACH SERVICE ENTRANCE CONDUIT WITH JUMPER SIZED BY TABLE I.E.C 250.66, PVC IS NOT REQUIRED TO BE BONDED BOND LOAD SIDE CONDUIT BY I.E.C 250.96 & 250.97 NO SPECIAL PROCEDURE REQUIRED INSTALL MAIN BONDING JUMPER AS REQUIRED BY I.E.C 250.28 SIZE GROUNDING ELECTRODE CONDUCTOR BY I.E.C TABLE 250.66 BOND GROUNDING ELECTRODE RACEWAY OR CHASE NIPPLE AS REQUIRED BY I.E.C 250.92 GROUNDING ELECTRODE SYSTEM SHALL BE MADE UP AS REQUIRED BY I.E.C 250.50 & 52 NO CLAMP MODIFICATIONS SHALL BE ALLOWED--I.E.C 250.70 CONDUCTOR TO GROUND ROD REQUIRED TO BE NO LARGER THAN #6 CU (CAN BE SOLID) I.E.C 250.66, 310.3 - CAN GO DIRECTLY TO GROUND BAR, WATER PIPE OR BUILDING STEEL. GROUND ROD SHALL COMPLY WITH I.E.C 250.52 (C,3) & 250.10 EQUIPMENT GROUNDING CONDUCTOR OF CIRCUIT SERVING GAS FIRED EQUIPMENT BOND TO GAS PIPE AT TERMINATION TO EQUIPMENT. REFER TO I.E.C 250.104(B). NOTE-GAS PIPE MUST NOT BE PART OF THE GOUNDING ELECTRIDE SYSTEM (I.E.C 250.52(B)) MAIN SERVICE GROUNDING DETAIL NOT TO SCALE # 3/0 BARE COPPER GROUNDING CONSTRUCTED IN ACCORDANCE WITH I.E.C. 250.52(A)(4) AND 250.53(F) EXOTHERMIC CONNECTION TYPICAL IRREVERSIBLE GROUNDING RATED CONNECTION TYP. INTERIOR WALL-MOUNTED BATTERY EXIT WITH ADDITIONAL CAPACITY TO SUPPORT POWERING THE REMOTE HEAD FFOR 90 MINUTES MINIMUM (SEE LIGHT FIXTURE SCHEDULE) SEE REMORTE NOTE BELOW MC CABLE INTERIOR SURFACE-MOUNTED 4" SQ. BOX WITH BLANK COVER MOUNTED 6" ABOVE DOOR FRAME: 2-LAMP REMOTE (NO BATTERY) EXTERIOR SURFACE-MOUNTED (SEE LIGHT FIXTURE SCHEDULE) EQUA L EQU AL PRIMETER EGRESS MAN-DOOR 3/4" IMC NIPPLE (LENGHT DEPEN- DENT ON WALL THICKNESS) VIA WALL CORE WITH FIRESTOP EXTERIOR EGRESS REMOTE HEAD DETAIL NO SCALE SHEET TITLE SHEET NUMBER Kite Realty Group 30 S. Meridian Street, #1100 Indianapolis, Indiana 46204 Owner Republic Airways Holdings RATIO 101 South Pennsylvania Street Indianapolis, Indiana 46204 317-633-4040 Architect McComas/O'donnell & Naccarato Structural Engineer Mechanical / Plumbing Design/Builder Civil Engineer 8909 Purdue Road, Suite 300 Indianapolis, Indiana 46268 1717 E. 116th Street, Suite 200 Carmel, Indiana 46032 317-580-0402 DEEM LLC 6831 E 32nd Street Indianapolis, Indiana 46226 Kimley Horn 250 East 96th Street, Suite 580 Indianapolis, Indiana 46240 KEY PLAN B A HOTEL PROJECT NO. SHEET ISSUE SEAL | DATE COPYRIGHT NOTICE: ENGINEERING DRAWING IS GIVEN IN CONFIDENCE AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH BARTH ELECTRIC. NO OTHER USE, DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF BARTH. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED. TRAINING CENTER Electrical Design/Builder Barth Electric Co., Inc. 1934 N. Illinois Street Indianapolis, Indiana 46202 12/17/2021 4:29:00 PME-501 DETAILS 210930 Republic Airways Training Center 12195 N. Meridian St. Carmel, Indiana 46032 1 PERMIT SET 11/30/21 2 CD SET 12/17/21 12/17/21 02/23/22