HomeMy WebLinkAboutE501bEXIT NOTES: 1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. 2. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COURSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED. CEILING F H S E VC IC FSYMBOLS: FLOOR W C S M96"96"72"48"96"96"96"72"48"16"48"48"84"CU GRD. BAR RACKS #6 AWG INSULATED GROUND CONDUCTOR MDF & IDF'S MAIN EQUIPMENT BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) TO MAIN SERVICE EQUIPMENT SWITCHBOARD OR PANELBOARD GROUND BUS AT SERVICE ENTRANCE N G COMMUNICATIONS SYSTEMS EQUIPMENT CABINET GROUND COMMUNICATIONS PLYWOOD BACKBOARD GROUND BAR TELEPHONE SERVICE DEMARK GROUND BAR 3/4"X10' CU GROUND ROD AS REQUIRED (SEE SECTION 260526) EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS G NEUTRAL BUS GROUND BUS #3/0 CU EQUIPMENT BONDING JUMPER BONDING BUSHING (TYPICAL) SERVICE EQUIPMENT ENCLOSURE (MAIN SWITCHBOARD) MAIN BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) PANELBOARD BUILDING FOUNDATION REBAR #3/0 BARE CU GROUND RING INCOMING METAL WATER SERVICE BUILDING STEEL INCOMING SERVICE METAL CONDUITS #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR TRANSFORMER C N B A NTL AS SHOWN ON DRAWINGS NO GROUND CABLE UTILITY TRANSFORMER CB CB FACP ZAM ZAM ZAM SS SS SS ZAMZAM CB PER ONE LINE DIAGRAM A SINGLE RACEWAY) (MAY BE COMBINED IN 2#14, 3/4"C. TELE. CABLE NOTES: TELE. OUTLET SECOND LOBBY FLOOR IN HOISTWAY IN ELEVATOR EQUIPMENT FIRST LOBBY FLOOR ROOM #18 SHIELDED INDUSTRIAL VAPORTITE IN PIT FIXTURE RECEPTACLE GFI POWER FEED, SIZED 208V, 3∅ELEVATOR 2#12,#12G., 3/4"C. MANUFACTURER/ INSTALLER CAB CABHVAC CONTROL CAB LIGHTS BY DIVISION 26 BY ELEVATOR TO 208V PANEL PER PLANS IN HOISTWAY EQUIPMENT ROOM IN ELEVATOR FIRST FLOOR LOBBY BY DIV. 16 TWISTED PAIR FLOOR LOBBY THIRD SECOND FLOOR LOBBY FOURTH FLOOR LOBBY FLOOR LOBBY THIRD FLOOR LOBBY FOURTH NOTES: 1. PROVIDE ENGRAVED PHOENELIC NAMEPLATE ON DISCONNECTS STATING MORE THAN ONE SOURCE SERVES THE ELEVATOR CABINET. 2. SHOULD THE GENERAL CONTRACTOR UTILIZE AN ELEVATOR MANUFACTURER THAT REQUIRE MORE ELECTRICAL WORK THAN SHOWN ON THIS DETAIL, THE COSTS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 3. IF ELEVATOR CAN BE OPERATED FROM NEC 702 OPTIONAL POWER SYSTEM, ALL HVAC EQUIPMENT SERVING THE ELEVATOR EQUIPMENT ROOM SHALL BE CONNECTED TO THE OPTIONAL POWER SYSTEM. 4. EQUIPMENT SHOWN SHADED IS BY ELEVATOR MANUFACTURER. ITEMS SHOWN DARK ARE BY DIVISION 26. TO 208/120V PANEL DEDICATED CIRCUIT TO 208/120V PANEL DEDICATED CIRCUIT 2#14, 3/4"C. 208V 3P CIRCUIT BREAKER, PER ONE LINE DIAGRAM WITH AUXILIARY N.O. CONTACT IN ELEVATOR MACHINE ROOM 20A/1P CIRCUIT BREAKER IN ELEVATOR MACHINE ROOM 2#10, #10G., 3/4"C. TO 208/120V PANEL PER PLANS C C C C C C C C ZAM FLOOR LOBBY ROOF TOP OF BOX TO BE NO MORE THAN +48" AFF BOTTOM OF BOX TO BE NO LESS THAN +16" AFF OPEN BOX MOUNTING BRACKET TO BE USED WHEN BOX LARGER THAN 2- GANG IS REQUIRED WALL STUD (TYP) TYPICAL BOX MOUNTING BRACKET NOTES: 1. BOX MOUNTING BRACKETS ARE TO BE USED WHEN MOUNTING MULTIPLE BOXES WITHIN THE SAME STUD SPACE. 2. WHEN RECEPTACLES ARE SHOWN BELOW SWITCHES ALIGN VERTICALLY. 2' - 0"3"3"*5'-0" (4) #4 REBAR (<15' POLE)*6'-0" (4) #4 REBAR (15'-25' POLE)*7'-0" (5) #4 REBAR (26'-40' POLE)4"48"1 2" SUB GRADE FINISHED PAVEMENT PROVIDE VENDOR BASE COVERS TO MATCH POLE IN COLOR POLE GROUNDING LUG OPPOSITE OF HANDHOLE TYPICAL COIL EXCESS TO ALLOW FUSES AND CONNECTORS TO BE REMOVED THRU HANDHOLE #10 GROUND AND NEUTRAL KEEP SPACE BETWEEN BOLT COVERS AND FOUNDATION TO A MINIMUM. CAULK NEATLY ALL AROUND TO FILL GAPS. GROUT COLOR SHALL MATCH POLE 1/2" PVC CONDUIT YELLOW, METAL BACKED POLYETHELENE TAPE MARKED "ELECTRIC" #6 BARE STRANDED COPPER GROUND CABLE EXOTHERMIC WELD SCHEDULE 40 PVC CONDUIT TO NEXT POLE (1" MINIMUM) EXCEPT WHERE NOTED REINFORCING STEEL REQUIRED, BUT NOT COMPLETELY SHOWN LEVELING NUTS WITH WASHERS. PROTECT NUTS AND THREADS DURING CONCRETE POUR. TYPICAL FOURWAY BOLTED CONNECTOR WITH WATERPROOF INSULATION (MAX. 4 #10 COPPER) HANDHOLE WITH COVERPLATE TYPICAL WATERTIGHT IN LINE FUSE HOLDER WITH FUSE SIZED PER MANUFACTURER RECOMMENDATION FOR EACH PHASE CONDUCTOR #10 PHASE CONDUCTORS UP TO LUMINAIRE (1 OR 2 CONDUCTORS) FINISHED GRADE 4" OCTAGONAL JUNCTION BOX (AT LEAST 1.5" DEEP). DO NOT INSTALL SENSOR WITHOUT JUNCTION BOX. CEILING DEPLUGGABLE TERMINAL SENSOR (2) MOUNTING SCREWS FRONT COVER 50 South B.B. King Blvd. Suite 600 Memphis, TN 38103 901.521.1440 Drawing Name: Client: Drawn By: Checked By: Project Name: Issued / RevisedDate # Issues and Revisions ©2020 LRK Inc. Drawings, written material, and design concepts shall not be used or reproduced in whole or part in any form or format without prior written consent of LRK Inc. Do not scale drawings. Use given dimensions only. If not shown, verify correct dimensions with the Architect. Contractor shall check and verify all dimensions and conditions at job site. KBSO Project Number: 20070 1344 South Rangeline Road Suite 202 Carmel, IN 46032 317.344.8044 8/20/2021 12:31:16 PM C:\Users\Slove\Documents\20070 The Corner MEP v19_SamuelLove.rvt LRK Project Number: 01.18066.00 E501b ELECTRICAL DETAILS The Corner Carmel, IN Checker Author 116th Street & Rangeline Carmel, INThe Corner Carmel, IN •01.18066.003/8" = 1'-0" TYPICAL ELECTRICAL ELEVATION1 12" = 1'-0" TYPICAL GROUNDING DETAIL2 12" = 1'-0" TYPICAL ELEVATOR WIRING DIAGRAM3 1/2" = 1'-0" TYPICAL BOX SUPPORT DETAIL4 1" = 1'-0" TYPICAL LIGHT POLE BASE5 12" = 1'-0" TYPICAL OCCUPANCY SENSOR MOUNTING DETAIL6 1 06.16.21 Permit Set 2 08.20.21 IFC Set 11/01/21