FINISHED INTERIOR MIN. 32" SQUARE DOOR MIN. 30"MECHANICAL EQUIPMENT PLENUM CLEARANCE CPVC CONDENSATE DRAIN; ROUTE TO HUB DRAIN FLEX CONN. DUCT FIRE DAMPER FAN COIL SIDE VIEW TOP VIEW NOTE: TYPICAL CONDITION SHOWN FOR UNITS, REFER TO MECHANICAL AND PLUMBING FLOOR PLANS FOR ADDITIONAL REQUIREMENTS. CEILING RADIATION DAMPER (TYP.) MIN. 20" NOTES: 1. ROUTE CONDENSATE PIPING (SIZE PER MANUFACTURER) TO HUB DRAIN. 2. REFER TO REFRIGERANT PIPING DETAIL ON MECHANICAL DETAIL SHEET FOR ASSOCIATED REQUIREMENTS. 3. REFER TO STRUTURAL UNIT PLAN DRAWINGS FOR ACTUAL CONDITION AT EACH CLOSET. HARD DUCT MAIN ALWAYS ROUTES PARALLEL TO JOISTS. 4. COORDINATE HARD DUCT ELEVATION AT JOIST SPACE WITH FIRE AND PLUMBING PIPING PRIOR TO INSTALLATION. 5. FIRESTOP ALL PENETRATIONS AT CEILING AND FLOOR AND THROUGH AHU SUPPORT. 6. ALL MATERIALS CONTAINED WITHIN MECHANICAL CLOSET HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. REFRIGERANT SUCTION / LIQUID; ROUTE TO CONDENSING UNIT RETURN GRILLE, SEE PLANS 10" X 10" ACCESS PANEL R.A. DUCT WALL MOUNT EQUIPMENT OUTSIDE AIR CONNECTION FINISHED INTERIOR MIN. 32" SQUARE DOOR MIN. 30" WATER HEATER PAN WATER HEATER MECHANICAL EQUIPMENT PLENUM CLEARANCE CPVC CONDENSATE DRAIN W/ TRAP; ROUTE TO HUB DRAIN WITH AIR GAP MAIN SHUT-OFF WATER HEATER PAN FLEX CONN. FAN COIL WATER HEATER HWCW VALVE SIDE VIEW TOP VIEW NOTE: TYPICAL CONDITION SHOWN FOR UNITS, REFER TO MECHANICAL AND PLUMBING FLOOR PLANS FOR ADDITIONAL REQUIREMENTS. CEILING RADIATION DAMPER (TYP.) MIN. 20" REFRIGERANT SUCTION / LIQUID; ROUTE TO CONDENSING UNIT RETURN GRILLE, SEE PLANS SECURE AIR HANDLER TO WALL WITH Z PANEL CLIPS / HANGERS AND ANGLE BRACKETS NOTES: 1. ROUTE CONDENSATE PIPING (SIZE PER MANUFACTURER) TO HUB DRAIN. 2. REFER TO REFRIGERANT PIPING DETAIL ON MECHANICAL DETAIL SHEET FOR ASSOCIATED REQUIREMENTS. 3. REFER TO STRUCTURAL UNIT PLAN DRAWINGS FOR ACTUAL CONDITION AT EACH CLOSET. HARD DUCT MAIN ALWAYS ROUTES PARALLEL TO JOISTS. 4. COORDINATE HARD DUCT ELEVATION AT JOIST SPACE WITH FIRE AND PLUMBING PIPING PRIOR TO INSTALLATION. 5. FIRESTOP ALL PENETRATIONS AT CEILING AND FLOOR. 6. ALL MATERIALS CONTAINED WITHIN MECHANICAL CLOSET MUST HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. 7. FLOAT SWITCH TO BE EQUAL TO RECTORSEAL 97637 SAFE-T SWITCH. FIRE DAMPER 10" X 10" ACCESS PANEL INSTALL FLOAT SWITCH ON AUXILIARY DRIAN TO SHUT DOWN FAN COIL IF PRIMARY DRAIN IS BLOCKED. PROVIDE 16 GA. NAIL STOP WHERE LINE OR PIPE IS LESS THAN 1-1/2" FROM STUD FACE. PROVIDE 1-1/4" GAP ABOVE THE PIPE TO ACCOMODATE WOOD SHRINKAGE. PROVIDE 16 GA. NAIL STOP WHERE LINE OR PIPE IS LESS THAN 1-1/2" FROM STUD FACE. INTERIOR NON LOAD BEARING WALL STUDS EXTERIOR AND/OR LOAD BEARING WALL STUDS "N" (MAX) "D" (MAX) 40% W ( SEE NOTE 3) 40% W 25% W 40% W NOTES: 1. BORED HOLES SHALL NOT BE LOCATED AT THE SAME SECTION OF STUD AS A NOTCH. 2. PROVIDE ELONGATED HOLES SO AS TO ACCOMODATE WOOD SHRINKAGE (RE;SPECS). NOT PROVIDING A GAP BETWEEN THE STUD AND THE PIPE MAY RESULT IN DAMAGE TO THE PIPE. 3. "D" MAY BE INCREASED TO 60% OF "W" FOR TWO CONSECUTIVE NON LOAD BEARING STUDS MAXIMUM BUT STUDS MUST BE DOUBLED UP. "W" "D""N" "W" 5/8" MIN. 5/8" MIN. LINESET (1 PER SLEEVE) 3" MIN. FIRECAULK (INSIDE AND OUTSIDE SLEEVE) 3" METAL SLEEVE 20 GA MIN. TAPE CUT ENDS (TO PREVENT SHARP EDGES) FLOOR ASSEMBLY SUBFLOOR WOOD TRUSS CEILING ASSEMBLYFIRECAULK (INSIDE AND OUTSIDE PIPE) 8" MIN.2"2"GENERAL NOTES: 1. DO NOT INSTALL IN CORNERS 2. SLEEVES AT TOP FLOOR CEILING ROD 3. SLEEVES TO BE FASTENED IN PLACE BEFORE DRYWALL / LINESET INSTALL 4. MIN 8" FROM SIDEWALL AND 4" FROM BACK WALL.RSRLEVAPORATOR COIL THERMAL EXPANSION VALVE SIGHTGLASS REFER TO AIR COOLED CONDENSING UNIT SCHEDULE FOR REFRIGERANT LINE SIZES AIR COOLED CONDENSING UNIT WITH FACTORY INSTALLED: 1. LIQUID LINE FILTER DRIER 2. SUCTION AND DISCHARGE LINE REFRIGERATION CHARGING CONNECTIONS FIELD BRAZED CONNECTIONS ISOLATION VALVE, TYP. CAULK WATERTIGHT 12" MIN.ROOF PROVIDE WOOD BLOCKING BELOW CURBS (TYPICAL)TYPICAL PIPING OR CONDUIT FILL VOIDS WITH BATT INSULATION INSULATED PIPE CURB ASSEMBLY SPECIFICATION FOR JOINING AND ATTACHING FLEXIBLE DUCT DUCTWORK SPIN-IN FITTING FLEXIBLE DUCT-NO MORE THAN TWO (2) 90° BENDS. SQUARE TO ROUND FITTING CEILINGAIR TERMINAL WITH RADIATION DAMPER A. METALLIC FLEXIBLE DUCT SHALL BE ATTACHED USING A MINIMUM OF THREE #8 SHEET METAL SCREWS EQUALLY SPACED AROUND THE DUCT'S CIRCUMFERENCE; DUCTS LARGER THAN 12"Ø SHALL HAVE A MINIMUM OF FIVE #8 SHEET METAL SCREWS. SCREWS SHALL BE LOCATED AT LEAST 8" FROM THE DUCT END. B. NON-METALLIC FLEXIBLE DUCT SHALL BE SECURED TO THE SLEEVE OR COLLAR USING A DRAW BAND. IF THE DUCT COLLAR EXCEEDS 12"Ø, THE DRAW BAND MUST BE POSITIONED BEHIND A BEAD ON THE METAL COLLAR. C. INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY-FABRICATED DUCTS SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BE SUPPLEMENTALLY SECURED WITH A DRAW BAND. D. FLEXIBLE DUCT SEALING SHALL BE A CLASS "B" FOR LOW PRESSURE DUCT. FINISHED FLOOR AS SCHEDULED LIGHTING CONTROLS, INTERCOM, PULL STATION, THERMOSTAT DOOR FRAME/WALL OPENING WHERE OCCURS LOCATE DEVICES 6" FROM DOOR/WALL OPENING, OR AS DIMENSIONED. WHERE NOT DIMENSIONED, LOCATE AT NEAREST STUD FROM LOCATION SHOWN ON FLOOR PLAN 6"UON44" UONINSTALL BOT. OF UNI NOM. 7" ABOVE CEILING, SAME AT ALL LOCATIONS EXH. VENT TERMINATION, SEE PLANS CAULK/SEAL WALL FLANGE & WATER-TIGHT SEAL, PER MFGR'S INSTR. REFER TO ARCHITECTURAL PLANS FOR WALL CONSTRUCTION DUCT TO BE RIGID IF BATH EXHAUST LAST 5-FEET OF DUCT TO BE PITCHED TO EXTERIOR 50 South B.B. King Blvd. Suite 600 Memphis, TN 38103 901.521.1440 Drawing Name: Client: Drawn By: Checked By: Project Name: Issued / RevisedDate # Issues and Revisions ©2020 LRK Inc. Drawings, written material, and design concepts shall not be used or reproduced in whole or part in any form or format without prior written consent of LRK Inc. Do not scale drawings. Use given dimensions only. If not shown, verify correct dimensions with the Architect. Contractor shall check and verify all dimensions and conditions at job site. KBSO Project Number: 20070 1344 South Rangeline Road Suite 202 Carmel, IN 46032 317.344.8044 8/20/2021 12:46:24 PM C:\Users\Slove\Documents\20070 The Corner MEP v19_SamuelLove.rvt LRK Project Number: 01.18066.00 M501b MECHANICAL DETAILS The Corner Carmel, IN SJO SLL 116th Street & Rangeline Carmel, INThe Corner Carmel, IN •01.18066.0012" = 1'-0" MECHANICAL ROOM DETAIL (CORRIDOR) 1 12" = 1'-0" MECHANICAL ROOM DETAIL (RESIDENT)2 12" = 1'-0" NOTCHES & BORED HOLES IN WALL STUDS DETAIL3 12" = 1'-0" LINESET SLEEVE DETAIL4 12" = 1'-0" REFRIGERATION PIPING DETAIL5 12" = 1'-0" CONDENSING UNIT ROOF VAULT DETAIL6 12" = 1'-0" CONDENSING UNIT SUPPORT DETAIL7 12" = 1'-0" TYPICAL AIR TERMINAL INSTALLATION DETAIL8 1/2" = 1'-0" TYPICAL THERMOSTAT MOUNTING DETAIL9 12" = 1'-0" VENT TERMINAL DETAIL10 1 06.16.21 Permit Set 2 08.20.21 IFC Set 11/01/21