DOOR ALARM CONTROL PANEL DACP
HINGE SIDE PLUNGER SWITCH DC
FIRE PROTECTION SYMBOLS
FIRE ALARM CONTROL PANEL FACP
FFIRE PULL BOX
HORN/STROBE ALARM COMBO
SSTROBE
FSFLOW SWITCH
TSPIV TAMPER SWITCH
HORN/STROBE ALARM COMBO WEATHER PROOF
AHOOD ANSUL SYSTEM CONNECTION
SSMOKE DETECTOR
DUCT SMOKE DETECTOR S
HEAT DETECTOR H
SD
MAGNETIC LOCK WITH KEY PAD
MAGNETIC LOCK WITH CARD READER
HS
KP
CR
CARBON MONOXIDE DETECTOR CO
ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE
BID IN STRICT ACCORDANCE WITH DESIGN BASIS
EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE
COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS
OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS
OF DESIGN. SUBSTITUTE ITEMS WILL BE COMPARED
AGAINST DESIGN BASIS DURING SUBMITTAL PROCESS.
ENGINEER RESERVES THE RIGHT TO REJECT
SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS
LISTED IN DESIGN BASIS..
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO
ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH
GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS,
CONTRACTORS NAME AND PROJECT NAME. CLEARLY
INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES
AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN
PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES
THE RIGHT TO REJECT ANY SUBSTITUTE ITEM FOUND NOT
EQUAL TO THE SPECIFIED ITEM AS DESIGNED.
3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR
THE USE OF ALL TRADES DURING CONSTRUCTION AS
REQUIRED BY THE GENERAL CONTRACTOR. REMOVE ALL
TEMPORARY EQUIPMENT AS PERMANENT SERVICES
BECOME AVAILABLE.
4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND
ARE NOT INTENDED TO DEFINE EXACT QUANTITIES,
LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS
SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN
ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS
REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED
WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY
FOR ALL REQUIRED PERMITS.
5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL
REQUIRED LABOR, MATERIALS, EQUIPMENT, AND
CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE
INSTALLATION OF SYSTEMS REQUIRED IN FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES.
THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE
IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR
A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE
ALL LABOR AND MATERIALS ENTERING INTO CONTRACT
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
ACCEPTANCE.
6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2009
INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA
ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE,
COUNTY, CODES AND ORDINANCE AND INDIANA
AMENDMENTS. COORDINATE WORK WITH OTHER TRADES.
ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS
RESULTING FROM ANY NON COMPLIANCE WITH CODE
REQUIREMENTS
7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS
INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL
WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND
LISTED BY U.L. MATERIALS AND EQUIPMENT SHALL
CONFORM WITH THE LATEST ISSUES OF APPLICABLE
TECHNICAL STANDARDS.
8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A
COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND
POWER AS REQUIRED. VERIFY ALL VOLTAGES AND PHASE
REQUIREMENTS WITH MECHANICAL CONTRACTOR'S
EQUIPMENT PRIOR TO PERFORMING ANY WORK.
9. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND
VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING A
BID. NO EXTRAS WILL BE ENTERTAINED FOR
CONTRACTORS FAILURE TO IDENTIFY EXISTING
CONDITIONS AND ADJUST AS REQUIRED TO MEET DESIGN
INTENT.
10. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE
COMPRESSION TYPE AND MADE TO ENSURE POSITIVE
GROUNDING CONTINUITY. MAKE CONNECTIONS TO
EQUIPMENT SUBJECT TO VIBRATION WITH 18 INCHES OF
FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT
FITTINGS. PROVIDE FOR SUPPORT AND SECURING OF ALL
CONDUIT AND EQUIPMENT. CONNECTIONS TO LIGHTING
FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE
CONDUIT FROM A BOX WITHIN TWO (2) FEET OF THE
FIXTURE. SPLICE ALL WIRES ONLY IN ACCESSIBLE BOXES.
ALL FIXTURE WHIPS TO BE FLEXIBLE METAL CONDUIT 1/2"
MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH
INSULATED THROATS. WHIPS SHALL NOT EXCEED 6'.
FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING
STRUCTURE.
WIRING AND RACEWAYS
1. ALL LIGHTING AND BRANCH CIRCUIT WIRING SHALL BE
SOLID COPPER MINIMUM SIZE #12 AWG. 600V INSULATION,
75 DEG. C., TYPE THW OR THWN, NOT LESS THAN #12 AWG.
ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL
BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE
EITHER STRANDED COPPER CONDUCTOR OR ASTM B800
ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT
LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN #8
AWG FOR ALUMINUM. EACH WITH MINIMUM 600V THW OR
THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE
SIZED IN ACCORDANCE WITH NEC 310.15.
2. ALL EXPOSED WIRING SHALL BE IN EMT RACEWAY.
EXTERIOR WIRING SHALL BE IN CONDUIT. CONCEALED
WIRING SHALL BE IN EMT OR METAL CLAD CABLE WHERE
ALLOWED BY CODE.
3. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR
EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE.
4. ALL CABLE SHALL BE NEW WIRE OF RECENT
MANUFACTURE AND IN ACCORDANCE WITH THE LATEST
STANDARDS OF IPCEA AND NEMA AS A MINIMUM.
5. ALL DEVICES AND EQUIPMENT SHALL BE SOLIDLY
GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS.
6. ALL SOLID CONDUCTOR WIRES MAY BE TERMINATED
UNDER SCREW HEADS. STRANDED WIRES MAY BE
TERMINATED BY USING PUSH-IN CLAMP TYPE
CONNECTORS FURNISHED WITH DEVICES OR TERMINATED
WITH COMPRESSION TYPE TERMINAL LUGS. SET SCREW
TYPE TERMINATIONS ARE NOT PERMITTED.
7. NO MOTORS ARE TO BE SUPPLIED UNDER THIS CONTRACT
UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BY
THIS CONTRACTOR. THE CONTRACTOR SHALL FURNISH
ALL STARTERS FOR ALL MOTORS REQUIRING A STARTER.
THE CONTRACTOR SHALL CONNECT ALL POWER
EQUIPMENT IF & WHERE SHOWN ON PLANS UNLESS
OTHER-WISE SPECIFIED & ASSURE OWNER THE MOTORS
ARE IN GOOD RUNNING ORDER.
8. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET
MEANS OF DISCONNECT PER N.E.C. FOR ALL HARD WIRED
EQUIPMENT.
PANELS AND DISCONNECTS
1. PANELBOARDS SHALL BE A DEAD-LOCK SAFETY TYPE,
SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED
WITH THERMAL-MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED.
TERMINALS FOR FEEDER CONDUCTORS TO THE
PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED
AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED.
TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER
AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS
SHALL BE OF THE FULL COMPRESSION TYPE.THE
PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A
STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND
GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA
STANDARD PUBLICATION NO. PB-1971 AND U.L.
STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL
BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT
RUST-RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS
AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER
TUMBLER-TYPE LOCKS WITH CATCHES AND SPRING
LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT
PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD
LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE
ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE
CONCEALED WHEN THE DOORS ARE CLOSED. DOORS
SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL
HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR
IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME
AND TYPE WRITTEN CARD WITH A CLEAR PLASTIC
COVERING SHALL BE PROVIDED ON THE INSIDE OF THE
DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT
LEAST 1/4" HIGH X 3" LONG OR EQUIVALENT FOR EACH
CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL
FINISHED STEEL WITH RUST-INHIBITING PRIMER FACTORY
FINISHED ENAMEL PAINT.
2. LOAD CENTERS SHALL BE UL LISTED AND MANUFACTURED
IN ACCORDANCE WITH THE LATEST NEMA STANDARDS.
CABINETS SHALL USE HINGED STYLE DOORS. MOUNT AT
6'-6" TO TOP OF CABINET.
3. CIRCUIT BREAKERS SHALL BE QUICK-MAKE, QUICK-BREAK,
THERMAL-MAGNETIC, TRIP INDICATING AND HAVE COMMON
TRIP ON ALL MULTI-POLE BREAKERS. BRANCH CIRCUIT
BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE
SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE
THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT
REPEATED ARCING SHORTS RESULTING FROM FRAYED
APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT
ON.
4. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT
AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT
CURRENT AVAILABLE AT THE PANELS. ALL
PANELS/BREAKERS/SWITCHES ARE TO BE BRACED TO
EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND
CIRCUIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING
FAULT CURRENT. MANUFACTURER SHALL PROVIDE ALL
REQUIRED FAULT CURRENT AND ARC-FLASH LABELING PER
110.16 AND 110.24.
5. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT
EXCEED 1750 WATTS. VOLTAGE DROP OF BRANCH
CIRCUITS SHALL NOT EXCEED 3% AND FEEDER CIRCUITS
SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER
TIGHT. FIRE STOP WHERE REQUIRED.
6. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE
NAMEPLATES FOR ALL ELECTRICAL PANELS AS REQUIRED
BY NEC 408.4(B) AND SHALL LABEL ALL DISCONNECTS,
TRANSFORMERS AND MOTORS OVER 1 HP. FURNISH
TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY ALL
ELECTRICAL CIRCUITS BOTH NEW AND EXISTING.
7. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA
TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR
OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER
OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS
INDICATED ON THE DRAWINGS.
DEVICES
1. VERIFY EXACT LOCATION, COLOR AND HEIGHTS OF ALL
OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT
WITH OWNER'S REPRESENTATIVE PRIOR TO START OF
WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP
SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS,
HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS,
DISTRIBUTION PANELS ETC. AS REQUIRED.
2. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18"
ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS
NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL
BE 42" A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE
ON THE DRAWINGS.
3. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FINAL LOCATIONS
AND COLORS OF ALL DEVICES WITH OWNER.
4. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO
ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING
SURFACES AND FREE FROM ALL OBSTRUCTIONS.
REWORKING OF EQUIPMENT INSTALLED IMPROPERLY
SHALL BE AT THE CONTRACTOR'S EXPENSE.
5. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1
CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA
TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS.
6. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL
BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO
HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15
AMPERES, SINGLE POLE, 125/277V. MULTI-POLE OR
SPECIAL SWITCHING SHALL BE AS NOTED ON THE
DRAWINGS.
7. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES,
DUPLEX, GROUNDED HUBBELL COMMERCIAL
SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE
AS NOTED ON THE DRAWINGS.
8. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL
RECEPTACLES AND SWITCHES.
LIGHTING FIXTURES:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE
BETWEEN LIGHTING FIXTURE PER FLOOR PLANS.
2. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FIXTURE
QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER
FOR ALL FIXTURES.
3. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT
NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP
HOLDERS, REFLECTORS, BALLASTS, STARTERS AND
WIRING.
4. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS
AS INDICATED, IN ACCORDANCE WITH FIXTURE
MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
REQUIREMENTS OF NEC, NECA'S "STANDARD OF
INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED
INDUSTRY PRACTICES TO ENSURE THAT LIGHTING
FIXTURES FULFILL REQUIREMENTS.
5. COORDINATE WITH OTHER ELECTRICAL WORK AS
APPROPRIATE TO PROPERLY INTERFACE INSTALLATION OF
INTERIOR LIGHTING FIXTURES WITH OTHER WORK.
6. E.C. TO FASTEN FIXTURES SECURELY DIRECTLY TO
BUILDING STRUCTURAL SYSTEM. LIGHT TROFFERS SHALL
BE SUPPORTED AT EACH CORNER OF FIXTURE BY WIRES
OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID.
ATTACH EARTHQUAKE CLIPS TO GRID AS RECOMMENDED
BY LIGHT MANUFACTURER. USE SCREWS IF REQUIRED BY
MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE
ABOVE. LIGHTS SHALL NOT BE SUPPORTED IN ANYWAY BY
LAY-IN CEILING.
7. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE
LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL
OBSTRUCTIONS. CLEAN ALL LIGHTING EQUIPMENT AFTER
LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS
COMPLETE. REPAIR ANY FIXTURES DAMAGED DURING
CONSTRUCTIONS.
8. PROVIDE NECESSARY MOUNTING FRAMES, SUPPORTS AND
RELATED ITEMS REQUIRED TO PROPERLY INSTALL
FIXTURES. SUPPORT FIXTURES INDEPENDENTLY OF PIPING
AND DUCTWORK. MAKE MODIFICATIONS TO THE
STRUCTURE AS REQUIRED TO INSTALL FIXTURES. ANY
MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE BUILDING.
LOW VOLTAGE
1. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN
CONSTRUCTION OR IN EXPOSED OPEN AREAS SHALL BE
RUN IN MINIMUM 3/4" EMT CONDUIT. CONTRACTOR SHALL
INSTALL 3/4" CONDUIT (MINIMUM) FROM EACH LOW
VOLTAGE ROUGH-IN LOCATION TO ACCESSIBLE CEILING
SPACE, LOW VOLTAGE WIRE TRAY OR HANGERS AND THEN
TO MDF, HEAD-IN, PBX PUNCH DOWN, CONTROLLER ETC.
2. E.C. SHALL COORDINATE WITH LOCAL PHONE AND CABLE
PROVIDER AS CHOSEN BY OWNER AND PROVIDE
RACEWAYS FOR BRINGING IN SERVICES AS REQUIRED.
3. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATED IN
PLENUMS.
4. ALL DATA CABLE SHALL BE CAT 6 UNLESS OTHER WISE
NOTED. TERMINATE, LABEL AND TEST ALL WIRING.
5. ALL TV CABLE SHALL BE HIGH DEFINITION COAX RG6 OR AS
REQUIRED BY PROVIDER, VERIFY PRIOR TO ROUGH IN.
FIRE STOPPING.
1. FIRE STOPPING SYSTEMS SHALL BE IN FULL COMPLIANCE
WITH SECTIONS 714 OF THE IBC AND NFPA 221.
2. CONTRACTOR SHALL MAKE REFERENCE TO
ARCHITECTURAL PLANS AND PROVIDE ALL REQUIRED FIRE
STOPPING.
3. CONTRACTOR SHALL PROVIDE AHJ WITH FULL SUBMITTAL
INDICATING METHODS OF CONSTRUCTION AND UL LISTINGS
FOR EACH PENETRATION SYSTEM USED.
4. PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS OR
FLOOR CEILING ASSEMBLIES BY ELECTRICAL DEVICES,
RACEWAYS OR PANELS, ETC. SHALL COMPLY WITH
SECTIONS 713.2 THROUGH 713.3.3 OF THE IBC.
5. ACCESS DOORS REQUIRED IN CEILINGS OF
FIRE-RESISTANCE-RATED FLOOR/CEILING AND
ROOF/CEILING ASSEMBLIES SHALL BE TESTED IN
ACCORDANCE WITH ASTM E 119 OR UL 263 AS HORIZONTAL
ASSEMBLIES AND LABELED BY AN APPROVED AGENCY FOR
SUCH PURPOSE.
CLOSE OUT
1. PROVIDE MANUFACTURERS OPERATION AND
MAINTENANCE MANUALS AND PROVIDE AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER
SELECTED PERSONNEL AS REQUESTED AND PROVIDE
WARRANTY INFORMATION FOR ALL MANUFACTURERS
WARRANTED EQUIPMENT
AMPS
MECHANICAL CONTRACTOR
ELECTRICAL ABBREVIATIONS
MANUFACTURER
MOUNTING HEIGHT
MFR
MH
MINIMUM
MOTOR OPERATED DAMPER
MLO
MIN
MOD
MOCP
MOUNTED
NOT IN CONTRACT
PLUMBING CONTRACTOR
ON CENTER
NOT TO SCALE
MTD
NIC
PC
NTS
OC
COMPANYCO
RUNNING LOAD AMPSRLA
ELECTRIC CONTRACTOR
DOWN
DRAWING(S)
ELECTRICAL DISTRIBUTION CENTER
EQUIPMENT
EC
DN
DWG(S)
EQUIP
EDC
EWC
ETR
FULL LOAD AMPS
MAXIMUM
FLA
MAX
MAIN BREAKERMB
MC
CONTRACTORCONTR
EXISTING TO REMAIN
ELECTRIC WATER COOLER
MIMIMUM CIRCUIT AMPSMCA
MAXIMUM OVER CURRENT PROTECTION
MAIN LUG ONLY
EMERGENCYEM
POUNDS PER SQUARE INCHPSI
REVOLUTIONS PER MINUTERPM
HORSE POWERHP
GENERAL CONTRACTORGC
ABOVE FINISHED FLOORAFF
EX EXISTING
FLOW SWITCHFS
A
VOLTSV
UNLESS OTHERWISE NOTEDUON
LIGHTING
PANELBOARD SCHEDULE
ABBREVIATIONS
POWER NON-SEASONALPN
MOTOR SUMMER
MOTOR NON-SEASONAL
MOTOR NON-SEASONAL INTERMITTENT
MOTOR WINTER
MS
MN
MNI
MW
POWER WINTERPW
KITCHENKT
RECEPTACLER
L
ELECTRICAL SYMBOLS
SPECIAL EQUIPMENT COORDINATE W/SUPPLIER
JUNCTION BOX
DISCONNECT
OUTLET - 4 WAY
MOTOR
OUTLET - GROUND FAULT INTERRUPT
OUTLET - DUPLEX
RECESSED DOWN LIGHT
LIGHT FIXTURE - ON NIGHT LIGHT CIRCUIT
LAYIN TROFFER FIXTURE
SUSPENDED LAYIN
EXIT SIGNAGE
SURFACE MOUNTED STRIP LIGHT
SUSPENDED STRIP LIGHT
LOW VOLTAGE TWO LINE
LOW VOLTAGE ONE LINE
ANALOG PHONE LINE
WIRELESS ACCESS POINT
OUTLET - 220V
EXIT SIGNAGE WITH EMERGENCY HEADS
LIGHT FIXTURE - WALL SCONCE
LIGHT FIXTURE - PENDANT
SURFACE MOUNTED LAYIN
J
FLRFLOOR OUTLET WITH POWER, DATA AND PHONE
D
3
SWITCH
SWITCH WITH DIMMER
SWITCH - 3 WAY
OSSWITCH WITH OCCUPANCY SENSOR
CEILING MOUNTED OCCUPANCY SENSOR
4SWITCH - 4 WAY
OUTLET - GROUND FAULT INTERRUPT WEATHERPROOF WP
LOW VOLTAGE # LINES #
PUSH BUTTON
BUZZER B
TIME CLOCK TC
PHOTO CELL P
POWER POLE
PANEL DESIGATION
X: XX,XX,XX
CIRCUIT BREAKER NUMBERS
WAP
EMERGENCY LIGHTING UNIT
EMERGENCY EXIT EGRESS LIGHT
LIGHT FIXTURE - TRACK
LIGHT FIXTURE - UNDER COUNTER
LIGHT FIXTURE - RECESSED DOWN LIGHT
LIGHT FIXTURE - VANITY LIGHT
OUTLET - DUPLEX WITH USB
J
PP
OS
HS
WP
ELECTRICAL
ABBREVIATIONS,
SYMBOLS, &
SPECIFICATIONS
1. A SPRINKLER MONITORING FIRE ALARM SYSTEM THAT
ACTIVATES THE OCCUPANT NOTIFICATION SYSTEM
SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
WITH SECTION 907 OF THE IBC, NFPA 72 AND THE LOCAL
FIRE DEPARTMENT.
2. THE FINAL DESIGN FOR THE FIRE ALARM SYSTEM SHALL
BE BY A LICENSED FIRE PROTECTION CONTRACTOR
WITH A MINIMUM OF 5 YEARS EXPERIENCE. THE SYSTEM
SHALL BE FULLY ADDRESSABLE. FIRE ALARM DEVICES
ON THE PLANS ARE FOR INTENT ONLY. FINAL DESIGN
SHALL BE BY MINIMUM NICET III LICENSED DESIGNER
AND SHALL BE SUBMITTED AND APPROVED BY ALL
AUTHORITIES HAVING JURISDICTION. REGARDLESS OF
WHAT IS INDICATED ON THESE INTENT PLANS
CONTRACTOR SHALL PROVIDE ALL REQUIRED DEVICES
NEEDED FOR THE APPROVED SYSTEM AT NO
ADDITIONAL COST TO THE OWNER.
3. FIRE ALARM CONTRACTOR SHALL SUBMIT THEIR PLANS
FOR REVIEW AND APPROVAL BY AUTHORITY(S) HAVING
JURISDICTION AND SHALL BE RESPONSIBLE FOR
OBTAINING ALL REQUIRED APPROVALS AND PERMITS
AND FOR PASSING ALL REQUIRED INSPECTIONS.
4. GENERAL SPECIFICATIONS INCLUDE BUT ARE NOT
LIMITED TO THE FOLLOWING:
a. SYSTEM SHALL BE EQUIPPED WITH AUTOMATIC
EMERGENCY POWER WITH A MINIMUM 24 HOUR
SUPPLY.
b. DETECTORS SHALL INCLUDE SMOKE DETECTORS
(AREA AND DUCT) AND HEAT DETECTORS AS
REQUIRED.
c. CENTRAL ALARM NOTIFICATION DEVICES ARE
REQUIRED IN ALL APARTMENTS WITH LOW
FREQUENCY (520 HZ) AUDIBLE NOTIFICATION IN ALL
SLEEPING ROOMS. ALL DWELLING AND SLEEPING
UNIT NOTIFICATION DEVICES SHALL HAVE THE
CAPABILITY TO SUPPORT VISIBLE ALARM
NOTIFICATION. ALL ADA UNITS ARE REQUIRED TO
HAVE BOTH VISUAL AND AUDIBLE NOTIFICATION.
d. POWER TO FIRE ALARM CONTROL PANEL SHALL BE
PROVIDED WITH CIRCUIT BREAKER LOCK PER NFPA
72-13, SECTION 10.6.5.4 AND MARKED AS RED.
FIRE ALARM SPECIFICATIONS
220
LOW VOLTAGE DIMMING SYSTEMLV
DRAWING ISSUE HISTORY
ADLS ISSUE:
CONSTR ISSUE:
COPYRIGHT 2021
210422
JP
JP
AS NOTED
PROJECT NO:
DRAWING DATE:
DRAWN BY:
CHECKED BY:
DRAWING SCALE: CARMEL DETAIL CENTER4250 E 96th STREETINDIANAPOLIS, INDIANAA u t o m o t i v e G r o u pN BID / PERMIT ISSUE: MEP Consulting Engineers262 Tradewinds DriveSanta Rosa BeachFlorida 32459317.506.8151dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP:E:874 Cheltenham DriveAvon IN, 46123South OfficeNorth Office 11-10-21
11-10-21JEFFREY M . PE
R
KEY 11/10/2021
CANT AROUND TOP 1"
(8) #4 REBAR VERTICALY WITH #4 REBAR SPIRALED
AT 6" O.C. AND (3) LAYERS OF #4 REBAR AT TOP
AND BOTTOM OF BASE SPACED AT 2" O.C. MAINTAIN
MINIMUM OF 3" FROM REBAR TO EDGE OF
CONCRETE.
ANCHOR BOLTS
HAND HOLE
1. POLE SHALL BE CAPABLE OF WITH STANDING
130 MPH WIND GUSTS
2. CONCRETE SHALL BE MINIMUM 3000 PSI
3. MATCH ANCHOR BOLT PATTERN TO POLE
MANUFACTURERS BASE PLATE
#6 COPPER GROUND WIRE BONDED TO POLE.
5/8"X10' GROUND ROD WITH EXOTHERMIC
CONNECTION TO #6 GROUNDING CONDUCTOR.
NOTES
60"
GRADE
3/4" PVC
CONDUIT TO POLE
GROUND.
24"
1 NOT TO SCALE
LIGHT POLE DETAIL
36" In All areas
LIGHT POLE (LENGTH AS REQUIRED TO
ACCOMMODATE MOUNTING HEIGHT INDICATED ON
ELECTRICAL SITE PLAN.
12/28/21