HomeMy WebLinkAboutE002 - ELECTRICAL SCHEDULES, DIAGRAMSE002
ELECTRICAL DETAILS,
DIAGRAMS, &
SCHEDULES
DRAWING ISSUE HISTORY
ADLS ISSUE:
CONSTR ISSUE:
COPYRIGHT 2021
210422
JP
JP
AS NOTED
PROJECT NO:
DRAWING DATE:
DRAWN BY:
CHECKED BY:
DRAWING SCALE: CARMEL DETAIL CENTER4250 E 96th STREETINDIANAPOLIS, INDIANAA u t o m o t i v e G r o u pN BID / PERMIT ISSUE: MEP Consulting Engineers262 Tradewinds DriveSanta Rosa BeachFlorida 32459317.506.8151dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP:E:874 Cheltenham DriveAvon IN, 46123South OfficeNorth Office 11-10-21
11-10-21JEFFREY M . PE
R
KEY 11/10/2021
INTERIOR LIGHTING FIXTURE SCHEDULE
F1
TYPE DESCRIPTION MANUFACTURER MODEL FINISH
DL150931 - 4' LED STRIP WITH CHAIN KIT
F2
OWNER SUPPLIED / CONTRACTOR INSTALLED BLACK
BLACK
F3
F4
F5
F6
DL135726 - 4' LED HIGH BAY WITH CABLE KIT
DL150936 - 2X2 LED PANEL
DL150940 - LED DIFFUSE LIGHT BOX
BLACK
BLACK
BLACK
REFER TO CBMC DRAWING / SCHEDULE FOR DETAILS
REFER TO CBMC DRAWING / SCHEDULE FOR DETAILS
REFER TO CBMC DRAWING / SCHEDULE FOR DETAILS
REFER TO CBMC DRAWING / SCHEDULE FOR DETAILS
NEEWER PHOTOGRAPHY LED LIGHTING KIT
OWNER SUPPLIED / CONTRACTOR INSTALLED
OWNER SUPPLIED / CONTRACTOR INSTALLED
OWNER SUPPLIED / CONTRACTOR INSTALLED
OWNER SUPPLIED / CONTRACTOR INSTALLED
DL130643 - 4' VAPOR LIGHT - WALL MOUNT
NOT USED
PRIMARY CONDUITS
UTILITY
TRANSFORMER
M
A
PANEL
UTILITY
METER
TRANSFORMER T1
112.5 KVA, 480-120/208V
3Ø-4W
T
GROUND
HA
PANEL
PER NEC
3#3/0 A0L, #4G AL,
GROUND
PER NEC
4#500 MCM AL, #2G AL, 3-1/2"C
2"C
(2) 3-1/2"C, 4#500 MCM AL EA., #2/0G AL EA.
1 NOT TO SCALE
ELECTRICAL RISER DIAGRAM
HB
PANEL
JUNCTION BOX @ 4" A.F.F.
(2) 18 GA. WIRES BY E.C.
JUNCTION BOX @ 24" A.F.F.
(2) 18 GA. WIRES BY E.C.
JUNCTION BOX @ 4" A.F.F.
(2) 18 GA. WIRES BY E.C.
JUNCTION BOX @ 24" A.F.F.
(2) 18 GA. WIRES BY E.C.
PUSH BUTTON STATION BY
OHD, INSTALLED BY E.C.
(4) 18 GA WIRES BY THE E.C.
TOTAL OF (10) 18 GA. WIRES
ON THE SIDE WITH THE
PUSH BUTTON.
TOTAL OF (4) 18 GA. WIRES
ON THE SIDE WITHOUT THE
PUSH BUTTON.
E.C TO RUN ALL CONDUIT &
WIRES TO THE OPERATOR
LOCATION.
DETAIL NOTES:
1. ALL WIRES, CONDUIT, & J-BOXES BY THE E.C. LINE VOLTAGE WIRES, CONDUIT, &
CONNECTIONS BY THE E.C.
2. LOW VOLTAGE CONNECTIONS & SETUP FOR THE UP/DOWN LIMITS TO BY THE
OVERHEAD DOOR VENDOR.
3. PHOTOCELL @ 4" A.F.F. ARE TO PROTECT AGAINST HUMAN ENTRAPMENT PER UL-325
CODE.
4. PHOTOCELLS @ 30" ARE TO PROTECT VEHICLES.
(INSIDE LOOKING OUT)
FINISHED FLOOR
10" +/-10" +/-
3 SCALE: NO SCALE
MOTORIZED OVERHEAD DOOR DETAIL
BUILDING STEEL
NEC(250-52(A)(2)
BUILDING
WATER SERVICE
(METALLIC)
NEC 250-52(A)(1)
BUILDING
FOUNDATION
STEEL REBARS
NEC 250-52(A)(3)
INCOMING ELECTRICAL
SERVICE NO GROUND
CONDUCTOR CONSULT
LOCAL UTILITY
MAIN BONDING JUMPER,
PER NEC 250-28 (d) OR
INSTALLED AT FACTORY
BONDING BUSHING IF
METTALIC CONDUIT
(TYP.) NEUTRAL BUS
EQUIP. GRND. BUS
SERVICE EQUIPMENT
ENCLOSURE
NEC 250-66 NEC 250-66
NEC 250-66(b)
BRANCH PANEL
NEUTRAL
EQUIP.
GRND.
BUS
EQUIPMENT
GROUNDING
CONDUCTOR
NEC 250-122 TABLE
BONDING JUMPER
IF METTALIC
CONDUIT
MAIN EQUIP.
BONDING JUMPER
PER NEC 250-102(C)
OR INSTALLED
AT FACTORY
EQUIP. GROUND.
CONDUCTOR NEC
250-166 TABLE
122
BARE CU
IN PVC CONDUIT
NEC 250-66(A)
5/8"Ø X 10'-0" CU
CLAD STEEL
GROUND ROD(S)
NEC 250-52(A)(5)
2 SCALE: NO SCALE
ELECTRICAL GROUNDING DETAIL
ELECTRODE SIZING (NEC 250.66)
COPPER
<2
* TOTAL OF LARGEST OR SUM OF ALL PARALLEL
INCOMING UNGROUNDED PHASE CONDUCTORS.
#8
ALUMINUM
#6
GND CONDUCTORSERVICE ENTRANCE*
1 - 1/0 #6 #4
2/0 - 3/0 #4 #2
> 3/0 - 350 #2 1/0
> 350 - 600 1/0 3/0
> 600 - 1100 2/0 4/0
> 1100 3/0 250
COPPER ALUMINUM
<1/0
2/0 - 3/0
4/0 - 250
> 250 - 500
> 500 - 900
> 900 - 1750
> 1750
1-1/2"C, 4#1 AL, #6G AL
12/28/21