HVAC DETAILS
DRAWING ISSUE HISTORY
ADLS ISSUE:
CONSTR ISSUE:
COPYRIGHT 2021
210422
JP
JP
AS NOTED
PROJECT NO:
DRAWING DATE:
DRAWN BY:
CHECKED BY:
DRAWING SCALE: CARMEL DETAIL CENTER4250 E 96th STREETINDIANAPOLIS, INDIANAA u t o m o t i v e G r o u pN BID / PERMIT ISSUE: MEP Consulting Engineers262 Tradewinds DriveSanta Rosa BeachFlorida 32459317.506.8151dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP:E:874 Cheltenham DriveAvon IN, 46123South OfficeNorth Office 11-10-21
11-10-21
11/10/2021
30° MAX
O
CONCENTRIC
TRANSITION MAX, 45
DEG. DIVERGING AND
60 DEG. CONVERGING
OFFSET. PROVIDE MINIMUM 2"
STRAIGHT SECTION AT EACH
END. MAX 30 DEG.
ECCENTRIC TRANSITION
MAX, 30 DEG.
30° MAX
NOTE:
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
WHERE "R" IS EQUAL TO OR
GREATER THAN "A" MINIMUM
RADIUS (R) = 4 INCHES.
R=A
A
DUCT CONSTRUCTION DETAILSD
45 DEG.
OCL CONNECTION
TAKE OFF. HAMMER
LOCKED OR FLANGED AND
FULLY SEALED
RECTANGULAR
DUCT
BRANCH
AIR FLOWV.D.
45 DEG. HIGH EFFICIENCY
TAKE OFF COMPLETELY
SEALED
ROUND SHEET METAL
DUCT TO DIFFUSER
118"
NOTE:
DOUBLE THICKNESS
TURNING VANES TO BE USED
WHERE NORMAL RADIUS
ELBOW IS IMPRACTICAL
& WHERE ELBOW IS WITHIN 5
FT OF A
BRANCH TAKE-OFF.AIR FLOWSPIRAL DUCT
DOUBLE DEFLECTION REGISTER
WITH INTEGRAL OBD.
CURVED SPIRAL REGISTER DETAILO
NOTE: SEE DWGS FOR
DIRECTION
DIRECT MOUNT REGISTER WITH
DAMPER SEALED TO SPIRAL DUCT
WITH FULL PERIMETER BUTYL
GASKET AND #10 SCREWS 4" O.C.
UNIFORM PATTERN. ENSURE
CONNECTION IS AIR TIGHT.
0°-45°
GASKET
LAY-IN DIFFUSER DETAILK
SECURE FLEXIBLE DUCT TO
SUPPLY DIFFUSER ELBOW
FITTING WITH DRAWBANDS.
SHEET METAL ELBOW
SEAL ALL RIBS AND
CONNECTION TO
DIFFUSER NECK
SUPPLY DIFFUSER ACT CEILING
FLEX DUCT MAXIMUM LENGTH
SHALL NOT EXCEED 7'-0"
REFERENCE ARCHITECTURAL
REFLECTED CEILING PLAN AND
ELECTRICAL LIGHTING PLAN AND
COORDINATE INSTALLATION WITH ALL
CEILING ELEMENTS.
ROUND CHIMNEY TOP
METALBESTOS FLUE
RECOMMENDATIONS
MANUFACTURER'S
INSTALL PER
NOTE
FLASHING
ROOF
STORM COLLAR
METAL ROOF
AIR SPACE AROUND FLUE
LISTED
CONNECT TO APPLIANCE WITH B-VENT CONNECTOR
PIPING SLOPE AT MINIMUM 1/4" PER FOOT
IR FLUE DETAILH
CAULK WATER TIGHT
ATTACH TO
ROOF DECK
W/ #10 SHEET
METAL SCREWS
MINIMUM 36" ABOVE ROOF LINE
METALBESTOS CONNECTOR
ROUTED FULLY TO APPLIANCE
NO SINGLE WALL ALLOWED.
SCALE: NONE
MINIMUM 3'-6" ABOVE
ROOF LINE
SINGLE WALL DUCTING TO FAN.
STORM COLLAR
ROOF
METALBESTOS FLUE
SCALE: NONE
EXHAUST FAN TERMINAL DETAILL
LISTED
ROUND CHIMNEY TOP
METAL ROOF
FLASHING
METALBESTOS FLUE PIPE
BRACE TO STRUCTURE
STRUCTURAL MEMBER
ROOF MEMBRANE
24"
CONCENTRIC DETAILM
NOTE: MAINTAIN ALL
CLEARANCES PER IFGC
DIRECT VENTING
SECTIONS.
EQUIP MANUFACTURER SUPPLIED
CONCENTRIC ROOF VENT
RUBBER BOOT DECK FLASHING
DESIGN FOR ROOFING SYSTEM.
SPECIFICALLY
SEAL WITH POLYURETHANE BASED
SEALER, SIKAFLEX-221 OR EQUAL.
SILICONE SEALANT IS NOT
ACCEPTABLE
FIELD INSTALL PIPE
SUPPORT. BRACE TO
STRUCTURE
FIELD ROUTE PVC VENTING IN STRICT
ACCORDANCE WITH EQUIP. MANUF.
RECOMMENDATIONS.
MINIMUM 3'-0"
ABOVE ROOF
LINE
STORM COLLAR
ROOF
SEAL ALL JOINTS
DRYER GOOSENECK DETAILN
4" SPIRAL NO SCREENS
ON OUTLET
TALL CONE
METAL ROOF
FLASHING
NOTE
LENGTH NOT TO
MANUFACTURER'S
RECOMMENDATIONS
6" SPIRAL SLEEVE
BRACE TO UNDERSIDE OF ROOF
STRUCTURE
4" SPRIAL GASKETED DUCTING
RIVET ALL JOINTS AND SEAL WITH
HIGH TEMPERATURE SEALANT.
STORM COLLAR
ROOF
METALBESTOS FLUE
LISTED
ROUND CHIMNEY TOP
METAL ROOF
FLASHING
NOTE
INSTALL PER
MANUFACTURER'S
RECOMMENDATIONS METALBESTOS FLUE, SEAL WITH
HIGH TEMPERATURE SEALANT.
FRESH AIR DETAIL G
DO NOT REMOVE OR DEFACE THIS PLACARD
MANDATED BY IMC 504.6.5 & IRC MM1502.4.5
RISK OF FIRE
LOCATION IS FEET
Dryer Placard - Equal to part No. PLAC34 (888-443-7937) Post within 6'-0"
feet of dryer's exhaust duct connection. HVAC contractor to fill in duct
lenght for each individual installation taking into account the actual installed
equivalent length including fittings used.
THE MAXIMUM ALLOWABLE EXHAUST DUCT LENGTH
STATED IN THE CLOTHES DRYER'S INSTALLATION
INSTRUCTIONS SHALL BE EQUAL TO OR GREATER THAN
THE POSTED EQUIVALENT LENGTH INDICATED ON THIS
PLACARD.
THE NET EQUIVALENT* LENGTH
OF DRYER DUCT FROM THIS
E IR HEATER WIRING DIAGRAM
Relay Modual
IR Heater
120V #12 w/grd
IR Heater
IR Heater IR Blower
S-Black
Bulb
Sensor
OA
Sensor
(1) Shielded Stranded twisted
pair 2 C 18 AWG and (1) 4 C
Solid 18 AWG Cables in 34"
EMT. max 350 feet
Typical
Shielded 2 C 18 AWG
Cable in 34" EMT
on 4x4 box
10"x10" Nema 1 enclosure box
(1) Shielded Stranded twisted
pair 2 C 18 AWG and (1) 4 C
Solid 18 AWG Cables in 3
4"
EMT Max 350 feet.
IR Blower
IR Blower
Remote Smart Com
controller
IR Heater IR Blower
120V #12 w/grd
120V #12 w/grd
Heater Power feed
L1 L2 L3
460 1 PH to 120 1 PH
fused transformer
M
O/L
FUSE
O/L
M
MAN
AUTO
Armstrong AMD
CO Controller by
M.C.
G
M 115 V Interlock Power
to Motorized Actuator
on Intake Damper3 Ph Exhaust fan
460 V 3 Phase Combination Motor Starter
with 115 V Holding Coil and HOA Switch
with Pilot light by Electrical Contractor.
115 V #12 w.grd
Controller power
feed
J CO WIRING BLOCK DIAGRAM THREE PHASE
CO/NOx
Sensor
(2) SHIELDED STRANDED TWISTED PAIR 4 C
18 AWG CABLES IN 34" EMT BY E.C. SEE
PLANS FOR LOCATIONS TYPICAL.
IR Heater IR Blower
SLOPE DOWNWARDS TOWARDS BURNER BY APPROXIMATELY 1/2"
* *
* *
BEAM CLAMP
EYE HOOK
VERTICAL SUSPENSION
CHAIN IDEAL WHERE
SUPPORTS ARE INCLINED.
MAXIMUM RECOMMENDED
ANGLE OF INCLINATION IS
15 DEG.
WHERE CHAIN SUPPORTS
HAVE AN ANGLE OF
INCLINATION GREATER
THAN 15 DEG. AN EQUAL
AND OPPOSITE SUPPORT
IS RECOMMENDED.
* THESE ANGLES TO BE EQUAL
AND NOT MORE THAN 45°
CHAIN
('U' TYPE SHOWN)
55° SUSPENSION
NOTE:
REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS
AND INSTALL HEATER IN ACCORDANCE WITH ALL CLEARANCE
AND INSTALLATION RECOMMENDATIONS.
2/0 GA CHAIN
(TWISTED LINK,
PLATED) TYPICAL.
15°MAX
INFRARED HEATER INSTALLATION DETAILSF
M
SEDIMENT TRAP
FILTER RACK
FURNACE
3
4" PVC DRAIN, SLOPE AT MIN 1
4" PER
FOOT.
GALVANIZED SECONDARY DRAIN
PAN, EXTEND MINIMINUM 6"
PAST ENTIRE FURNACE AND DX
COIL BOX
UNI-STRUT RACKING FOR BOTH
DRAIN PAN AND FURNACE.
CONNECT TO STRUCTURE WITH 3
8"
RODS.
CAP AND PROVIDE WATER
SHUT OFF SWITCH
20" MIN
WORK AREA
PVC VENT PIPING. ROUTE
TO CONCENTRIC VENT
TERMINAL PER
MANUFACTURES
RECOMMENDATIONS
INSULATED OUTSIDE AIR
DUCT WITH MOTORIZED
AND MANUAL DAMPER.
ROUTE TO WALL CAP
REFRIGERATION PIPING.
INSTALL PER
MANUFACTURES
RECOMMENDATIONS
AC "N" DX COIL INSTALL
MANUFACTURES
DEFLECTION PLATE FOR
HORZ. APPLICATION.
MANUAL SHUTOFF
GAS VALVE AND
UNION
CONDENSATE
TRAP WITH
TOP CLEAN
OUT.
SCALE: NONE
HORIZONTAL FURNACE DEATILC
MIN. 8"
SLOPE
ROOF MOUNT ACCU DETAILB
PITCH POCKET
COORDINATE
LOCATION/TYPE WITH
ROOFING CONTRACTOR
INVERTED TRAP, PITCH
SUCTION LINE TOWARD
COMPRESSOR. PROVIDE
OIL RETURN TRAPS PER
MANUFACTURES PIPING
RECOMMENDATIONS.
MECHANICALLY FASTENED
LINE SETS VIA CUSH CLAMPS
AND TREATED 4x4'S
REFRIGERANT TUBING WITH 1/2" WALL MIN. ARMAFLEX INSULATION.
INSULATION LOCATED OUTDOORS SHALL BE PAINTED WITH UV
RESISTANT ARMAFLEX PAINT.
NEMA 3R DISCONNECT SIZED
AND INSTALLED PER NEC.
MOUNT TO SIDE OF UNIT
INSTALL ALL REFRIGERATION
SPECIALTIES AS INDICATED ON
EQUIPMENT SCHEDULES.
GALVANIZED EQUIPMENT RAIL
EQUIPMENT SUPPORTS LIKE
PATE EQ-1 WITH SLIP SHEET
UNDER RAIL SET ON ROOF
MEMBRANE
AIR COOLED CONDENSER
MOUNTED ON 2" SQUARE
VIBRATION PAD LIKE DIVERSITECH
#MP-2E ANTI-VIBRATION PAD
GFCI WHERE SHOWN ON
PLANS
HIGH WALL UNIT
DISCONNECT
BY E.C.
DUCTLESS MINISPLIT DETAILA
MINI-WHITE TANK MINI SPLIT
CONDENSATE PUMP WITH
HIGH LEVEL CUT OUT. WIRE
TO IDU PER MANUFACTURES
INSTRUCTIONS
1/2" HOSE TO OPEN SITE
HUB DRAIN PROVIDED BY
P.C.
PATE PORTAL ROOF CURB
TYPICAL ALL LINE SETS.
INSULATE AND SEAL
WATER TIGHT.
ALL PIPING SHALL BE SIZED PER
MANUFACTURERS RECOMMENDATIONS.
INSULATE SUCTION AND LIQUID LINES WITH 1/2"
WALL ARMAFLEX. ALL EXTERIOR INSULATIONS
SHALL BE PAINTED WITH UV RESISTANT
ARMASHIELD PAINT.
INVERTED SUCTION LINE
TRAP. SLOPE LINE BACK
TO COMPRESSOR.
AIR COOLED
CONDENSING
UNIT
GALVANIZED
EQUIPMENT RAIL
BY MC
INSTALL PER SPECIFICATIONS
AND MANUFACTURERS
RECOMMENDATIONS.
SCALE: NONE
SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
SCALE: NONE
SCALE: NONE
SCALE: NONE
SCALE: NONE
SCALE: NONE
SCALE: NONE
RETURN AIR DUCTING
SINGLE WALL DUCTING TO UNIT.
MINIMUM 3'-6"
ABOVE ROOF LINE
12/28/21