HomeMy WebLinkAboutM100 - FIRST FLOOR HVAC PLANT
IR-1
IR-2
IR-3
40/16 22"Ø20"Ø 10"ØT
T
RTU-1
EF-1
75
S-1
50
R-2
S-3
430
S-3
460
S-3
460
S-3
460
S-3
460
S-3
460
S-3
460
S-3
460
40/16
4" W.C.
IR-1
IR-2
EF-5
4600
EF-3
800
EF-4
4600
EF-6
250
EF-5
300
4" W.C.
S-1
50
S-2
250
10"Ø14"Ø 16"Ø 18"Ø 20"Ø
S-3
460
S-3
460
S-3
460
S-3
460
S-3
460
18"Ø 16"Ø 14"Ø
6"Ø
EF-1
75
30"Ø S-3
430
S-3
430
S-3
430
S-3
430
S-3
430
S-3
430
14"Ø 18"Ø16"Ø 20"Ø
S-3
500
S-3
500
S-3
500
S-3
500
S-3
500
S-3
500
18"Ø 16"Ø 14"Ø 12"Ø 22"Ø
IH-1
9200
FD
R-2
R-2
10/10
8/8
40/19 40/19
IR-1
DVB
EF-2
75
6"Ø
M
S-2
250 10/1210"Ø10"Ø
6"Ø
6"Ø
8"Ø UP
F-1
1.5 TON
22"Ø
22"Ø
30"Ø18"Ø 16"Ø 14"Ø
S-3
460
NOx COMS
AMDSC
CO
COSIM-1
S IR
MANIFOLD 1(117.9 °F)
MS-1
1 TON
T
T
M100
KEY NOTES: GENERAL NOTES:
FIRST FLOOR
HVAC PLAN
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEET M002 FOR SCHEDULES.
3. REFERENCE SHEET M003 FOR DETAILS.
N
1. ROUTE SUPPLY AND RETURN DUCTWORK FROM
ROOFTOP UNIT SHALL BE A MINIMUM OF 16" ABOVE
CAR WASH ROOF LEVEL. TYPICAL.
2. ROUTE SUPPLY 40/16 DUCTWORK THRU EXTERIOR
WALL. SEE SHEET M200 FOR DUCTWORK
CONTINUATION. TYPICAL.
3. ROUTE RETURN 40/19 DUCTWORK THRU EXTERIOR
WALL. PROVIDE WIRE MASH ON RETURN AT END OF
DUCTWORK AS REQUIRED. TYPICAL.
4. PROVIDE AND INSTALL TRANSFER GRILLE WITH FIRE
DAMPER AT 12" ABOVE FINISHED FLOOR
5. PROVIDE AND INSTALL FRANCE ABOVE CEILING AS
HIGH AS POSSIBLE. ROUTE CONDENSATE TO MOP
SINK .
6. PROVIDE AND INSTALL 8" B-VENT WITH RAIN CAP
FOR EXHAUST THROUGH ROOF. SEE DETAIL ON
M003.
7. PROVIDE AND INSTALL GOOSE NECK DRYER VENT
ON ROOF. SEE DETAIL ON M003.
8. PROVIDE AND INSTALL 6" B-VENT WITH RAIN CAP
FOR FRESH AIR. MAINTAIN A MINIMUM OF 10'-0" FROM
ALL EXHAUST OUTLETS. SEE DETAIL ON M003.
9. PROVIDE AND INSTALL SMART COM. IR
TEMPERATURE CONTROLLER WITH OA LOCK OUT
AND SIMULTANEOUS CONTROL OF ALL BAY
HEATERS. SEE M003 FOR DETAILS.
10. ARMSTRONG AMD CO/NOX REMOTE SENSOR
EMERGENCY VENTILATION SYSTEM CONTROLLER.
PROVIDE WITH REMOTE SENSORS. INTERLOCK CO
EXTRACTION FAN MOTOR STARTER TO BAY
EXHAUST FANS. REFERENCE SHEET M003 FOR MORE
INFORMATION.
11. CAR WASH EXIT SNOW AND ICE MELT SYSTEM. FIELD
VERIFY AND COORDINATE INSTALLATION AND SIZE
WITH G.C., SITE CONTRACTOR, AND M.C. ADJUST
LOOPS SIZE AND LOCATION AS NEEDED. ALL
INSULATION, PIPING, EQUIPMENT AND CONTROLS
ARE BY M.C. RACEWAYS ARE BY E.C.
12. COORDINATE LOCATION OF SIM EQUIPMENT WITH
ALL OTHER TRADES AND ADJUST LOCATION AS
NEEDED.
13. ROUTE CONDENSATE TO CLOSET DRAIN
COORDINATE WITH P.C. ON LOCATION.
#
DRAWING ISSUE HISTORY
ADLS ISSUE:
CONSTR ISSUE:
COPYRIGHT 2021
210422
JP
JP
AS NOTED
PROJECT NO:
DRAWING DATE:
DRAWN BY:
CHECKED BY:
DRAWING SCALE: CARMEL DETAIL CENTER4250 E 96th STREETINDIANAPOLIS, INDIANAA u t o m o t i v e G r o u pN BID / PERMIT ISSUE: MEP Consulting Engineers262 Tradewinds DriveSanta Rosa BeachFlorida 32459317.506.8151dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP:E:874 Cheltenham DriveAvon IN, 46123South OfficeNorth Office 11-10-21
11-10-21
11/10/2021
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR HVAC PLAN
12
3 3
4
8
5
7
6
9
10
3 SCALE: NONE
INFLOOR PIPING DETAIL
HYDRONIC HEATING DETAILS
CAPACITY DESCRIPTION AREA
FT2 MBTUH
NUMBER
OF LOOPS
LOOP
SPACING
560 3
GPM
LOOPSLOOP
PIPING
Type A
5/8" hepex
FT DP-FT
SIM 1
A/S
R S
M1
3/4"
ET-1
ZP-1
M-1
1-1/4"
6 loops
1-1/4"
BOILER
1-1/4"
EXH CA
A/S
3/4" PVC DRAIN
PRV
CND HOSE
2 SNOW MELT PIPING
TO PERVIOUS SOIL GRADERP-1
GLY-1
ET-1 EXPANSION TANK - EXTROL 30
SP-1 SNOW MELT CIRCULATION PUMP: GRUNDFOS
CAST IRON UPS26-99F-MED, 7.8 GPM @ 20 FT.
BOILER SIM WALL MOUNTED BOILER WITH
INTEGRATED PUMP. HIGH EFFICIENCY GAS
BOILER: IBC HC 29-106 MBH, 10 GPM @ 1.5' HD
WITH AUTO AIR VENT AND RELIEF VALVE.
120 12" max 190-2301.3 12
GPM
5
TOTAL
SEE PLANS FOR LOOP LAYOUTS AND ZONE LENGTHS.
3" PVC ROUTE UP THROUGH
ROOF JACKS PER
MANUFACTURERS
RECOMMENDATIONS.
TYPICAL TUBING TIE DOWN
4' TYP
CONCRETE SLAB
INSULATION BOARD BY SIM
CONTRACTOR INSTALLED
UNDER SLAB AND AT CAR
WASH EXIT TYPICAL FOR
ALL AREAS CONTAINING
TUBING.
SENSOR TUBING
ROUTE TO WALL
THERMOSTAT.
COORDINATE WITH E.C.
4"
MAX
REBAR AND WIRE MESH
GRID ELEVATED ONN
STAND OFFS. PLANE TO BE
APPROXIMATELY CENTER
OF SLAB DEPTH.
SECURE PIPING WITH STABLES AND
OR WIRE TIES, PRESSURIZE PRIOR
TO POUR AND MONITOR PRESSURE
DURING CONCRETE POUR
1-1/4"
1-1/4"
TEKMAR 654 SNOW
SOA/RAIN
S OUTDOOR TEMP
MELT CONTROLLERXFRM
XFRM
SEQUENCE OF OPERATION
BOILER
1. BOILER SHALL BE ENABLED BELOW 40 (ADJ)
OA TEMP.
2. ON CALL FOR SNOW MELT FIRE BOILER AND
MAINTAIN 120 (ADJ) WATER TEMPERATURE.
3. BOILER CONTROL SHALL BE INTEGRAL WITH
BOILER PACKAGE.
CAR WASH SNOW MELT / ICE MELT
1. TEKMAR 654 CONTROLLER SHALL ENABLE
SNOW MELT CONTROL BELOW OA TEMP OF 40
DEG (ADJ).
2. TEKMAR 645 SHALL MONITOR OA
TEMPERATURE, RAIN SWITCH, DOOR SWITCH
AND SLAB SENSOR AND SHALL CONTROL SLAB
TEMPERATURE ANYTIME OA TEMP IS BELOW
34 AND CAR WASH DOOR IS OPEN OR RAIN
SENSOR DETECTS MOISTURE.
J
S OA
5/8" PEX TUBING
O2 BARRIER TYPE
B-1
AIR SEPERATOR: SPIROL THERM 1-1/4" AIR
SEPARATOR.
GLYCOL FEEDER - WESSELS GLYMATICK
GMP-6 AUTO GLYCOL FILL STATION.
ET-1 EXPANSION TANK - WESSELS N-30, 4.8
GALLON, 3 GALLON ACCEPTANCE, 3.7 TOTAL
GALLON VOLUME
REHAU 1-1/4" XL (4) PORT SUPPLY AND
RETURN MANIFOLD, WALL MOUNTED,
INTEGRAL BALANCING VALVES/GAUGES.
GLYCOL
FEEDER
GLY
SCALE: NONE
12
11
13