HomeMy WebLinkAboutS411WELDED WIRE FABRIC SLAB "t"PER PLANVAPOR RETARDER/BARRIER COMPACTED GRANULAR DRAINAGE FILL PROOF-ROLLED & VERIFIED SUBGRADE 1. LOCATE WELDED WIRE FABRIC IN UPPER THIRD OF SLAB. SUPPORT ON BOLSTERS, CHAIRS, OR CONCRETE BRICKS. 2. LAP WELDED WIRE FABRIC A MIN. OF ONE FULL MESH SPACING. 3. THE USE OF NYLON OR POLYPROPYLENE FIBER IN LIEU OF WELDED WIRE FABRIC AS A SECONDARY REINFORCEMENT IS PERMISSIBLE, UNLESS OTHERWISE NOTED. NOTE: FIBER MAY NOT BE SUBSTITUTED FOR W.W.F. IN SUPPORTED SLABS. 4. SEE PLAN, NOTES, AND SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS SUCH AS FINISH, JOINTING, CURING, ETC. CONTROL JOINTS SHALL BE SAWN NOT LATER THAN THE FOLLOWING TABLE, OR 16 HOURS AFTER FINAL TROWELING (WHICHEVER IS LESS), WHERE TEMP EQUALS THE AMBIENT TEMPERATURE IN DEGREES FAHRENHEIT AT THEN TIME OF FINAL TROWELING. SAWCUTTING SHALL BE SUSPENDED ONLY IF THE LARGE AGGREGATE IS DISLODGED OR LOOSENED. ALTERNATE: USE PRE-FORMED JOINT FORMER. TEMP, DEG. F TIME, HOURS 40 50 60 70 80 90 <16 14 8 1/2 5 1/2 4 3 SLAB "t"PER PLAN1/8" W. X 1/4 SLAB "t" IN UNEXPOSED AREAS WHERE JOINTS WILL NOT BE FILLED. 1/4" W. X 1/4 SLAB "t" WET SAWCUT -SEE TABLE BELOW F.F. PER PLAN TOOL OR CHASE w/ SAWCUT SIM. TO CONTROL JOINT SLAB "t"PERPLAN8"2 '-0" FORMED KEYWAY W/ 3/4" DIA. x 18" LONG SMOOTH DOWELS @ 18" O.C., GREASE ONE END FOR BOND BREAK PROVIDE CONSTRUCTION JOINT IN LIEU OF CONTROL JOINT AT TERMINATION OF POUR 2 '-0" 3/4" CHAMFER, TYPICAL HOUSEKEEPING PAD -SIZE, LOCATION & HT. PER MEP DRAWINGS #4 @ 12" O.C. EACH WAY #4 w/ 6" HORIZ. LEGS @ 4'-0" O.C. (MIN. 1 PER CORNER) CNTR'D UNDER MAS. WALL (2) #5 x CONTINUOUS 8" CONCRETE SLAB ON GRADE PER PLAN INTERIOR NON-LOAD BEARING WALL, THICKNESS & LOCATION PER THE ARCHITECTURAL FLOOR PLANS. (TYPICAL @ ALL CMU WALLS WITHOUT FOOTINGS) NOTE: PROVIDE 2'-6" DOWELS ANCHORED INTO CONCRETE SLAB w/HILTI HIT-HY 200 ADHESIVE SYSTEM OR APPROVED EQ. (6" MIN. EMBEDMENT). DOWEL SIZE & SPACING TO MATCH SCHEDULED VERTICAL REINF. IF NOT INDICATED ON PLAN OR SCHEDULE, USE #5 DOWELS @ 32" O.C. CONCRETE SLAB ON GRADE PER PLAN REINF. PER PLAN & SCHEDULE SLAB CONSTRUCTION JOINT SEE TYPICAL DETAIL 8"3' -0" TYPICAL U.N.O. CNTR'D UNDER MAS. WALL 3' -0" TYPICAL U.N.O. BASE PLATE BY STAIR MANUF. STAIR STRINGER BY STAIR MANUF. ANCHORAGE BY STAIR MANUF. W.W.F. (3) -#4 EACH WAY BOTTOM 2' -6"1'-0"(3) -#4 EACH WAY BOTTOM STAIR POST BY STAIR MANUF. ANCHORAGE BY STAIR MANUF. W.W.F. 2' -6"1'-0" 1'-0" MIN. 1'-0" MIN. 1'-0" MIN. 1'-0" MIN. 1'-0" MIN.8" 8"F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN DEPTH OF RECESS/STEP OR DEPRESSION DEPTH OF RECESS/STEP OR DEPRESSION DEPTH OF RECESS/STEP OR DEPRESSION + SLAB THICKNESS FORMED KEYWAY CONCRETE SLAB ON GRADE PER PLAN FORMED KEYWAY CONCRETE SLAB ON GRADE PER PLAN CONCRETE SLAB ON GRADE PER PLAN 2" MAX.W.W.F. TO BE DEPRESSED OR LAPPED AT DEPRESSIONS REFER TO ARCH. PLANS & ROOM FINISH SCHEDULES FOR LOCATION & DEPTH OF RECESSED SLABS. COLUMN OR WALL FOOTING 1'-6" REFER TO M.E.P. DRAWINGS & SPECIFICATIONS FOR INFO. RELATING TO TRENCH EXCAVATION, BEDDING, AND BACKFILL FOR ANY EXCAVATION THAT MUST EXTEND BEYOND THIS LINE, SHORING MUST BE PROVIDED TO KEEP THE EXCAVATION FROM UNDERMINING THE FOUNDATIONS. 1V 1.5H NOTE: ANY SHORING SCHEME REQUIRED MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW, PRIOR TO EXCAVATION. PROTECTED ZONE SECOND POUR FIRST POUR 36 BAR DIA. LAP FORMED KEYWAY 1/3 1/3 1/3FTG. DEPTHPER SECTIONS(2) #5 x 3'-0" LONG AT JOINT 1'-6" 3" REINF. IN SAME SIZE & NO. AS FOOTING. LAP 36 BAR DIA. w/ FTG. REINF. SLOPE STEPPED CUT IF REQUIRED BY SOIL CONDITIONS T/F EL. -REF. PLAN "L" MIN. "D""H""D" "H""D""D"1. "H" DENOTES HEIGHT OF STEP AS SHOWN ON PLAN. 2. "L" DENOTES LENGTH BETWEEN STEPS. LAYOUT TO MAINTAIN SLOPE OF 1 VERTICAL TO 2 HORIZONTAL UNLESS NOTED OTHERWISE. 3. "D" DENOTES FOOTING DEPTH, REFER TO PLANS, SECTIONS & SCHEDULES. NOTES: 1.01.5 MAX.12" HORIZ. LEG TYPICAL CONTINUOUS FTG. REINF. PER SECTIONS FTG. DEPTHPER SECTIONSMAINTAIN MIN. 6" OF CONCRETE COVER ALL AROUND BARS TO MATCH FTG. REINF. W/ (4) #4 TRANSVERSE BARS x FOOTING WIDTH -6" PIPE SLEEVE 3" LARGER THAN PIPE DIAMETER LOOSE INSULATION NOTES: 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATION OF ALL UNDERGROUND PIPING. 2. PROVIDE THIS DETAIL WHERE A PENETRATION THROUGH A WALL FOOTING IS UNAVOIDABLE. 3. NO SLEEVES IN COLUMN FOOTINGS ARE PERMITTED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER. LC CONC. SLAB PER PLAN F.F. PER PLAN COLUMN BASE PLATE & ANCHOR BOLTSSTEEL COLUMN PER PLAN SEE SCHEDULE FOR SIZE & REINF.VARIESREFERENCE COLUMN ISOLATION JOINT DETAILS EQUAL EQUALSEE FOOTINGSCHEDULE EXTEND FOOTING DEPTH AS REQUIRED TO MAINTAIN MIN. 3" COVER AROUND BOTTOM OF ANCHOR BOLTS WHEN FOOTING DEPTH IS LESS THAN ANCHOR BOLT EMBEDMENT PAINT ALL STEEL BELOW GRADE w/ 2 COATS OF ASPHALTUM OR ENCASE IN MIN. 4" CONC. CL CONC. SLAB PER PLAN F.F. PER PLAN SEE SCHEDULE FOR SIZE & REINF. COLUMN BASE PLATE & ANCHOR BOLTS STEEL COLUMN PER PLAN 8" TYP.1/2" ISOLATION MATERIAL PAINT ALL STEEL BELOW GRADE w/ 2 COATS OF ASPHALTUM OR ENCASE IN MIN. 4" CONC.VARIES HOLD 1 1/2" FIRST (5) TIES SPACED 3" OC MAX. 4" REF. PIER SCHEDULE FOR REINF. SIZE & TIE SPACING BALANCE AT FULL SPACE EQUAL EQUALSEE FOOTINGSCHEDULE NOTE: ANCHOR ROD DETAIL SIM. FOR PRECAST COLUMNS. PIPE SLEEVE 3" LARGER THAN PIPE DIAMETER LOOSE INSULATION SEE STEPPED FOOTING DETAIL CONTIN. FOOTING REINF. PER SECTIONS/SCHEDULE NOTES: 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATOIN OF ALL UNDERGROUND PIPING. 2. STEP FOOTING FOR PIPE PENETRATION THROUGH FOUNDATION WALL UNLESS WRITTEN PERMISSION IS OBTAINED FROM THE MEP ENGINEER. 3. PROVIDE PRECAST OR BOND BEAM LINTEL FOR MULTIPLE PENETRATIONS OR OPENINGS GREATER THAN 24" IN WIDTH. NOTES: WHERE VERTICAL REINFORCING IS INTERRUPTED BY THE OPENING, HALF OF THE INTERRUPTED STEEL SHALL BE ADDED EACH SIDE OF THE OPENING. USE FULL LENGTH BARS. IF BARS CANNOT BE PLACED AS DETAILED, REPLACE THE 1'-6" EXTENSION WITH 6" AND A STANDARD HOOK. COORDINATE FINAL LOCATION OF MECHANICAL PENETRATIONS WITH MECHANICAL CONTRACTOR BEFORE INSTALLATION OF THE REINFORCING. THIS DETAIL APPLIES TO ALL SQUARE AND RECTANGULAR OPENINGS IN CONCRETE WALLS UNLESS OTHERWISE NOTED ON THE PLANS. 2 -#5 (1 EACH FACE) AT BOTTOM OF OPENING 2'-0" TYPICAL OR PROVIDE A STANDARD 90 HOOKo 2 -#7 (1 EACH FACE) AT TOP OF OPENING COORDINATE SLEEVES WITH MECHANICAL OPENING OPENING2 -#5 (1 EACH FACE) TYPICAL AT JAMBS2 -#5 x 4'-0" (1 EACH FACE)1'-6"1'-6" 2" CL.2 -#5 x LENGTH VARIES (1 EACH FACE) 45o COORDINATE SLEEVES WITH MECHANICAL. PROVIDE LINK-SEAL FOR ALL PENETRATIONS THRU BASEMENT WALLSNOTES: WHERE VERTICAL REINFORCING IS INTERRUPTED BY THE OPENING, HALF OF THE INTERRUPTED STEEL SHALL BE ADDED EACH SIDE OF THE OPENING. USE FULL LENGTH BARS. IF BARS CANNOT BE PLACED AS DETAILED, REPLACE THE 1'-6" EXTENSION WITH 6" AND A STANDARD HOOK. COORDINATE FINAL LOCATION OF PIPE PENETRATIONS WITH MECHANICAL CONTRACTOR BEFORE INSTALLATION OF THE REINFORCING. THIS DETAIL APPLIES TO ALL ROUND AND ELLIPTICAL OPENINGS IN CONCRETE WALLS, UNLESS OTHERWISE NOTED ONTHE PLANS. EXTERIOR FACE INTERIOR FACE 36 DIA.36 DIA.#5 @ 12" O.C. NOTE: AT "TEES" PROVIDE TWO HOOKED BARS NOTE: PROVIDE SIMILAR CORNER BARS FOR CONC. WALLS WITH ONE LAYER OF REINFORCEMENT. LOCATE ON OUTSIDE FACE & PROVIDE (3) #4 VERT'S FOR SUPPORT 36 DIA.36 DIA. 36 DIA. SLAB CONTROL JOINTS -SEE GENERAL NOTES, DTL. THIS SHEET, & FDN. PLAN FOR LOC'N. COLUMN BLOCKOUT SECONDARY POUR2 '-0" OR ASREQ 'D.WRAP BASE OF COLUMN w/ 1/2" ISOLATION JOINT MATERIAL & CAULK ISOLATION JOINT -1/2" PREFORMED JOINT MATERIAL OUTLINE OF BASE PLATE BELOW IN AREAS SUBJECT TO HIGH MOISTURE CONDITIONS, SUCH AS BELOW GRADE APPLICATIONS, THICKEN SLAB TO 8" MIN. SUBSTITUTE A COLD-JOINT WATERSTOP FOR THE 1/2" ISOLATION MATERIAL. 1. TUBE COLUMN SHOWN FOR ILLUSTRATIVE PURPOSES ONLY. WIDE FLANGES, PIPES, AND OTHER STEEL SHAPES ARE SIMILAR. 2. ADJUST 2'-0" DIMENSION AS REQUIRED TO ACCOMMODATE COLUMN BASE PLATES AND GROUTING PROCEDURES. 3. WHERE THIN-SET EPOXY TERRAZZO OR VINYL SHEET GOODS ARE THE SCHEDULED FLOOR FINISH, ELIMINATE THE DIAMOND-SHAPED ISOLATION JOINT AND EXTEND THE CONTROL JOINTS TO THE COLUMN. WRAP BASE OF COLUMN w/ 1/2" ISOLATION JOINT MATERIAL & CAULK OUTLINE OF BASE PLATE BELOW IN AREAS SUBJECT TO HIGH MOISTURE CONDITIONS, SUCH AS BELOW GRADE APPLICATIONS, THICKEN SLAB TO 8" MIN. SUBSTITUTE A COLD-JOINT WATERSTOP FOR THE 1/2" ISOLATION MATERIAL. NOTE: THIS DETAIL SHOULD BE USED IN LIEU OF A DIAMOND OR ROUND ISOLATION JOINT TO PREVENT TELEGRAPHING THROUGH FINISH FLOOR MATERIALS SUCH AS THIN-SET TERRAZZO, CERAMIC TILE, VINYL TILE, ETC. SOME MINOR RANDOM SHRINKAGE CRACKS SHOULD BE ANTICIPATED. DETAIL IS SIMILAR AT WIDE-FLANGE COLUMNS. SLAB CONTROL JOINTS -SEE GENERAL NOTES, DTL. THIS SHEET, & FDN. PLAN FOR LOC'N.ARCHITECTCLIENT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS ENGINEERTHE SIGNATURECARMELCARMEL, INTYPICAL DETAILS -FOUNDATIONS20010 4/23/2021 PERMIT SET S411 NOT TO SCALE 1 SLAB ON GRADE CONSTRUCTION NOT TO SCALE2SLAB CONTROL/CONTRACTION JOINT NOT TO SCALE3SLAB CONSTRUCTION JOINT NOT TO SCALE4MECHANICAL EQUIPMENT PAD DETAIL NOT TO SCALE 5 THICKENED SLAB DETAILS NOT TO SCALE6THICKENED SLAB AT STAIR POSTS NOT TO SCALE 8 RECESSED SLAB DETAIL NOT TO SCALE7EXCAVATION LIMITS DETAILS NOT TO SCALE9 WALL FOOTING CONSTRUCTION JOINT NOT TO SCALE10STEPPED FOOTING DETAIL NOT TO SCALE11WALL FOOTING SLEEVE DETAIL NOT TO SCALE 12 TYPICAL INTERIOR COLUMN FOOTING NOT TO SCALE 13 INTERIOR COLUMN FOOTING W/ PIER NOT TO SCALE14 CMU FOUNDATION WALL PIPE SLEEVE DETAIL NOT TO SCALE15C.I.P. WALL RECTANGULAR OPENING NOT TO SCALE16 C.I.P. WALL ROUND OPENING NOT TO SCALE 17 C.I.P. WALL CORNER REINFORCING NOT TO SCALE 18 COLUMN ISOLATION JOINT DETAIL NOT TO SCALE19 COLUMN ISOLATION JOINT DETAIL 10/12/21