December 15, 2005
Mr. Jeff A volt
Ryland Homes
9025 North River Road, Suite 100
Indianapolis, IN 46250
Re; Lot 131, Claybourne, Cannel
P.O. 43-26179
Dear Mr. A volt:
430 Not1h RangeUne Road (46032)
POBox 742
Cannel, Indiana46082-0742
317.581-8877
JI7.58J.8856Fax
,r-nqYl\
V~~
As you requested, 1 inspected the fuuning in the garage of this home under COnstructiOlL The framing of
the house resulted in the stud wall on the east side of the garage overhanging the foundation wall for
distances ranging fiom % to I Y, inches. For most of the 33-foot wall, the overhang is about one inch.
The bottom of the plate is about 5 }Ii inches above the garage floor.
Your suggestion to attach short lengths of treated 2 x 65 to the wall under each stud will provide the
necessary strength and stability to the wall. Each piece should be cut to fit snugly between floor and
bottom plate.
Please let me know if you have any questiollS.