HomeMy WebLinkAbout42230026 - GR2 80 - Truss DetailsDE DANSCO ENGINEERING, LLC P.O. Box 3400 Apollo Beach, FL 33572 Telephone (813) 645-0166 Facsimile (813) 645-9698 The truss drawing(s) attached have been prepared by Dansco Engineering, LLC under my direct supervision and control based on the parameters provided by Stark Truss Inc. Job: 2107059-12T 28 truss design(s) 86850-W1 09/16/2021 Samuel A. Greenberg, P.E. Indiana Reg. #19700485 Indiana Residential Building Code 2020 based on IRC 2018 with Indiana specific amendments. 675 IAC 14-4.4-81 Section R802.10.1; truss design drawings, R802.10.1; truss design drawings shall be provided to the building official as required by the General Administrative Rules (675 IAC 12) for Class 1 structures or by local ordinance for Class 2 structures. Note: Gable end frames with stud lengths exceeding 4’ require permanent bracing. On structural gables, where studs may be made from two or more boards as they cross diagonals, the 4’ length is the distance from the top chord to bottom chord. The seal on these drawings indicate acceptance of professional engineering responsibility solely for the truss components shown. The suitability and use of this component for any particular building is the responsibility of the building designer, per ANSI/TPI 1-2014 Chapter 2. Warning !—Verify design parameters and read notes before use. These designs are based only upon parameters shown, and are for individual building components to be installed and loaded vertically. Applicability of design parameters and proper incorporation of component is responsibility of building designer – not truss designer or truss engineer. Bracing shown is for lateral support of individual web members only. Additional temporary bracing to ensure stability during construction is the responsibility of the erector. Additional permanent bracing of the overall structure is the responsibility of the building designer. For general guidance regarding fabrication, quality control, storage, delivery, erection and bracing, consult ANSI/TPI 1 National Design Standard for Metal Plate Connected Wood Truss Construction and BCSI 1-03 Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses from Truss Plate Institute, 583 D’Onofrio Drive, Madison, WI 53719 DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ªŁ˝ Œ¤ ªŒ¤Ł ª¤ ª¤º ªŒ¤Ł ª¤Œ ª¤ ª¤º ª¤ ªŒ¤Ł ªŁ˝ Œ¤ Œ Ø Ł º Ł Ø Œ º º º ºº Œ ºØºØ ºØ ºº ºº ºººŒ ºŒ ŒŒØØ ˝‰¿·» ª —·¿‹» ””›»‹› ł¨ ˙¯Ł…„»ºŁˆ ¯Ł ºˆ ¯ºŒ ˆ ¯Ł ºˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŒŒ ˚»fi‹ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł Ł Ł˝Øæ ˛» ˝‹fi»›› †‰fi Ł –fiƒł Ł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ Ł · ª ß ¸˛ — ˛¤ ˝— – ˛¤Ł ˝— ˝¤ ˝— ˝‹«… ¤‰»‹ º¤ ˝— – ¤Œ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ ˛˝ł·æ›•ƒ»ŁªºŁØŁæŒ ł‡•† ªºŒŒæŒ ł‡•† ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹Łª ł ª ł ¿¤ fi¿“ŁªŒŒØ ł ªŒØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªŁŒæ ªŒŁŒæŁ ªŒØæ ºªŒØæ ººªŒŁŒæŁ ºŒªŁØæØº ªºŒŁæ ŒŁ ªºŁæŁØº ˛ŒªæŁŁŁ ŒØªæŁŁŁ ØªæŁŁŁ ŁªŒŁæØ Ł ªŒŁæØ ªŒŁæØ ªŒŁæØ ªŒŁæØ ªŒæØŁ ªŒæØŁ ªŒæØŁ ªŒæØŁ ªæ ºªæ Łºªæ ˝ªŁØæºØº ºªºŁæ ºªŒæØ ªºŒŁæ ªæ ªŒæŒŒº Œ ªŒæŒºŁ ˝ ·§ ‹fi«›› ‹– » ‰–††»‰‹»… ‹–„»‹‚»fi '•‹‚ … ł ¤ †¿•·› ¿› ”–··–'› – ‰‚–fi…› ‰–††»‰‹»… ¿› ”–··–'› ¤ fi–' ¿‹ Œ –‰ ¤Œ fi–'› ›‹¿„„»fi»… ¿‹ –‰ –‹‹–‡ ‰‚–fi…› ‰–††»‰‹»… ¿› ”–··–'› ¤Ł fi–'› ›‹¿„„»fi»… ¿‹ Ł –‰ » ‰–††»‰‹»… ¿› ”–··–'› ¤ fi–' ¿‹ –‰ ·· ·–¿…› ¿fi» ‰–†›•…»fi»… »fl«¿··§ ¿·•»… ‹– ¿·· ·•»› »¤‰»‹ •” †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ”¿‰» •† ‹‚» ˝ł˝ ›»‰‹•–† —·§ ‹– ·§ ‰–††»‰‹•–†› ‚¿“» »»† fi–“•…»… ‹– …•›‹fi•«‹» –†·§ ·–¿…› †–‹»… ¿› ł –fi ł «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ º ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª Œ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Ł ·· ·¿‹»› ¿fi» ·¿‹»› «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ¿†„»fił› –fi –‹‚»fi ‰–††»‰‹•–† …»“•‰»ł› ›‚¿·· » fi–“•…»… ›«””•‰•»†‹ ‹– ›«–fi‹ ‰–†‰»†‹fi¿‹»… ·–¿…ł› ØØ · …–'† ¿†… Ł · « ¿‹ ØØº · …–'† ¿†… · « ¿‹ ØØº · …–'† ¿†… · « ¿‹ º ŁŒ · …–'† ¿†… º · « ¿‹ Ø Œ · …–'† ¿†… Ø · « ¿‹ Ø Œ · …–'† ¿†… Ø · « ¿‹ Œ · …–'† ¿†… Ø · « ¿‹ Ø · …–'† ¿†… Ø · « ¿‹ Ø · …–'† ¿†… Ø · « ¿‹ º ¿†… Ø · …–'† ¿†… Ø · « ¿‹ Ø ¿†… Ø · …–'† ¿†… Ø · « ¿‹ –† –‹‹–‡ ‰‚–fi… ‚» …»›•„†æ›»·»‰‹•–† –” ›«‰‚ ‰–††»‰‹•–† …»“•‰»ł› •› ‹‚» fi»›–†›••·•‹§ –” –‹‚»fi› –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º–‡‡–† •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» '‰˘'—˛ƒÆfi§fi†ÆŁ§‰””·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚§Ł–flfi‰‚ØØ¨˙§… –†‹•†«»… –† ¿„» DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº ªº Œ ªº ŒØ ªº Łª –†‰»†‹fi¿‹»… –¿…› ł· ˚»fi‹ ªº ł Œ ªØ ł ØªØŁ ł Ł ªØŁ ł ªØ ł ªº ł ªº ł ªŒ ł ªŒ ł ªŒ ł ºªŒ ł –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º–‡‡–† •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» '‰˘'—˛ƒÆfi§fi†ÆŁ§‰””·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚§Ł–flfi‰‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤Œ ª¤ ª¤ ªŒ¤Œ ªº¤ ªŁ¤Ł ªŒ¤Ł ªº¤Œ ª¤Œ ª¤Ł ªŒ¤Œ ª¤ Ł Ø ØŒ Łºº Œ Ø ŁºŒ ºŁ Œ Ł Ł º ŁŒŁ º Ł ºŁ ºŁ Œ º Ł ºØŁ ŁŁ ºŁºØº˝‰¿·» ª Ł —·¿‹» ””›»‹› ł¨ ˙¯ºˆ ¯Øˆ ¯Ł …„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŒ ˚»fi‹ł Øæ ˝†–' ł—”æ—„æ «‡»fi ºØŒ ˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi ŒØ –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ ¤Œ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªºŒæŒ ł‡•† ªŁæŒ ł‡•† ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹ªØ ł ª ł ¿¤ fi¿“ªŁØ ł ªº ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªæŒŒ ºªºæŁ Œ ºŒªººæŁØ ŒªºØæŁØ تºŒºæŁ ØŁªºŒæŁ ºŁªºŒæŁ ºŒªæŒ ŒªŒæº ªºØæº ØªæŒ ªØæ ØªŁæºº ˛ªŁæŒ ªŁæŒ ªŁ æŒ ªºŒæº ªºŒæº ªºŒæº ªºŒæ º ˝ªæŁ ªØæºŒ ªŒæØŒ ºªæŒ ºªºæ ŒªºæŒ ªæ ØªæŒ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… Ø · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ¿†„»fił› –fi –‹‚»fi ‰–††»‰‹•–† …»“•‰»ł› ›‚¿·· » fi –“•…»… ›«””•‰•»†‹ ‹– ›«–fi‹ ‰–†‰»†‹fi¿‹»… ·–¿…ł› º · …–'† ¿†… · « ¿‹ Ł Ø · …–'† ¿†… Œ · « ¿‹ º ¿†… Ø · …–'† ¿†… Œ · « ¿‹ Ø ¿†… Ø · …–'† ¿†… Œ · « ¿‹ –† ‹– ‰‚–fi… ¿†… º · …–'† ¿†… · « ¿‹ Ł · …–'† ¿†… · « ¿‹ º · …–'† ¿†… · « ¿‹ Ø ¿†… · …–'† ¿†… · « ¿‹ ¿†… Ł · …–'† ¿†… Ø · « ¿‹ Ø –† –‹‹–‡ ‰‚–fi… ‚» …»›•„†æ›»·»‰‹•–† –” ›«‰‚ ‰–††»‰‹•–† …»“•‰»ł› •› ‹‚» fi»›–†›••·•‹§ –” –‹‚»fi› † ‹‚» ˝ł˝ ›»‰‹•–† ·–¿…› ¿·•»… ‹– ‹‚» ”¿‰» –” ‹‚» ‹fi«›› ¿fi» †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº ªº ºªŒ ºŒªº ŒØªº ØŁªº ª –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿· •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˇ†'Æ›¶«¤†º¿›‡§‰`¶”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚ƒ–·¸‰º¶‚ØØ¨˙§… –†‹•†«»… –† ¿„» DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. –†‰»†‹fi¿‹»… –¿…› ł· ˚»fi‹ ª ł ª ł ºªŁ ł Œ ªŁ ł ØªŁ ł ª ł ª ł ª ł ªŁ ł –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿· •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˇ†'Æ›¶«¤†º¿›‡§‰`¶”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚ƒ–·¸‰º¶‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ªº¤ ª¤ ª¤ ªŒ¤Œ ª¤Ł ªº¤ªŒ¤Œ ª¤ ª¤ªº¤ Ø Ł Ł Ø Œ ºŒ º º ŁŁ ŁŁ ŁŁŁ ºŁ Ł ØŁ Œ Œ Œ ºŁºØººººº˝‰¿·» ª Œ —·¿‹» ””›»‹› ł¨ ˙¯º…„»ˆ ¯ºº…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł Øæ ˝†–' ł—”æ—„æ «‡»fi ºº˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi –fiƒł Ł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤— »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ŁªŁ æŒ ł‡•† Ł ªŁ æ Œ ł‡•† Ł ¿¤ –fi•ƒªŒØ ł ¿¤ ¸·•”‹ŁªŒ ł ªŒ ł Ł ¿¤ fi¿“Łªº ł Œ ªº ł Œ ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªŁæ ªŁæ ªŁæ ªŁæ ºªŁæ ºŒªŁæ ºŒªŁæ ºŒªŁæ ªººæ ŒŁ ªººæ ˛ØªŁØæº ØªŁØæº ŁªØ æº ŁªØæº ˝ªºæºº ªæº ºªŒæºº ªæŒ Œ ªæŒ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Œ · «·•”‹ ¿‹ ¶–•†‹ ¿†… Œ · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ¿†„»fił› –fi –‹‚»fi ‰–††»‰‹•–† …»“•‰»ł› ›‚¿·· » fi–“•…»… ›«””•‰•»†‹ ‹– ›«–fi‹ ‰–†‰»†‹fi¿‹»… ·–¿…ł› Œ · …–'† ¿†… Ø · « ¿‹ Ł Ł º · …–'† ¿†… º · « ¿‹ Ł º · …–'† ¿†… º · « ¿‹ ºŁ ¿†… º · …–'† ¿†… º · « ¿‹ ØŁ ¿†… Œ · …–'† ¿†… Ø · « ¿‹ Ø Ł –† ‹– ‰‚–fi… ¿†… · …–'† ¿†… Œ · « ¿‹ ŁŁ · …–'† ¿†… · « ¿‹ Ł · …–'† ¿†… · « ¿‹ ºŁ ¿†… · …–'† ¿†… · « ¿‹ ØŁ ¿†… · …–'† ¿†… Œ · « ¿‹ Œ –† –‹‹–‡ ‰‚–fi… ‚» …»›•„†æ›»·»‰‹•–† –” ›«‰‚ ‰–††»‰‹•–† …»“•‰»ł› •› ‹‚» fi»›–†›••·•‹§ –” –‹‚»fi› † ‹‚» ˝ł˝ ›»‰‹•–† ·–¿…› ¿·•»… ‹– ‹‚» ”¿‰» –” ‹‚» ‹fi«›› ¿fi» †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº ªº ºªŒ ºŒªº ŒØªº Łª –†‰»†‹fi¿‹»… –¿…› ł· ˚»fi‹ ª ł ª ł ª ł Ø ª ł Łª ł –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º• •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ‡¸›‚‡¨ƒŁ‹†ƒ”‹§‰`”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚˙–«§‰¸‚Ø Ø¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. ª¤ª¤ º Ø Œ º º ºØ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŁ ˚»fi‹ł ºØæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł ºŁ ˛» ˝‹fi»›› †‰fi –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi º –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ »‰‚¿†•‰¿· ł‡•† Ł ªæ »‰‚¿†•‰¿· ł‡•† Ł ºªŁºæŁ ł‡•† Ł ¿¤ –fi•ƒºªØ ł ¿¤ ¸·•”‹ªº ł ªØ ł ºª ł Ł ¿¤ fi¿“ªŒº ł ªŒŁ ł Ø ºªº ł Ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Œ ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ º º · «·•”‹ ¿‹ ¶–•†‹ ¿†… Ø · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— •†…•‰¿‹»› … łŁ ¤ –fi … ł Ł ¤º ‹–»†¿•·› »fi ˝ „«•…·•†»› † ‹‚» ˝ł˝ ›»‰‹•–† ·–¿…› ¿·•»… ‹– ‹‚» ”¿‰» –” ‹‚» ‹fi«›› ¿fi» †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº –†‰»†‹fi¿‹»… –¿…› ł· ˚»fi‹ ŒªŁØ łª ª ت łª ª fi¿»ƒ–•…¿· –¿…› ł·æ”‹ ˚»fi‹ ª łª ª‹–Œª łªº ªº Œª ł ªº ªº‹–ªºŒ łª ª ºª łª ª‹–ØªŁ łªŒ ªŒ ØªŁ łªŒ ªŒ ‹–ª łª ª –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º•¿„–†¿· • •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» Æ ”º‚”—¨¿˝—ƒ`Ł ‡˛§‰Æ”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚…–«‰‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ªº¤ªº¤ª¤ º Ł ŁØ˝‰¿·» ª º –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŒ ˚»fi‹ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤Œ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ł –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªØæ »‰‚¿†•‰¿· ł‡•† Ł ªØæŒ ł‡•† Ł ¿¤ –fi•ƒªŒ ł ¿¤ ¸·•”‹ªŁº ł ªº ł ¿¤ fi¿“ª ł Ł ª ł Ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› º˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Œ —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ º · «·•”‹ ¿‹ ¶–•†‹ ¿†… Łº · «·•”‹ ¿‹ ¶–•†‹ Ø ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— Ł ¿†„»fił› –fi –‹‚»fi ‰–††»‰‹•–† …»“•‰»ł› ›‚¿·· » fi–“•…»… ›«””•‰•»†‹ ‹– ›«–fi‹ ‰–†‰»†‹fi¿‹»… ·–¿…ł› · …–'† ¿†… Œ · « ¿‹ –† –‹‹–‡ ‰‚–fi… ‚» …»›•„†æ›»·»‰‹•–† –” ›«‰‚ ‰–††»‰‹•–† …»“•‰»ł› •› ‹‚» fi»›–†›••·•‹§ –” –‹‚»fi› † ‹‚» ˝ł˝ ›»‰‹•–† ·–¿…› ¿·•»… ‹– ‹‚» ”¿‰» –” ‹‚» ‹fi«›› ¿fi» †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº ª –†‰»†‹fi¿‹»… –¿…› ł· ˚»fi‹ ºª ł –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ºØ º¿‰·–›»… •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» •›‡…•¤˘Ø§‰`‹Ø¤'‹–˘¸·Ł†•˙†'•˝fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. ªº¤ªº¤ º Ł Ł ŁØ˝‰¿·» ª Ø –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŁ ˚»fi‹ł ºØæ ˝†–' ł—”æ—„ºæ «‡»fi ºŒ ˚»fi‹ł ºŁ ˛» ˝‹fi»›› †‰fi –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ Ł · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ł –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ »‰‚¿†•‰¿· ł‡•† Ł ªæ »‰‚¿†•‰¿· ł‡•† Ł ºªæŁ ł‡•† Ł ¿¤ –fi•ƒºªº ł ¿¤ ¸·•”‹ªº ł Œ ª ł ºªŒØ ł Ł ¿¤ fi¿“ªº ł ªº ł Ø ºªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Œ ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ ŒØ · «·•”‹ ¿‹ ¶–•†‹ º º · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— † ‹‚» ˝ł˝ ›»‰‹•–† ·–¿…› ¿·•»… ‹– ‹‚» ”¿‰» –” ‹‚» ‹fi«›› ¿fi» †–‹»… ¿› ”fi–†‹ ł –fi ¿‰ ł ˝ł˝ ˝‹¿†…¿fi… »¿… ı ˝†–' ł¿·¿†‰»… «‡»fi †‰fi»¿›»ªº —·¿‹» †‰fi»¿›»ªº ¸†•”–fi‡ –¿…› ł·æ ”‹ ˚»fi‹ ªº fi¿»ƒ–•…¿· –¿…› ł·æ”‹ ˚»fi‹ ª łª ª‹–ª łª ª ºª łª ª‹–ª łª ª –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ŒØº•¿„–†¿· • •fi…»fi – ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˛˘fifl‰…¨·§‰`ˇØ¤'‹–˘¸·Ł†•˙¸…•˝fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤º ª¤ ª¤ ª¤ ªº¤Œ ª¤º º Ł Ø Œ º Ł Œ Ø ºŒ ºŒ Ø Ø ŁŁ ˝Ł ˝Ø ˝Œ ˝º ˝ ˝ ˝ ˝ ˝Ø ˝Œ ˝º ˝ ˝ ˝ ˝ Œ Œ Œ ØŁ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi ºº˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝Ø –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛˝¤ ˝— ˝‹«… ¤‰»‹ ˝Ł˝Ø¤ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ ˝ ˛–' ¿‹ ‡•…‹Ø •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝·· »¿fi•†„› ł· ¿¤ –fi•ƒºªº ł º ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› º Œ º »¤‰»‹ ª ł Ø ª ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› º Œ Ø º ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ŁØªŁ ºæºº Łªæ ªæŁ ªŒæº ªØæº ªæØ ŁªŁØæºØ Łªæº ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… –fi†»fił ‹– ¤‹»fi•–fił ‹– Œ –fi†»fił˛ Œ ‹– Ø Œ ¤‹»fi•–fił Ø Œ ‹– Ł ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ fi«›› …»›•„†»… ”–fi '•†… ·–¿…› •† ‹‚» ·¿†» –” ‹‚» ‹fi«›› –†·§ –fi ›‹«…› »¤–›»… ‹– '•†… ł†–fi‡¿· ‹– ‹‚» ”¿‰» ›»» ˝‹¿†…¿fi… †…«›‹fi§ ¿·» †… »‹¿•·› ¿› ¿·•‰¿·» –fi ‰–†›«·‹ fl«¿·•”•»… «•·…•†„ …»›•„†»fi ¿› »fi ˝æ— ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª º¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Ø ·· ·¿‹»› ¿fi» º¤ «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ł ¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ fi«›› ‹– » ”«··§ ›‚»¿‹‚»… ”fi–‡ –†» ”¿‰» –fi ›»‰«fi»·§ fi¿‰»… ¿„¿•†›‹ ·¿‹»fi¿· ‡–“»‡»†‹ ł•» …•¿„–†¿· '» ¿·» ›‹«…› ›¿‰»… ¿‹ –‰ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› º Œ º »¤‰»‹ ł¶‹ª· ª ª ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º–‡‡–† ˝«–fi‹»… ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ƒ•˝§·«Ł¶†˝ƒ§‰—Ø˘‡˝Ł§¸‡“˝Łƒ‚Œ'›‹‡¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ª¤Ł ª¤ ª¤ ª¤ºª¤ª¤ª¤ ª¤ ª¤ ª¤ ª¤ ª¤Ł ª¤ ª¤º ª¤ºŁ Ø Œ º Ł Ø º Œ Œ ŁØ º º º º Œ ŁØ ˝ ˝ ˝ Œ Œ Ø ŒŒ º Ł ºØº Ł Œ Œ Œ º Ł Œ Œ º Ł ºØŁ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯Łˆ ¯Œ…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºº˚»fi‹ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi ˙˝ºŁ –fiƒł Œ †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ Œ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ ¤ ˝— ˝‹«… ˝¤ ˝— ˝‹«… ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝·· »¿fi•†„› ØŒ »¤‰»‹ ª »‰‚¿†•‰¿· ł· ¿¤ –fi•ƒªŒØ ł ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› »¤‰»‹ ª ł Ø ØªØ ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› Ł »¤‰»‹ ªŁŁ ł ØªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ŒªºæØ Œªæ ØªØæ تŒŒŒæ ºªŒ ºŁæØ ºŁªØºæŁ Ł ªØæ ŒªŁæ ŒØªæº Øªæ ŁªŁºæ Łªæ ªŁØæº ˛ªØæŁº ªæØº ˝ŒªºæŁ ªæ Œªººæ Œªæ Ł ªæ Œ ªæ ŒªŒ 挌 ØªŁŁæ ŒªºæŒŁ ªŁæØ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił Ø ‹– ºØ †‹»fi•–fi ł ºØ ‹– Œ ¤‹»fi•–fił˛ Œ ‹– ØŒ †‹»fi•–fi ł Ø Œ ‹– Ł ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ fi«›› …»›•„†»… ”–fi '•†… ·–¿…› •† ‹‚» ·¿†» –” ‹‚» ‹fi«›› –†·§ –fi ›‹«…› »¤–›»… ‹– '•†… ł†–fi‡¿· ‹– ‹‚» ”¿‰» ›»» ˝‹¿†…¿fi… †…«›‹fi§ ¿·» †… »‹¿•·› ¿› ¿·•‰¿·» –fi ‰–†›«·‹ fl«¿·•”•»… «•·…•†„ …»›•„†»fi ¿› »fi ˝æ— ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ º¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† Œ ·· ·¿‹»› ¿fi» º¤ «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ø ¿·» ›‹«…› ›¿‰»… ¿‹ –‰ Ł ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› »¤‰»‹ ł¶‹ª· ª تŒ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿· ˝‹fi«‰‹«fi¿· ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» `•„˘˝Æ¨˚¨ˇ§§»‡§‰—˘‡˝Ł§¸‡“˝Łƒ‚Œ›˚‹”'¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ª¤ºª¤ª¤ Œ º Ø Ł Ł Œ ØŒ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ºªŁæ ł‡•† Ł Œªæ ł‡•† Ł ¿¤ –fi•ƒŒªØ ł ¿¤ ¸·•”‹ºª ł ¿¤ fi¿“ºª ł ŒªŒ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ºªæŒ ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… –fi†»fił ‹– ¤‹»fi•–fił ‹– Œ ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ fi«›› …»›•„†»… ”–fi '•†… ·–¿…› •† ‹‚» ·¿†» –” ‹‚» ‹fi«›› –†·§ –fi ›‹«…› »¤–›»… ‹– '•†… ł†–fi‡¿· ‹– ‹‚» ”¿‰» ›»» ˝‹¿†…¿fi… †…«›‹fi§ ¿·» †… »‹¿•·› ¿› ¿·•‰¿·» –fi ‰–†›«·‹ fl«¿·•”•»… «•·…•†„ …»›•„†»fi ¿› »fi ˝æ— ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Ø fi«›› ‹– » ”«··§ ›‚»¿‹‚»… ”fi–‡ –†» ”¿‰» –fi ›»‰«fi»·§ fi¿‰»… ¿„¿•†›‹ ·¿‹»fi¿· ‡–“»‡»†‹ ł•» …•¿„–†¿· '» Ł ¿·» ›‹«…› ›¿‰»… ¿‹ –‰ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ º ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º–†–•‹‰‚ ˝«–fi‹»… ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˚–`¸`–¿‰—˝˘'ˇ˝ˇØ‚‡`§…ؤ'‹–˘¸·Ł†•˙¤•˝fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ªº¤Œ ªŁ˝ ¤ª¤ª¤Œ ª¤ ª¤ ª¤ ªº¤Ł ª¤Ł ª¤ª¤ Ø Œ º ŁŒŁ Ø º Œ º Œ º ˝Œ ˝Ø ˝ ˝º ˝ ˝ ˝ ˝Ł ˝ ˝ ˝ ˝ ˝ ˝ º Œ º Œ ØØ ØØ Ø Œ Ø º Œ Œ Œ ØŒ ØŒ Ø Œ ØŁØ ØØŒ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯…„»ˆ ¯…„»ˆ ¯ŁØ Ł ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŁ ˚»fi‹ł ºØ Øæ ˝†–' ł—”æ—„ºæ «‡»fi ººŁ ˚»fi‹ł Ø ºØ Ł Ł˝Øæ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł Ł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ ºº · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ ¤ ˝— ˝‹«… ˝¤ ˝— ˝‹«… ¤‰»‹ ¤ ˝— – ˛˝¤ ˝— ˝‹«… »”‹ ¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi ¿‰•†„ ¤‰»‹ Œ –‰ fi¿‰•†„ Ł ºØ –‰ fi¿‰•†„ ØŁ ˝ ˛–' ¿‹ ‡•…‹ºŁ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝·· »¿fi•†„› Œ ł· ¿¤ –fi•ƒØªŁ ł Œ ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ Łªº ł Ø ª ł Œ تŒ ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› »¤‰»‹ ŁªŒ ł Ø ºªŒØ ł تŒ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªŒæºŁŒ ªºŒæØ ªØŁæºŒ ªØæŒ ºªºŁæØ ºªæº ˛ŒªºŁæŒ Ł ŒªºŁæŒ ØŁªæŁØ ŁªØæŁ ˝ºŁªºØæŁØ Œºªæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił ˛ Œ ‹– Œ Œ †‹»fi•–fi ł ŒŒ ‹– Œ ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… –fi‰‚ ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ fi«›› …»›•„†»… ”–fi '•†… ·–¿…› •† ‹‚» ·¿†» –” ‹‚» ‹fi«›› –†·§ –fi ›‹«…› »¤–›»… ‹– '•†… ł†–fi‡¿· ‹– ‹‚» ”¿‰» ›»» ˝‹¿†…¿fi… †…«›‹fi§ ¿·» †… »‹¿•·› ¿› ¿·•‰¿·» –fi ‰–†›«·‹ fl«¿·•”•»… «•·…•†„ …»›•„†»fi ¿› »fi ˝æ— ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª º¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Ø ·· ·¿‹»› ¿fi» ·¿‹»› «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ł ·· ·¿‹»› ¿fi» º¤ «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… ¿·» ›‹«…› ›¿‰»… ¿‹ –‰ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› º »¤‰»‹ ł¶‹ª· تº Łª ª ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿· ˝‹fi«‰‹«fi¿· ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ·¶Øƒ—Æ˝†§Ø §‰—†˘‡˝Ł§¸‡“˝Łƒ‚Œ¶˝'‹•¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ª¤ º Œ Ł Ł ŁØ ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºº˚»fi‹ł ºØæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł ºŁ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ł –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªŒŒæ »‰‚¿†•‰¿· ł‡•† Ł ªæ »‰‚¿†•‰¿· ł‡•† Ł ºªŒ ŁæŒ ł‡•† Ł ¿¤ –fi•ƒºªØŒ ł ¿¤ ¸·•”‹ªŒ ł Œ ª ł Œ ºªŁ ł Œ ¿¤ fi¿“ª ł ªºØ ł Ø ºª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Œ ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ø »¿fi•†„ ¿‹ ¶–•†‹ł› º ‰–†›•…»fi› ¿fi¿··»· ‹– „fi¿•† “¿·«» «›•†„ ˝æ— ¿†„·» ‹– „fi¿•† ”–fi‡«·¿ «•·…•†„ …»›•„†»fi ›‚–«·… “»fi•”§ ‰¿¿‰•‹§ –” »¿fi•†„ ›«fi”¿‰» Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Ł · «·•”‹ ¿‹ ¶–•†‹ º Œ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º¿‰»†– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» º'Ł·fi‹»¶„Ł˚¨§‰”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚–‹‰‚Ø Ø¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ª¤ º Ø Ø ØØ ˝‰¿·» ª Œ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł ºØæ ˝†–' ł—”æ—„ºæ «‡»fi ºØ ˚»fi‹ł ºŁ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ø –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ »‰‚¿†•‰¿· ł‡•† Ł ªºæ »‰‚¿†•‰¿· ł‡•† Ł ºªŒæŒ ł‡•† Ł ¿¤ –fi•ƒºªº ł ¿¤ ¸·•”‹ªŁ ł ª ł ºªØ ł ¿¤ fi¿“ª ł ª ł ºªº ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Œ ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Ø · «·•”‹ ¿‹ ¶–•†‹ º Ł · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º¿‰»†– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ‚„–Æ–ººˇ‚fl»“¨§‰”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚–“‰‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ª¤ º ŁŁ ŁŁ ŁŁºØº˝‰¿·» ª Ø –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł ºØæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł ºŁ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˛ »•„‚‹ Ø · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ł Ł –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ »‰‚¿†•‰¿· ł‡•† Ł ªæ »‰‚¿†•‰¿· ł‡•† Ł ºªŒæŒ ł‡•† Ł ¿¤ –fi•ƒºªºŁ ł ¿¤ ¸·•”‹ªØ ł Œ ª ł ºªº ł Œ ¿¤ fi¿“ª ł ª ł Ø ºªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Œ ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ º · «·•”‹ ¿‹ ¶–•†‹ º Ø · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ºØ º¿‰»†– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ›˝…fl‚¸¤«·¸¨Æ·–ƒ˛fifi§‰Ø¤'‹–˘¸·Ł†•˙`–•˝fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. ª¤ ª¤ª¤Œ ª¤ ª¤ª¤Œ ª¤ ŒØ Ł ºØ Ł Ł ºŒ Ø Œ º ˝Œ ˝º ˝˝ ˝ ˝ Œ Œ º º º غ ŒŁ غº ºººŒºŒŒØŒºŒºŒŒŒŒ˝‰¿·» ª ºŒ —·¿‹» ””›»‹› ł¨ ˙¯º…„»ˆ ¯…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºØ ˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi ºŁ ˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝Œ –fi•ƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ ŁØ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ¤‰»‹ ˝¤ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ ¤‰»‹ –‰ fi¿‰•†„ ŒØ ºŒ ˛–' ¿‹ ‡•…‹Œº ˝ ˛–' ¿‹ ‡•…‹Ø •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝·· »¿fi•†„› Ø ł· ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› »¤‰»‹ ª ł ªØ ł Ø ºª ł º Œª ł تŒ ł Ø Ł ªŁ ł Œ ªº ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› Œ Ł »¤‰»‹ ªŒ ł ºªŁº ł Ø ØªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªØ æŒ ºªºæ ºªØæ ªŒ Œæ Ł ŒØ ªŒæ Œ ØŒªæŒ ŁŒªºæØØ ŁªæØ ˛ªŒæŒ ŒºªæŁ ˝ØªæŁ تŒæŁ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ºº ¤‹»fi•–fił˛ ºº ‹– Ł º †‹»fi•–fi ł Ł º ‹– Ł ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ fi«›› …»›•„†»… ”–fi '•†… ·–¿…› •† ‹‚» ·¿†» –” ‹‚» ‹fi«›› –†·§ –fi ›‹«…› »¤–›»… ‹– '•†… ł†–fi‡¿· ‹– ‹‚» ”¿‰» ›»» ˝‹¿†…¿fi… †…«›‹fi§ ¿·» †… »‹¿•·› ¿› ¿·•‰¿·» –fi ‰–†›«·‹ fl«¿·•”•»… «•·…•†„ …»›•„†»fi ¿› »fi ˝æ— ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª º¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† Œ ·· ·¿‹»› ¿fi» º¤ «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ø ¿·» ›‹«…› ›¿‰»… ¿‹ –‰ Ł ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› »¿fi•†„ ¿‹ ¶–•†‹ł› º ‰–†›•…»fi› ¿fi¿··»· ‹– „fi¿•† “¿·«» «›•†„ ˝æ— ¿†„·» ‹– „fi¿•† ”–fi‡«·¿ «•·…•†„ …»›•„†»fi ›‚–«·… “»fi•”§ ‰¿¿‰•‹§ –” »¿fi•†„ ›«fi”¿‰» —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ · «·•”‹ ¿‹ ¶–•†‹ Œ · «·•”‹ ¿‹ ¶–•†‹ º Ø · «·•”‹ ¿‹ ¶–•†‹ ŒŁ · «·•”‹ ¿‹ ¶–•†‹ Ø Ø · «·•”‹ ¿‹ ¶–•†‹ Ł ¿†… º · «·•”‹ ¿‹ ¶–•†‹ –† ˝‹¿†…¿fi… »¿fi•†„ ‰–†…•‹•–† ˛»“•»' fi»fl«•fi»… »“»·»… ·¿‹» –fi ›‚•‡ fi»fl«•fi»… ‹– fi–“•…» ”«·· »¿fi•†„ ›«fi”¿‰» '•‹‚ ‹fi«›› ‰‚–fi… ¿‹ ¶–•†‹ł› Œ º Ø Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˙Ø º¿§† ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ›»˛fi¤'‹Ł˚§…—¨‡Ø¤'‹–˘¸·Ł†•˙ˇ§…“fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. ª¤ªº¤ªº¤ªº¤ ª¤ªº¤ªº¤ ª¤ º Ł Ø Œ ˝ ˝˝ Ø Ø ØŒ ØŒ˝‰¿·» ª ŒØ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºØ ˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝º–fi•ƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤— »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝·· »¿fi•†„› Ø ł· ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ Œª ł Ø Łªº ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› º Œ Ø Ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ¤‹»fi•–fił ˛ ‹– Ø †‹»fi•–fi ł Ø ‹– ØØ ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› º »¤‰»‹ ł¶‹ª· Łª Œª Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˙Ø º¿§† ¿·»– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ¸§‚˙''•§·¨ˇØ»¶fi§…—«Ø¤'‹–˘¸·Ł†•˙Łº•„fl•„`§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ªŒ¤Œ ª¤ ª¤º ª¤Œ ª¤ ª¤Œ ª¤Ł ª¤Ł ª¤º ª¤ ªŒ¤Œ ª¤ Ł º Ø Ł Œ Œ Ø º º Ø Ø Ø Œ ØØ Ø Ø Œ Ø Ł Ø º Ø º Ø ºØŁ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯ˆ ¯Ł…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŒŒ ˚»fi‹ł Ø Øæ ˝†–' ł—”æ—„ºæ «‡»fi ºº˚»fi‹ł Œ Ł ˛» ˝‹fi»›› †‰fi ˙˝º–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ¤‰»‹ º¤ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Ł –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ ˝ ˛–' ¿‹ ‡•…‹ Ø •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªºæ »‰‚¿†•‰¿· ł‡•† Ł ªØæŒ ł‡•† ¿¤ –fi•ƒªº ł ¿¤ ¸·•”‹ªºŁ ł Ø ªŁ ł Œ ¿¤ fi¿“ªØ ł ª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ºªºŒØæ ºªØºæ ªæ ŒªØæ ºŒ ºŒªæØ ºØªæØŒ Œ ØªØæº ŒŁªŁæºº Ø Łªæ ØªŁæ ŁªºŒæ ªæ ŁªØæ ˛ªæ ªæ ªŒºæŁ ˝ªØæ Œ Łªæ ªºæ ºªŒØæŒ تŒæŒ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił˛ Œ ‹– Ø Œ †‹»fi•–fi ł Ø Œ ‹– Ł ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Ł · «·•”‹ ¿‹ ¶–•†‹ ¿†… ºŁ · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º–‡‡–†– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ¨“‚”˚¿˚ˇŒ ”˘§‰‚˘‡˝Ł§¸‡“˝Łƒ‚Œ†—Æ‹„¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤º ª¤Œ ª¤ ª¤ ª¤Ł ª¤ ªº¤ª¤ª¤ª¤ª¤ ªŁ˝ ٤ ª¤ ª¤ ª¤ ª¤Ł ªº¤ªº¤ ª¤Ł ª¤º Ł Ø Œ º º ºŁ ØŒ º Ł Œ º Ø Œ º غ Ł Ø Ø ºØ Œ ºŒ Œ Œ Œºº Œ Œ Ø º Ł ŁØŁ ˝‰¿·» ª ºØ —·¿‹» ””›»‹› ł¨ ˙¯ŒŁ Łˆ ¯ˆ ¯ŒŒ…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ººØ ˚»fi‹ł Ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi ººŒ ˚»fi‹ł Ł Ł Ł˝Øæ ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ Œ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ ¤ ˝— ˝‹«… ˝¤ ˝— ˝‹«… ¤‰»‹ ŒØ¤ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ »‰‚¿†•‰¿· ł‡•† Ł ªŒæŒ ł‡•† ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹ªºŁ ł Ø ªŁ ł Œ ¿¤ fi¿“ªŒ ł ª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªŒØæ ºªŁæº ºªŁŒæº ªŒæ Œ ŒªæØØ ŒØªæŒ ØªØºæ ªŁæØ Ł ŁªŒæ Œº ŁªØººæŁ ºªØ æŒ ºªŁØæŒ ªŁØæ Ø ªØæ ªŁ æŒ ˛ŁªŒŒæŁŒ ØŒªŁØæ ºŒªºæºØ ºªºŁæØØ ˝ŁŒªºØæ ŁºªæŁº ºªŒæºŒ ªŁæØ ºŒ ªŒæ Œ ªŒæŒŒ Œ ŁªØæ ŒŒªØŒæŒŁ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił ˛ Œ ‹– Ø Œ †‹»fi•–fi ł Ø Œ ‹– Ł ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ·· ·¿‹»› ¿fi» ·¿‹»› «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ø ·· ·¿‹»› ¿fi» ¤ «†·»›› –‹‚»fi'•›» •†…•‰¿‹»… Ł ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Ł · «·•”‹ ¿‹ ¶–•†‹ ¿†… ºŁ · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿·– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ¨“‚”˚¿˚ˇŒ”˘§‰‚˘‡˝Ł§¸‡“˝Łƒ‚Œ·‹¿¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ª¤Ł ª¤Ł ª¤ª¤ªº¤ ª¤ ª¤ ª¤Ł ª¤Ł ªº¤ ª¤ ª¤Œ ª¤Ł ª¤ ª¤ ª¤Ł ª¤ªº¤ ª¤º ª¤ Ł Ø ºŒ Ł ŁØ ºŒº Œ Ø º Ø º Œ ŁØ Œ º º ŁŁ Œ Ø Ø Ø ºØºº Œ ØŒ ØŒ Œ Œ Œ Ø ºº Œ ºº Œ ØŒ ØŒŁØ ØØŒ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯…„»ˆ ¯…„»ˆ ¯ˆ ¯ŒºŁ ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ººŁ ˚»fi‹ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł ØØ Ł ˛» ˝‹fi»›› †‰fi ˙˝º–fiƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ Œ¤ ˝— ˝‹«… ˝¤ ˝— ˝‹«… »”‹ ¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi º –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi ºŒ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝ł·æ›•ƒ»ªŁæ ł‡•† Ł ªØæ »‰‚¿†•‰¿· ł‡•† Ł ªŁŒ æŒ ł‡•† ¿¤ –fi•ƒªŁ ł Œ ¿¤ ¸·•”‹ª ł ªØ ł Ø ªØ ł Œ ¿¤ fi¿“ªŒ ł Œ ªØº ł ªØØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªæ ªØæ ªæº ºªŒæŒ Ø ººªººæ Œ ºªºŒæ ŒØªºæ ØŒªºØØæ ŒØªºæØ ŁØªŒºŁæŁØ ŁŁªºæº ŁªæŁŁ ªºæ ªØæŁ ˛ªæ ªæ ªºæŒ ªæŒ ºŒªŁØæº ºªŁæ ªØæ ˝ªºæØ غªºæŁØ Łºªººæº ŁªæŁ ªºæØŁ ŁªŒæŒ ŒŁªæºØ ºŒªæØØ ºªŒæŁ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił ˛ Œ ‹– Œ Œ †‹»fi•–fi ł ŒŒ ‹– Œ ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… –fi‰‚ ·»”‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ Ø · «·•”‹ ¿‹ ¶–•†‹ ¿†… Ø · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿·– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˇ»…¿•˛˚¿“„˛‚§§‰º˘‡˝Ł§¸‡“˝Łƒ‚Œ–•˚‹„…¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ª¤Ł ª¤ ª¤ª¤ª¤ ª¤ ª¤ ªº¤Ł ª¤Ł ª¤ ª¤ ª¤ª¤ Ł Ø Ø Œ Ł º Ł º Ø Œ Œ Œ ŒŒ Œ Œ Ø ØŒ ØŒ Œ Œ ŒŒ Œ Œ Ø ØŒ ØŒŁØ ØØŒ˝‰¿·» ª º —·¿‹» ””›»‹› ł¨ ˙¯…„»ˆ ¯…„»ˆ ¯Ø…„»ˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºº˚»fi‹ł Œ ºØæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł Œ Ł ˛» ˝‹fi»›› †‰fi ˙˝º–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ¤‰»‹ ¤ ˝— ˝‹«… ˝¤ ˝— ˝‹«… ¤‰»‹ º¤ ˝— – »”‹ ¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi ºŁ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi º –‰ fi¿‰•†„ ˝ ˛–' ¿‹ ‡•…‹º •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªæ ł‡•† Ł ŁªØæ »‰‚¿†•‰¿· ł‡•† Ł ªØæŒ ł‡•† Ł ¿¤ –fi•ƒªŁ ł Œ ¿¤ ¸·•”‹ª ł ŁªŒ ł Ø ª ł Œ ¿¤ fi¿“ª ł Œ ŁªŁØ ł ª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛Øªººæ ØªŁæ ªæŁ Łªºæº ºŁ ªŁæº ºªººæŒ ªºŒæŁ ŒªŒºæŒ ŒªººæŒº تŒæ ØŁªØºæ ˛ªŁæºØ ªŁæºØ ªŁŒæ ªºæØ ªŒŒæŁºŒ ˝ªæºŒ ºªººæ Œ ªŒæº ØªØæØº ºªæŒ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił ˛ Œ ‹– Œ Œ †‹»fi•–fi ł ŒŒ ‹– Œ ƒ–†» ‰¿†‹•·»“»fi ·»”‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ »¤–›»… –fi‰‚ ·»”‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ · «·•”‹ ¿‹ ¶–•†‹ ¿†… Œ · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿·– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˇ»…¿•˛˚¿“„˛‚§§‰º˘‡˝Ł§¸‡“˝Łƒ‚Œ–˝˚”‹„¨“¿¿ÆŒ§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ªº¤Œ ª¤ ª¤º ª¤ ª¤ ª¤Ł ª¤º ª¤ ªº¤Œ ª¤ Ł Ø Œ º ºŁ Œ Ø º ºº Œ ºØºØ ºØ ºŁ ºŁ ºŁºŁŁ ºŁŁ ŒŁŁØØ ˝‰¿·» ª Ø —·¿‹» ””›»‹› ł¨ ˙¯Ł ˆ ¯ŒŁˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŒ ˚»fi‹ł Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł Ø Ł ˛» ˝‹fi»›› †‰fi ˙˝Œ –fiƒł Ł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi ºº –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ŁªŁ æŒ ł‡•† Ł ªŁ æ Œ ł‡•† Ł ¿¤ –fi•ƒªŁ ł º ¿¤ ¸·•”‹Łª ł Ø ª ł Œ ¿¤ fi¿“Łª ł ª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªØºæŁ ªæØ ºªŁØæ ºŒªŁ æ ŒªØæºØ Ø ªØæ ºØ ØŁªŁæ ºŁªŁØæ ºªæØ ŒªØºæŁ ªŁŁæØ ŒŁªŁŁæØ ˛ªºæØ ªºæØ ªØæØ ˝ªŒ æŁ Œ ªØæŁ ªæ º ªØŁæ ºªæº ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ¤‹»fi•–fił˛ ‹– †‹»fi•–fi ł ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ºØØº–‡‡–†– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» Æ ·˚Œ «ƒ”º§¶§‰“”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚fi–›‰¿‚Ø Ø¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ª¤Ł ª¤Œ ª¤Ł ª¤ ª¤Œ ªŒ¤Œ ª¤ ª¤Œ ª¤Ł ª¤ Ł Ø º Œ Œ Ø Ł º º Ø Ł Ł Ł Ł Ø ŁŒØŒŒŒ ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł Ł Øæ ˝†–' ł—”æ—„æ «‡»fi ºŒ ˚»fi‹ł Ø Ø Ł ˛» ˝‹fi»›› †‰fi ˙˝Ø –fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi º –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªŁ æŒ ł‡•† ªŁ æŒ ł‡•† ¿¤ –fi•ƒªŒ ł º ¿¤ ¸·•”‹ª ł Ø ª ł Œ ¿¤ fi¿“ªº ł ªº ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛Œªæ ŒØ ªºæŁ تºæ ºªØæ Ł ºŁªºæ Ł ªºæŁ Œªæ ªŒæŁ تŒæŁ ˛ªŒæ ªºŒæØ ªºŒæØ ªæ ˝ªæ Œ ªæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– Ł ¤‹»fi•–fił Ł ‹– Ł ¤‹»fi•–fił ˛ Ł ‹– Ø Ø †‹»fi•–fi ł Ø Ø ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ŒØº•– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˙„§Œ †Æ¨˛–•¨˝˘•Œ§‰””·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚·–†‰º‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ªŒ¤Œ ª¤Ł ª¤Œ ª¤ ª¤ª¤Œ ª¤Ł ªŒ¤Œ ª¤ Ł Ø Œ º Ø ŁŒ º Ł Ł Ł Ø Ł Ø Ł ØŁ Ø Ø ØØŁºØººº˝‰¿·» ª Ł —·¿‹» ””›»‹› ł¨ ˙¯Łˆ ¯ŒŁˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŁ ˚»fi‹ł Œ Øæ ˝†–' ł—”æ—„æ «‡»fi ºØ ˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi ˙˝–fiƒł Ł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ Ł · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ¤‰»‹ ¤Œ ˝— – ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ŁªŁºŁæŒ ł‡•† ªŁºŁæŒ ł‡•† ¿¤ –fi•ƒª ł º ¿¤ ¸·•”‹Łª ł Ø ª ł Œ ¿¤ fi¿“Łªº ł ªº ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªæºØ ªŁæ Œ ºªŁæØ ºªØºæ ŒªŁØæ ŒØªŁØæ ØªŁØŒæŁ ŁªŁØŒæŁ Ł ªŁ Øæ ºªŁØæ ºªØºæ ªŁæØ ªŁ æŒ Œ ªæºØ ªØæ ŒŁªØæ ˛ªØæ ªæ ªæ Ł ªºæ ˝ªºæØº ŒªºæØº ªºæ ªºæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ØŁ ¤‹»fi•–fił˛ ØŁ ‹– ºØ †‹»fi•–fi ł ºØ ‹– Ł ¤‹»fi•–fił ˛ Ł ‹– Ø †‹»fi•–fi ł Ø ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ØØº•– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ·˚'Ł˚‹˙'‰fiØ˙§§‰Æ”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚'ƒ–§‰‚Ø Ø¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ªº¤ ªº¤Œ ª¤º ªŒ¤Œ ª¤ ª¤Ł ªº¤ ªŒ¤Ł ª¤Ł ª¤Œ ªº¤Œ ª¤ Ł Ø º ŁØŒ º Œ ºŒ ºØ Ł ºŁ Œ º ºŁ º ŒŁ ºŁ ºŁ ºŁ º º º ºŁ ºº ŒŁ ŒºØº˝‰¿·» ª Ł —·¿‹» ””›»‹› ł¨ ˙¯ˆ ¯ºŁ…„»ˆ ¯ØŁˆ –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºº˚»fi‹ł Œ Øæ ˝†–' ł—”æ—„æ «‡»fi ºº˚»fi‹ł Ł ˛» ˝‹fi»›› †‰fi ˙˝º–fiƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ªŁØæŒ ł‡•† Ł ªŁØØæ Œ ł‡•† Ł ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹ªŁ ł Œ ªŁ ł Œ ¿¤ fi¿“ª ł ª ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ºªºæŒ ºªæ ŒªºæŒ Œ تºæŒ تºæŒ ŁªºæŒ ºŁªºæŒ ºŒªŒæØ ŒªŒºæº ªæ ªØæ ªæŒ Øªæ ªŁ Łºæºº ØªŁ Øæ ˛ªŒæŁ ªŒæŁ ªæ ˝ªæŒ ªºØØæŁ ºªæºº ºªæº ŒªºŁæ ªæØº تŒæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– †‹»fi•–fi ł ‹– ºŁ ¤‹»fi•–fił˛ ºŁ ‹– ŁŁ †‹»fi•–fi ł Ł Ł ‹– Œ ¤‹»fi•–fił˛ Œ ‹– †‹»fi•–fi ł ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ Ł · «·•”‹ ¿‹ ¶–•†‹ ¿†… Ł · «·•”‹ ¿‹ ¶–•†‹ ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ŁØº˛––” ˝»‰•¿·– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» „ƒŒ¸`“¨·Ł‰fiƒ•٧‰”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚Æ–fifl‰Ł‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ªº¤ ª¤ ªŒ¤Œ ªº¤ªº¤ ªŒ¤Œ ª¤ ª¤Ł ª¤ºªº¤ Ł Ø Œ º º Ø º Œ Ł Ł Œ ŁŁ ØØŁ ŁŁ Ł Œ ŒŁ ØºØŁºº˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºŁ ˚»fi‹ł Ł Øæ ˝†–' ł—”æ—„æ «‡»fi ºº˚»fi‹ł ºŁ Ł ˛» ˝‹fi»›› †‰fi ˙˝Ø –fiƒł Ø †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› »¤‰»‹ »†… “»fi‹•‰¿·› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ fi ¿‰•†„ ¤‰»‹ Œ –‰ fi¿‰•†„ Ø Ł •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…» ˛˝ł·æ›•ƒ»ØªŒ ŒæŒ ł‡•† Ł ªŁæ »‰‚¿†•‰¿· ł‡•† Ł ¿¤ –fi•ƒª ł ¿¤ ¸·•”‹ØªŒŁ ł Ø ª ł Œ ¿¤ fi¿“تºØ ł ªº ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªæ ªØØæ ªØØæ ªØØæ ªæ ºªºæ ººªºæØ ºØªººæŒŁ ˛ªŒæØ ªØæº Łªæºº ˝ªŒŒŁæ ºŁªØæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ‹– Ł †‹»fi•–fi ł Ł ‹– ŁŁ ¤‹»fi•–fił˛ ŁŁ ‹– Œ ŁŁ †‹»fi•–fi ł ŒŁŁ ‹– ØØŁ ¤‹»fi•–fił˛ Ø ØŁ ‹– Ø Ł †‹»fi•–fi ł ØŁ ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ª ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª «ªº •† ”·¿‹ fi––” ›†–' ·–¿… „–“»fi†› ˛¿•† ›«fi‰‚¿fi„» ¿·•»… ‹– ¿·· »¤–›»… ›«fi”¿‰»› '•‹‚ ›·–»› ·»›› ‹‚¿† ºæ •† ¿‰‰–fi…¿†‰» '•‹‚ ŒŁ ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi „fi»¿‹»fi –” ‡•† fi––” ·•“» ·–¿… –” ›” –fi ‹•‡»› ”·¿‹ fi––” ·–¿… –” º ›” –† –“»fi‚¿†„› †–†‰–†‰«fifi»†‹ '•‹‚ –‹‚»fi ·•“» ·–¿…› Œ —fi–“•…» ¿…»fl«¿‹» …fi¿•†¿„» ‹– fi»“»†‹ '¿‹»fi –†…•†„ Ø ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ł ˛»”»fi ‹– „•fi…»fił› ”–fi ‹fi«›› ‹– ‹fi«›› ‰–††»‰‹•–†› —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ ¿†… ŒŁ · «·•”‹ ¿‹ ¶–•†‹ Ø ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł Ø º˛––” ˝»‰•¿·– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Łº ˝ «„ Œ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ‚‰†˛˛“¿ƒ¿ƒ“¶§‰“”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚Ł–fi‹‰‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ª¤ªº¤ª¤ ˝ Œº ºº Ł Ł ººŁ˝‰¿·» ª Ł –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝Ł –fi•ƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤— »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi º –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝·· »¿fi•†„› º ł· ¿¤ –fi•ƒª ł Œ ت ł Œ ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› Ø ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› Ø »¤‰»‹ ªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªºæ º ªæ ˛ªæ ºŁ ªæ ˝ªŒØæØ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ Œ · «·•”‹ ¿‹ ¶–•†‹ ŒØ · «·•”‹ ¿‹ ¶–•†‹ ¿†… · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˚Ø º˚¿··»§– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˘¸˛˛fi«ŒŒŒ‚¿‰§‰·”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚º‰–“‹‰ƒ‚Ø Ø¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ ª¤ªº¤ª¤ ˝ ŒºŁ Ł ºŁ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝–fi•ƒł †æ¿†æ¿ –…»˛Łæ—¿‹fi•¤— »•„‚‹ · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝ł·æ›•ƒ»ªæ ł‡•† Ł ªæ ł‡•† Ł ªŒæ ł‡•† Ł ¿¤ –fi•ƒª ł Ø ¿¤ ¸·•”‹ªº ł ªº ł ªº ł Œ ¿¤ fi¿“ªŁ ł ªŁ ł ªØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† — ˛ªØæŁ ªŁ ٿ٠ªŁŒæØ ªØŁæØ ªŁæ Ł ªŁæŁ ˛ªŒæŁ ªŒæŁ ˝ªºŒæŁ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił Ł ‹– Ł †‹»fi•–fi ł Ł ‹– ¤‹»fi•–fił˛ ‹– Ø †‹»fi•–fi ł Ø ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ º · «·•”‹ ¿‹ ¶–•†‹ º · «·•”‹ ¿‹ ¶–•†‹ ¿†… º · «·•”‹ ¿‹ ¶–•†‹ Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˚Ø º˚¿··»§– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˘¸˛˛fi«ŒŒŒ‚¿‰§‰·”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚–›˛‰‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ªº¤ªº¤ ª¤ªº¤ªº¤ªº¤ ª¤ º Ł Ø Œ Œ º˝ ˝˝ Œ ºŒŒŁ Œ Ł ºŁ˝‰¿·» ª Ø –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• º˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi º˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝Ø –fi•ƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ Ø · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝·· »¿fi•†„› ł· ¿¤ –fi•ƒªºŁ ł ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ Œª ł Ø Łª ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ ŒªØØ ł تº ł ŁªØØ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝Łªæ Œªæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił Ł ‹– †‹»fi•–fi ł ‹– Œ ¤‹»fi•–fił ˛ Œ ‹– †‹»fi•–fi ł ‹– ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› º »¤‰»‹ ł¶‹ª· Łª Œª Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˚Ø º˚¿··»§– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» ˘¸˛˛fi«ŒŒŒ‚¿‰§‰·”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚–“¶‰Œ‚ØØ¨˙§… DE Job# 86850-W1 \\ \ Dansco Engineering, LLC Date: 09/16/2021 WARNING – VERIFY DESIGN PARAMETERS AND READ NOTES BEFORE FABRICATION AND INSTALLATION!!! This truss design is adequate for the design parameters shown. Review and approval of design parameters is the responsibility of the building designer, not the truss designer or truss engineer. Permanent bracing requirements against out-of-plane buckling are noted/shown for individual truss members (and for the truss as a whole) subjected to gravity and wind loads. Additional permanent bracing design shall be the responsibility of the design professional of record. Temporary and erection bracing shall be the responsibility of the contractor. Reference ANSI/TPI-1, “National Design Standard for Metal Plate Connected Wood Truss Construction” and TPI/WTCA BCSI-06, “Building Component Safety Information Guide to Good Practice for Handling, Installing, Restraining and Bracing of Metal Plate Connected Wood Trusses” for additional information. Œ ª¤ªº¤ªº¤ ª¤ ª¤ªº¤ªº¤ªº¤ ª¤ º Ł Ø Œ ºŁ Œ Ø ˝ ˝˝ Œ º Ø Ł Ø Ł Ł Ł Ł ØºŁ˝‰¿·» ª –¿…•†„ł›”˝¿‰•†„˝•†ł·–‰·æ…»”·æ…—˝˛— łfi––”—·¿‹» fi• ºØ ˚»fi‹ł †æ¿†æ¿Øæ ˝†–' ł—”æ—„ºæ «‡»fi ºŒ ˚»fi‹ł †æ¿†æ¿ ˛» ˝‹fi»›› †‰fi ˙˝–fi•ƒł º†æ¿†æ¿ –…»˛Łæ—¿‹fi•¤˝ »•„‚‹ º · ª ß ¸˛ — ˛¤ ˝— – ˛¤ ˝— – ˛˝¤ ˝— ˝‹«… ˛ — ˛˝‹fi«‰‹«fi¿· '––… ›‚»¿‹‚•†„ …•fi»‰‹·§ ¿·•»… –fi –‰ «fi·•†› ˛˛•„•… ‰»•·•†„ …•fi»‰‹·§ ¿·•»… –fi Œ –‰ fi¿‰•†„ •» fi»‰–‡‡»†…› ‹‚¿‹ ˝‹¿•·•ƒ»fi› ¿†… fi»fl«•fi»… ‰fi–›› fi¿‰•†„ » •†›‹¿··»… …«fi•†„ ‹fi«›› »fi»‰‹•–† •† ¿‰‰–fi…¿†‰» '•‹‚ ˝‹¿•·•ƒ»fi †›‹¿··¿‹•–† „«•…»˛˝·· »¿fi•†„› Ø ł· ¿¤ –fi•ƒªØŒ ł ¿¤ ¸·•”‹·· «·•”‹ ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ Œª ł Ø ª ł Œ ¿¤ fi¿“·· fi»¿‰‹•–†› º ł· –fi ·»›› ¿‹ ¶–•†‹ł› º »¤‰»‹ ŒªºŁ ł ت ł ªºŁ ł ˛˝ł· ¿¤ –‡æ¿¤ »† ·· ”–fi‰»› º ł· –fi ·»›› »¤‰»‹ '‚»† ›‚–'† ˝ØªæØ ªæ Œªæ ˝ ¸†¿·¿†‰»… fi––” ·•“» ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† •†… ˝ ØŒ ˚«·‹ªº‡‚ ł›»‰–†… „«›‹ ˚¿›…ª‡‚ ªŒ›” ªŒ›” ‚ªº”‹ ¿‹ ¤ †‰·–›»… ˛˝ ł»†“»·–» »¤‹»fi•–fi ƒ–†» ¿†… ¤‹»fi•–fił Ł ‹– Ł †‹»fi•–fi ł Ł ‹– Ł ¤‹»fi•–fił ˛ Ł ‹– †‹»fi•–fi ł ‹– Ø ƒ–†» ‰¿†‹•·»“»fi ·»”‹ ¿†… fi•„‚‹ »¤–›»… »†… “»fi‹•‰¿· ·»”‹ ¿†… fi•„‚‹ »¤–›»… ”–fi ‡»‡»fi› ¿†… ”–fi‰»› œ ˛˝ ”–fi fi»¿‰‹•–†› ›‚–'† «‡»fi ªŒ ·¿‹» „fi• ªŒ ˝ ØŒ —fiª ›” łfi––” «‡ ªº —·¿‹» ªº —„ª ›” —”ªº ›” ł «‡ ªº —·¿‹» ªº ›ª ˛–«„‚ ¿‹ —¿fi‹•¿··§ ¤ »ª ›ª ‹ª ¸†¿·¿†‰»… ›†–' ·–¿…› ‚¿“» »»† ‰–†›•…»fi»… ”–fi ‹‚•› …»›•„† º¿·» fi»fl«•fi»› ‰–†‹•†«–«› –‹‹–‡ ‰‚–fi… »¿fi•†„ Œ ‚•› ‹fi«›› ‚¿› »»† …»›•„†»… ”–fi ¿ ›” –‹‹–‡ ‰‚–fi… ·•“» ·–¿… †–†‰–†‰«fifi»†‹ '•‹‚ ¿†§ –‹‚»fi ·•“» ·–¿…› Ø —fi–“•…» ‡»‰‚¿†•‰¿· ‰–††»‰‹•–† ł§ –‹‚»fi› –” ‹fi«›› ‹– »¿fi•†„ ·¿‹» ‰¿¿·» –” '•‹‚›‹¿†…•†„ · «·•”‹ ¿‹ ¶–•†‹ł› º »¤‰»‹ ł¶‹ª· ª Œª Ł ‚•› ‹fi«›› •› …»›•„†»… •† ¿‰‰–fi…¿†‰» '•‹‚ ‹‚» Ł †‹»fi†¿‹•–†¿· ˛»›•…»†‹•¿· –…» ›»‰‹•–†› ˛º ¿†… ˛Ł ¿†… fi»”»fi»†‰»… ›‹¿†…¿fi… ˝æ— ˝ł˝ ˝‹¿†…¿fi… –fi«››fi«›› §»ˇ‹§—·§ fi¿‡»fi‰§ –‹ Ł ˚Ø º˚¿··»§– ˛»”»fi»†‰» ł–‹•–†¿· ˛«† Ł ˝ »‰ —fi•†‹ Łº ˝ «„ Œ •» †…«›‹fi•»› †‰ »… ˝» º غŒ —¿„» Ø›»†fi‚¤fi‚˘‰›'Øfl§‰”·fl˙ƒ¨˝‡‰…¨‰•…˙¤˚–«–‰‚Ø Ø¨˙§…