HomeMy WebLinkAboutA041-FAIR HOUSING BLOCKING DETAILSMINIMUM REINFORCING BEHIND
TOILETS LOCATED BESIDE A WALL
MINIMUM
REINFORCED AREA-
AN ADDITIONAL 2" MIN
EACH SIDE AND BOTTOM
IS RECOMMENDED TO
MOUNT 24" STANDARD
GRAB BAR12" MIN. 12" MIN.
18"32" MAX30" MAX PREFERRED38" MIN.28"-32" REINFORCING
AREA SHOULD BE
PROVIDED TO
ACCOMMODATE A 24"
GRAB BAR12" MIN.24" MIN.42" PREFERREDWHEREVER POSSIBLE, SIDE REINFORCING
SHOULD ACCOMMODATE A 42" GRAB BAR
MINIMUM REINFORCING BEHIND TOILETS
LOCATED BESIDE A PARTIAL WALL
18"
12" MIN. 12" MIN.
18"
18"32" MAX30" MAX PREFERRED38" MIN.32" MAX30" MAX PREFERRED3'-2" MIN. 6"MAX.
MINIMUM REINFORCING @ BATHTUBS
WITHOUT PERMANENT SEATS
MINIMUM REINFORCING IN SHOWERS 32" MAX30" MAX PREFERRED38" MIN.ELONGATED
REINFORCING FOR
POSSIBLE ADDITION OF
FOLDING GRAB BAR
WHERE TOILETS DO NOT HAVE FULL
SIDE BAR REINFORCING,
REINFORCEMENT BEHIND THE TOILET
MUST BE ENLARGED TO SUPPORT A
FOLD-DOWN GRAB BAR ASSEMBLY
18" 2'-2" MIN. 2'-2" MIN.6" MIN.WALL TO WALL
REINFORCING
WALL TO WALL
REINFORCING
6"MAX. 6"MAX.
PROVIDE BLOCKING FOR FUTURE INSTALLATION OF GRAB
BARS AND SEATING PER SEC. 607.4 ANSI 117.1-2009
6"MAX.6" MAX.2'-4" MIN.2'-2" MIN.PROVIDE BLOCKING FOR FUTURE INSTALLATION OF GRAB
BARS AND SEATING PER SEC. 604.5 ANSI 117.1-2009
PROVIDE BLOCKING FOR FUTURE INSTALLATION OF GRAB
BARS AND SEATING PER SEC(S). 608.3, 608.2.1.3,
608.2.2.3, & 608.2.3.2 ANSI 117.1-20096" MIN.2'-4" MIN.4'-0"MIN.
A041FAIR HOUSINGBLOCKING DETAILSSCALE:
01 TYPICAL BLOCKING DIAGRAMS
1/2" = 1'-0"ARCHITECTCLIENT CONSTRUCTION MANAGER PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20011
APRIL 28, 2021AVANT PHASE IICARMEL, INEDWARD ROSEDEVELOPMENTCARMEL LLC.PERMIT SET