HomeMy WebLinkAboutA045-ANSI STANDARDS TYPE B UNITS60 min
1525
40 min
1015
40 min
1015
Ref
FIG. 1004.12.1.2
U-Shaped Kitchen Clearance in Type B
Units
DW
Ref
Ref
DW
FIG. 1004.12.1.1
Minimum Kitchen Clearance in Type B
Units
1004 Type B Units
1004.1 General. Type B units shall comply with Section 1004.
1004.2 Primary Entrance. The accessible primary entrance shall be on an
accessible route from public and common areas. The primary entrance shall not
be to a bedroom unless it is the only entrance.
1004.3 Accessible Route. Accessible routes within Type B units shall comply with
Section 1004.3.
1004.3.1 Location. At least one accessible route shall connect all spaces and
elements that are a part of the unit. Accessible routes shall coincide with or be
located in the same area as a general circulation path.
EXCEPTIONS:
1. An accessible route is not required to unfinished attics and unfinished
basements that are part of the unit.
2. One of the following is not required to be on an accessible route:
2.1 A raised floor area in a portion of a living, dining, or sleeping
room; or
2.2 A sunken floor area in a portion of a living, dining, or sleeping
room; or
2.3 A mezzanine that does not have plumbing fixtures or an enclosed
habitable space.
1004.3.2 Components. Accessible routes shall consist of one or more of the
following elements: walking surfaces with a slope not steeper than 1 :20, doors
and doorways, ramps, elevators, and platform lifts.
1004.4 Walking Surfaces. Walking surfaces that are part of an accessible route
shall comply with Section 1004.4.
1004.4.1 Clear Width. Clear width of an accessible route shall comply with
Section 403.5.
1004.4.2 Changes in Level. Changes in level shall comply with Section 303.
EXCEPTION: Where exterior deck, patio or balcony surface materials are
impervious, the finished exterior impervious surface shall be 4 inches (100
mm) maximum below the floor level of the adjacent interior spaces of the
unit.
1004.5 Doors and Doorways. Doors and doorways shall comply with Section
1004.5.
1004.5.1 Primary Entrance Door. The primary entrance door to the unit shall
comply with Section 404.
EXCEPTION: Storm and screen doors serving individual dwelling or sleeping
units are not required to comply with Section 404.2.5.
1004.5.2 User Passage Doorways. Doorways intended for user passage shall
comply with Section 1004.5.2.
1004.5.2.1 Clear Width. Doorways shall have a clear opening of 31 3/4 inches
(805 mm) minimum. Clear opening of swinging doors shall be measured between
the face of the door and stop, with the door open 90 degrees.
1004.5.2.1.1 Double Leaf Doorways. Where the operable parts on an inactive leaf
of a double leaf doorway are located more than 48 inches (1220 mm) or less
than 15 inches (380 mm) above the floor, the active leaf shall provide the
clearance required by Section 1004.5.2.1.
1004.5.2.2 Thresholds. Thresholds shall comply with Section 303.
EXCEPTION: Thresholds at exterior sliding doors shall be permitted to be
3/4 inch (19 mm) maximum in height, provided they are beveled with a slope
not steeper than 1 :2.
1004.5.2.3 Automatic Doors. Automatic doors shall comply with Section 404.3.
1004.6 Ramps. Ramps shall comply with Section 405.
1004.7 Elevators. Elevators within the unit shall comply with Section 407, 408,
or 409.
1004.8 Platform Lifts. Platform lifts within the unit shall comply with Section 410.
1004.9 Operable Parts. Lighting controls, electrical switches and receptacle
outlets, environmental controls, electrical panel boards, and user controls for
security or intercom systems shall comply with Sections 309.2 and 309.3.
EXCEPTIONS:
1. Receptacle outlets serving a dedicated use.
2. Where two or more receptacle outlets are provided in a kitchen above a
length of counter top that is uninterrupted by a sink or appliance, one
receptacle outlet shall not be required to comply with Section 309.
3. Floor receptacle outlets.
4. HVAC diffusers.
5. Controls mounted on ceiling fans.
6. Controls or switches mounted on appliances.
7. Plumbing fixture controls.
8. Reset buttons and shut-offs serving appliances, piping and plumbing
fixtures.
9. Where redundant controls other than light switches are provided for a
single element, one control in each space shall not be required to be
accessible.
10. Within kitchens and bathrooms, lighting controls, electrical switches and
receptacle outlets are permitted to be located over cabinets with counter
tops 36 inches (915 mm) maximum in height and 25 1/2 inches (650 mm)
maximum in depth.
1004.10 Laundry Equipment. Washing machines and clothes dryers shall comply
with Section 1004.10.
1004.10.1 Clear Floor Space. A clear floor space complying with Section 305.3,
shall be provided. A parallel approach shall be provided for a top loading
machine. A forward or parallel approach shall be provided for a front loading
machine.
1004.11 Toilet and Bathing Facilities. Toilet and bathing fixtures shall comply with
Section 1004.11.
EXCEPTION: Fixtures on levels not required to be accessible.
1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be
provided for the future installation of grab bars and shower seats at water
closets, bathtubs, and shower compartments. Where walls are located to permit
the installation of grab closets; bars and grab seats bars complying with Section
with Section 604.5 607.4 at water at bathtubs; and for grab bars and shower
seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at
shower compartments; reinforcement shall be provided for the future installation
of grab bars and seats complying with those requirements.
EXCEPTIONS:
1. In a room containing only a lavatory and a water closet, reinforcement is
not required provided the room does not contain the only lavatory or
water closet on the accessible level of the unit.
2. At water closets reinforcement for the side wall vertical grab bar
component required by Section 604.5 is not required.
3. At water closets where wall space will not permit a grab bar complying
with Section 604.5.2, reinforcement for a rear wall grab bar 24 inches (610
mm) minimum in length centered on the water closet shall be provided.
4. At water closets where a side wall is not available for a 42-inch (1065
mm) grab bar complying with Section 604.5.1, reinforcement for a sidewall
grab bar, 24 inches (610 mm) minimum in length, located 12 inches (305 mm)
maximum from the rear wall, shall be provided.
5. At water closets where a side wall is not available for a 42-inch (1065
mm) grab bar complying with Section 604.5.1 reinforcement for a swing-up
grab bar complying with Section 1004.11.1.1 shall be permitted.
6. At water closets where a side wall is not available for a 42-inch (1065
mm) grab bar complying with Section 604.5.1 reinforcement for two
swing-up grab bars complying with Section 1004.11.1.1 shall be permitted to
be installed in lieu of reinforcement for rear wall and side wall grab bars.
7. In shower compartments larger than 36 inches (915 mm) in width and 36
inches (915 mm) in depth reinforcement for a shower seat is not required.
1004.11.1.1 Swing-up Grab Bars. A clearance of 18 inches (455 mm) minimum from
the centerline of the water closet to any side wall or obstruction shall be
provided where reinforcement for swingup grab bars is provided. When the
approach to the water closet is from the side, the 18 inches (455 mm) minimum
shall be on the side opposite the direction of approach. Reinforcement shall
accommodate a swing-up grab bar centered 153 / 4 inches (400 mm) from the
centerline of the water closet and 28 inches (710 mm) minimum in length,
measured from the wall to the end of the horizontal portion of the grab bar.
Reinforcement shall accommodate a swing-up grab bar with a height in the down
position of 33 inches (840 mm) minimum and 36 inches (915 mm) maximum.
Reinforcement shall be adequate to resist forces in accordance with Section
609.8.
EXCEPTION: Where a water closet is positioned with a wall to the rear and
to one side, the centerline of the water closet shall be 16 inches (405 mm)
minimum and 18 inches (455 mm) maximum from the sidewall.
TYPE B UNITS RE4UIRED IN INDIANA
1004.11.2 Clear Floor Space. Clear floor spaces required by Section 1004.11.3.1
(Option A) or 1004.11.3.2 (Option 8) shall comply with Sections 1004.11 .2 and
305.3.
1004.11.2.1 Doors. Doors shall not swing into the clear floor space or clearance
for any fixture.
EXCEPTION: Where a clear floor space complying with Section 305.3, excluding
knee and toe clearances under elements, is provided within the room beyond the
arc of the door swing.
1004.11.2.2 Knee and Toe Clearance. Clear floor space at fixtures shall be
permitted to include knee and toe clearances complying with Section 306.
1004.11.3 Toilet and Bathing Areas. Either all toilet and bathing areas provided
shall comply with Section 1004.11.3.1 (Option A), or one toilet and bathing area
shall comply with Section 1004.11 .3.2 (Option B).
1004.11.3.1 Option A. Each fixture provided shall comply with Section 1004.11.3.1.
EXCEPTIONS:
1. Where multiple lavatories are provided in a single toilet and bathing area
such that travel between fixtures does not require travel through other parts of
the unit, not more than one lavatory is required to comply with Section
1004.11.3.1.
2. A lavatory and a water closet in a room containing only a lavatory and
water closet, provided the room does not contain the only lavatory or water
closet on the accessible level of the unit.
1004.11.3.1.1 Lavatory. A clear floor space complying with Section 305.3,
positioned for a parallel approach, shall be provided at a lavatory. The clear
floor space shall be centered on the lavatory.
EXCEPTION: A lavatory complying with Section 606 shall be permitted. Cabinetry
shall be permitted under the lavatory provided the following criteria are met:
(a) The cabinetry can be removed without removal or replacement of the
lavatory; and
(b) The floor finish extends under the cabinetry; and
(c) The walls behind and surrounding the cabinetry are finished.28 min710Figure 1004.11.1.1
SWING-UP GRAB BAR FOR WATER CLOSET
15 3/4
400 LC
18 min
455
18 min
455
1004.11.3.1.2 Water Closet. The water closet shall comply with Section
1004.11.3.1.2.
1004.11.3.1.2.1 Location. The centerline of the water closet shall be 16 inches
(405 mm) minimum and 18 inches (455 mm) maximum from one side of the
required clearance.
1004.11.3.1.2.2 Clearance. Clearance around the water closet shall comply with
Sections 1004.11.3.1.2.2.1 through 1004.11.3.1.2.2.3.
EXCEPTION: Clearance complying with Sections 1003.11.2.4.2 through
1003.11.2.4.4.
1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48
inches (1220 mm) minimum in width, measured perpendicular from the side of the
clearance that is 16 inches (405 mm) minimum and 18 inches (455 mm) maximum
from the water closet centerline.
1004.11.3.1.2.2.2 Clearance Depth. Clearance around the water closet shall be 56
inches (1420 mm) minimum in depth, measured perpendicular from the rear wall.
1004.11.3.1.2.2.3 Increased Clearance Depth at Forward Approach. Where a
forward approach is provided, the clearance shall be 66 inches (1675 mm)
minimum in depth, measured perpendicular from the rear wall.
1004.11.3.1.2.2.4 Clearance Overlap. A vanity or other obstruction 24 inches
(610 mm) maximum in depth, measured perpendicular from the rear wall, shall be
permitted to overlap the required clearance, provided the width of the remaining
clearance at the water closet is 33 inches (840 mm) minimum.
1004.11.3.1.3 Bathing Fixtures. Where provided, a bathtub shall comply with
Section 1004.11.3.1.3.1 or 1004.11.3.1.3.2 and a shower compartment shall comply
with Section 1004.11.3.1.3.3.
1004.11.3.1.3.1 Parallel Approach Bathtubs. A clearance 60 inches (1525 mm)
minimum in length and 30 inches (760 mm) minimum in width shall be provided in
front of bathtubs with a parallel approach. Lavatories complying with Section
606 shall be permitted in the clearance. A lavatory complying with Section
1004.11.3.1.1 shall be permitted at one end of the bathtub if a clearance 48
inches (1220 mm) minimum in length and 30 inches (760 mm) minimum in width is
provided in front of the bathtub.
1004.11.3.1.3.2 Forward Approach Bathtubs. A clearance 60 inches (1525 mm)
minimum in length and 48 inches (1220 mm) minimum in width shall be provided in
front of bathtubs with a forward approach. A water closet and a lavatory shall
be permitted in I the clearance at one end of the bathtub.
1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing
facility, the shower compartment shall have dimensions of 36 inches (915 mm)
minimum in width and 36 inches (915 mm) minimum in depth. A clearance of 48
inches (1220 mm) minimum in length, measured perpendicular from the shower
head wall, and 30 inches (760 mm) minimum in depth, measured from the face of
the shower compartment, shall be provided. Reinforcing for a shower seat is not
required in shower compartments larger than 36 inches (915 mm) in width and 36
inches (915 mm) in depth.
1004.11.3.2 Option B. One of each type of fixture provided shall comply with
Section 1004.11.3.2. The accessible fixtures shall be in a single toilet/bathing
area, such that travel between fixtures does not require travel through other
parts of the unit.
LC
24 min
610
Clear Floor Space
Figure 1004.11.3.1
LAVATORY IN TYPE B UNITS - OPTION A
BATHROOMS
1004.11.3.2.1 Lavatory. Lavatories shall comply with Sections 1004.11.3.1.1 and
1004.11.3.2.1.1.
1004.11.3.2.1.1 Height. The front of the lavatory shall be 34 inches (865 mm)
maximum above the floor, measured to the higher of the rim or counter surface.
1004.11.3.2.2 Water Closet. The water closet shall comply with Section
1004.11.3.1.2. 1004.11.3.2.3 Bathing Fixtures. The accessible bathing fixture shall
be a bathtub complying with Section 1004.11.3.2.3.1 or a shower compartment
complying with Section 1004.11.3.2.3.2.
1004.11.3.2.3.1 Bathtub. A clearance 48 inches (1220 mm) minimum in length
measured perpendicular from the control end of the bathtub, and 30 inches (760
mm) minimum in width shall be provided in front of bathtubs. 1004.11.3.2.3.2
Shower Compartment. A shower compartment shall comply with Section
1004.11.3.1.3.3.
Figure 1004.11.3.1.2
CLEARANCE AT WATER CLOSETS IN TYPE B
UNITS
Figure 1004.11.3.1.3.1
PARALLEL APPROACH BATHTUB IN TYPE B UNITS - OPTION A
BATHROOMS
1004.12 Kitchens and kitchenettes. Kitchens and kitchenettes shall comply with
Section 1004.12.
1004.12.1 Clearance. Clearance complying with Section 1004.12.1 shall be
provided.
1004.12.1.1 Minimum Clearance. Clearance between all opposing base cabinets,
counter tops, appliances, or walls within kitchen work areas shall be 40 inches
(1015mm) minimum.
1004.12.1.2 U-Shaped Kitchens. In kitchens with counters, appliances, or cabinets
on three contiguous sides, clearance between all opposing base cabinets,
countertops, appliances, or walls within kitchen work areas shall be 60 inches
(1525 mm) minimum.
1004.12.2 Clear Floor Space. Clear floor space at appliances shall comply with
Sections 1004.12.2 and 305.3.
1004.12.2.1 Sink. A clear floor space, positioned for a parallel approach to the
sink, shall be provided. The clear floor space shall be centered on the sink bowl.
EXCEPTION: A sink with a forward approach complying with Section 1003.12.4.1.
1004.12.2.2 Dishwasher. A clear floor space, positioned for a parallel or
forward approach to the dishwasher, shall be provided. The dishwasher door in
the open position shall not obstruct the clear floor space for the dishwasher.
Figure 1004.11.3.1.3.2
FORWARD APPROACH BATHTUB IN
TYPE B UNITS - OPTION A
BATHROOMS
Figure 1004.11.3.2.1
LAVATORY IN TYPE B UNITS -
OPTION B BATHROOMS
Figure 1004.11.3.1..3.3
TRANSFER TYPE SHOWER
COMPARTMENT IN TYPE B UNITS
Figure 1004.11.3.2..3.1
BATHROOM CLEARANCE IN
TYPE B UNITS - OPTION B
BATHROOMS
1004.12.2.3 Cooktop. Cooktops shall comply with Section 1004.12.2.3.
1004.12.2.3.1 Approach. A clear floor space, positioned for a parallel or forward
approach to the cooktop, shall be provided.
1004.12.2.3.2 Forward approach. Where the clear floor space is positioned for a
forward approach, knee and toe clearance complying with Section 306 shall be
provided. The underside of the cooktop shall be insulated or otherwise
configured to prevent burns, abrasions, or electrical shock.
1004.12.2.3.3 Parallel approach. Where the clear floor space is positioned for a
parallel approach, the clear floor space shall be centered on the appliance.
1004.12.2.4 Oven. A clear floor space, positioned for a parallel or forward
approach adjacent to the oven shall be provided. The oven door in the open
position shall not obstruct the clear floor space for the oven.
1004.12.2.5 Refrigerator/Freezer. A clear floor space, positioned for a parallel
approach to the refrigerator/freezer, shall be provided. The centerline of the
clear floor space shall be offset 24 inches (610 mm) maximum from the
centerline of the appliance.
1004.12.2.6 Trash Compactor. A clear floor space, positioned for a parallel or
forward approach to the trash compactor, shall be provided.
L C
16-18
405-455
Edge of
clearance, wall,
fixture or
other
obstruction
(a) Water closet location
LC
16-18
405-455
(b) Clearance Width and
Depth
48 min
122056 min1420L C
16-18
405-455
(c) Increased Clearance
Depth - Forward
Approach
48 min
122066 min1675LC
16-18
405-455
(d) Clearance with
Lavatory Overlap
33 min
840
60 min 30 min7601525control end wallhead end wallback wall
(a)
Lavatory
complying
with
Section
606
48 min 30 min7601220control end wallhead end wallback wall
(b)
Lavatory complying
with Section
1004.11.3.1.1
LC
60 min 30 min7601525control end wallhead end wallback wall
46 max1170Height
48 min
1220 91536 min36
915
91536 mincontrol
wall
back wall
seat
wall
48 min 30 min7601220control end wallhead end wallback wall
(a)(b)
A045 ARCHITECTCLIENTCONSTRUCTION MANAGERPROJECTDRAWING TITLESEALSHEETPROJECT INFOREVISIONS20011
APRIL 28, 2021AVANT PHASE IICARMEL, INEDWARD ROSEDEVELOPMENTCARMEL LLC.PERMIT SET
No. AR12000062
STATE OF
MDXELA
ARS
H
T E C TCHI
AR
STGI
R E E
DER
IANDI N AANSI STANDARDSTYPE B UNITS10/11/21