HomeMy WebLinkAboutE501 - ELECTRICAL DETAILSCU GRD. BAR RACKS MDF & IDF'S MAIN EQUIPMENT BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) N G COMMUNICATIONS SYSTEMS EQUIPMENT CABINET GROUND COMMUNICATIONS PLYWOOD BACKBOARD GROUND BAR TELEPHONE SERVICE DEMARK GROUND BAR EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS G NEUTRAL BUS GROUND BUS #3/0 CU EQUIPMENT BONDING JUMPER BONDING BUSHING (TYP) SERVICE EQUIPMENT ENCLOSURE (MAIN SWITCHBOARD) MAIN BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) PANELBOARD 3/4"X10' CU GROUND RODINCOMING METAL WATER SERVICE #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR 3/4"X10' CU GROUND ROD INCOMING SERVICE METAL CONDUITS #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR TRANSFORMER C N B A NTL AS SHOWN ON DRAWINGS NO GROUND CABLE UTILITY TRANSFORMER #3/0 CU10'-0"10 '-0"10'-0" 3/0 COPPER CABLE EXOTHERMICALLY WELD CABLE TO GROUND RODS 3/4" DIA. X 10' LONG COPPER CLAD STEEL GROUND ROD 3/0 COPPER CABLE EXIT NOTES: 1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. 2. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COURSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED. CEILING F H S E VC IC FSYMBOLS: FLOOR W C S M96"96"72"48"96"96"96"72"48"16"48"48"84"CB CB FACP ZAM ZAM ZAM SS SS SS ZAM ZAM CB 2#14, 3/4"C. (MAY BE COMBINED IN A SINGLE RACEWAY) TELE. OUTLET SECOND FLOOR LOBBY IN HOISTWAY IN ELEVATOR EQUIPMENT ROOMFIRST FLOOR LOBBY #18 SHIELDED TWISTED PAIR INDUSTRIAL VAPORTITE FIXTURE IN PIT GFI RECEPTACLE 208V, 3ø ELEVATOR POWER FEED, SIZED PER ONE LINE DIAGRAM 2#12,#12G., 3/4"C. CAB CAB HVAC CONTROL CAB LIGHTS BY DIVISION 26 BY ELEVATOR MANUFACTURER/ INSTALLER TO 208V PANEL PER PLANS IN HOISTWAY ROOM EQUIPMENT IN ELEVATOR FIRST FLOOR LOBBY BY DIV. 16 THIRD FLOOR LOBBY SECOND FLOOR LOBBY FOURTH FLOOR LOBBY THIRD FLOOR LOBBYFOURTH FLOOR LOBBY NOTES: 1. PROVIDE ENGRAVED PHOENELIC NAMEPLATE ON DISCONNECTS STATING MORE THAN ONE SOURCE SERVES THE ELEVATOR CABINET. 2. SHOULD THE GENERAL CONTRACTOR UTILIZE AN ELEVATOR MANUFACTURER THAT REQUIRE MORE ELECTRICAL WORK THAN SHOWN ON THIS DETAIL, THE COSTS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 3. IF ELEVATOR CAN BE OPERATED FROM NEC 702 OPTIONAL POWER SYSTEM, ALL HVAC EQUIPMENT SERVING THE ELEVATOR EQUIPMENT ROOM SHALL BE CONNECTED TO THE OPTIONAL POWER SYSTEM. 4. EQUIPMENT SHOWN SHADED IS BY ELEVATOR MANUFACTURER. ITEMS SHOWN DARK ARE BY DIVISION 26. TO 208/120V PANEL DEDICATED CIRCUIT TO 208/120V PANEL DEDICATED CIRCUIT IN ELEVATOR HOISTWAY GFI RECEPTACLE 2#12,#12G., 3/4"C. TO 208/120V PANEL DEDICATED CIRCUIT TO 480/277V PANEL DEDICATED CIRCUIT LIGHT FIXTURES IN ROOM 2#14, 3/4"C. 208V 3ø CIRCUIT BREAKER, PER ONE LINE DIAGRAM WITH AUXILIARY N.O. CONTACT IN ELEVATOR MACHINE ROOM 20A/1P CIRCUIT BREAKER IN ELEVATOR MACHINE ROOM 2#10, #10G., 3/4"C. TO 208/120V PANEL PER PLANS C C C C C C C C 2' - 0"3" 3"*5'-0" (4) #4 REBAR (<15' POLE)*6'-0" (4) #4 REBAR (15'-25' POLE)*7'-0" (5) #4 REBAR (26'-40' POLE)30"48"12"SUB GRADE FINISHED PAVEMENT PROVIDE VENDOR BASE COVERS TO MATCH POLE IN COLOR POLE GROUNDING LUG OPPOSITE OF HANDHOLE TYPICAL COIL EXCESS TO ALLOW FUSES AND CONNECTORS TO BE REMOVED THRU HANDHOLE #10 GROUND AND NEUTRAL KEEP SPACE BETWEEN BOLT COVERS AND FOUNDATION TO A MINIMUM. CAULK NEATLY ALL AROUND TO FILL GAPS. GROUT COLOR SHALL MATCH POLE 1/2" PVC CONDUIT YELLOW, METAL BACKED POLYETHELENE TAPE MARKED "ELECTRIC" #6 BARE STRANDED COPPER GROUND CABLE EXOTHERMIC WELD SCHEDULE 40 PVC CONDUIT TO NEXT POLE (1" MINIMUM) EXCEPT WHERE NOTED REINFORCING STEEL REQUIRED, BUT NOT COMPLETELY SHOWN LEVELING NUTS WITH WASHERS. PROTECT NUTS AND THREADS DURING CONCRETE POUR. TYPICAL FOURWAY BOLTED CONNECTOR WITH WATERPROOF INSULATION (MAX. 4 #10 COPPER) HANDHOLE WITH COVERPLATE TYPICAL WATERTIGHT IN LINE FUSE HOLDER WITH FUSE SIZED PER MANUFACTURER RECOMMENDATION FOR EACH PHASE CONDUCTOR #10 PHASE CONDUCTORS UP TO LUMINAIRE (1 OR 2 CONDUCTORS) FINISHED GRADE TOP OF BOX TO BE NO MORE THAN +48" AFF BOTTOM OF BOX TO BE NO LESS THAN +16" AFF OPEN BOX MOUNTING BRACKET TO BE USED WHEN BOX LARGER THAN 2- GANG IS REQUIRED WALL STUD (TYP) TYPICAL BOX MOUNTING BRACKET NOTES: 1. BOX MOUNTING BRACKETS ARE TO BE USED WHEN MOUNTING MULTIPLE BOXES WITHIN THE SAME STUD SPACE. 2. WHEN RECEPTACLES ARE SHOWN BELOW SWITCHES ALIGN VERTICALLY. DATA OUTLET AT +90" AFF TO HAVE (6) RJ45 PORTS BEHIND SINGLE WALL PLATE. PROVIDE CAT-6 HOMERUN TO DATA ROOM ON ASSOCIATED FLOOR. PROVIDE ADDITIONAL CAT-6 CABLE TO EACH DATA OUTLET SHOWN WITHIN APARTMENT UNIT. MIKROTIK RB260GS (OR EQUAL) DATA SWTICH A/C ADAPTER DUPLEX RECEPTACLE +90" AFF.ARCHITECTCLIENT CONSULTANT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONSKBSO Consulting1344 S Rangeline Rd. Suite 202CARMEL, INDIANA 46032P: 317-344-8044PERMIT SET APRIL 28TH, 2021 20005THE AVANTPHASE IIE501ELECTRICAL DETAILS CARMEL,INNOT TO SCALE GROUNDING SYSTEM DETAIL2 NOT TO SCALE SERVICE GROUNDING ELECTRODE ARRANGEMENT3 3/8" = 1'-0" TYPICAL ELECTRICAL ELEVATION1 12" = 1'-0" TYPICAL ELEVATOR WIRING DIAGRAM4 1" = 1'-0" LIGHT POLE BASE5 1/2" = 1'-0" TYPICAL BOX SUPPORT DETAIL 6 12" = 1'-0" TYPICAL APARTMENT DATA SWITCH7 # DESCRIPTION DATE 10/11/21