HomeMy WebLinkAboutE501 - ELECTRICAL DETAILSCU GRD. BAR
RACKS
MDF & IDF'S
MAIN EQUIPMENT BONDING
JUMPER (SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
N G
COMMUNICATIONS SYSTEMS
EQUIPMENT CABINET GROUND
COMMUNICATIONS PLYWOOD
BACKBOARD GROUND BAR
TELEPHONE SERVICE
DEMARK GROUND BAR
EQUIPMENT
GROUND -
SIZE AS
SHOWN ON
DRAWINGS
G
NEUTRAL BUS
GROUND BUS
#3/0 CU EQUIPMENT
BONDING JUMPER
BONDING BUSHING (TYP)
SERVICE EQUIPMENT ENCLOSURE
(MAIN SWITCHBOARD)
MAIN BONDING JUMPER
(SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
PANELBOARD
3/4"X10' CU
GROUND RODINCOMING
METAL
WATER
SERVICE
#3/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
3/4"X10' CU GROUND ROD
INCOMING SERVICE
METAL CONDUITS
#3/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
TRANSFORMER
C
N
B A
NTL AS SHOWN
ON DRAWINGS
NO GROUND CABLE
UTILITY
TRANSFORMER #3/0 CU10'-0"10 '-0"10'-0"
3/0 COPPER CABLE
EXOTHERMICALLY
WELD CABLE TO
GROUND RODS
3/4" DIA. X 10' LONG
COPPER CLAD STEEL
GROUND ROD
3/0 COPPER CABLE
EXIT NOTES:
1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS
INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS
OR IN THE SPECIFICATIONS.
2. WHERE DEVICES ARE LOCATED IN MASONRY WALLS
LOCATE DEVICE WITHIN COURSING SO THAT MOUNTING
INDICATED HERE IN IS NOT EXCEEDED.
CEILING
F
H
S
E
VC IC FSYMBOLS:
FLOOR
W
C S M96"96"72"48"96"96"96"72"48"16"48"48"84"CB CB
FACP
ZAM ZAM
ZAM
SS SS SS
ZAM ZAM CB
2#14, 3/4"C. (MAY BE
COMBINED IN A SINGLE
RACEWAY)
TELE.
OUTLET
SECOND
FLOOR
LOBBY
IN HOISTWAY
IN ELEVATOR
EQUIPMENT ROOMFIRST
FLOOR
LOBBY
#18 SHIELDED TWISTED PAIR
INDUSTRIAL
VAPORTITE FIXTURE
IN PIT
GFI
RECEPTACLE
208V, 3ø ELEVATOR
POWER FEED, SIZED PER
ONE LINE DIAGRAM
2#12,#12G., 3/4"C.
CAB
CAB
HVAC
CONTROL
CAB LIGHTS
BY DIVISION 26
BY ELEVATOR MANUFACTURER/
INSTALLER
TO 208V PANEL PER
PLANS
IN HOISTWAY
ROOM
EQUIPMENT IN
ELEVATOR
FIRST
FLOOR
LOBBY
BY DIV. 16
THIRD
FLOOR
LOBBY
SECOND
FLOOR
LOBBY
FOURTH
FLOOR
LOBBY
THIRD
FLOOR
LOBBYFOURTH
FLOOR
LOBBY
NOTES:
1. PROVIDE ENGRAVED PHOENELIC NAMEPLATE ON DISCONNECTS STATING MORE THAN ONE SOURCE SERVES
THE ELEVATOR CABINET.
2. SHOULD THE GENERAL CONTRACTOR UTILIZE AN ELEVATOR MANUFACTURER THAT REQUIRE MORE
ELECTRICAL WORK THAN SHOWN ON THIS DETAIL, THE COSTS SHALL BE THE RESPONSIBILITY OF THE
GENERAL CONTRACTOR.
3. IF ELEVATOR CAN BE OPERATED FROM NEC 702 OPTIONAL POWER SYSTEM, ALL HVAC EQUIPMENT SERVING
THE ELEVATOR EQUIPMENT ROOM SHALL BE CONNECTED TO THE OPTIONAL POWER SYSTEM.
4. EQUIPMENT SHOWN SHADED IS BY ELEVATOR MANUFACTURER. ITEMS SHOWN DARK ARE BY DIVISION 26.
TO 208/120V PANEL
DEDICATED
CIRCUIT
TO 208/120V PANEL
DEDICATED
CIRCUIT
IN ELEVATOR
HOISTWAY
GFI
RECEPTACLE
2#12,#12G., 3/4"C.
TO 208/120V PANEL
DEDICATED
CIRCUIT
TO 480/277V PANEL
DEDICATED
CIRCUIT
LIGHT
FIXTURES
IN ROOM
2#14,
3/4"C.
208V 3ø CIRCUIT BREAKER,
PER ONE LINE DIAGRAM WITH
AUXILIARY N.O. CONTACT IN
ELEVATOR MACHINE ROOM
20A/1P
CIRCUIT BREAKER
IN ELEVATOR MACHINE
ROOM
2#10, #10G., 3/4"C.
TO 208/120V
PANEL
PER PLANS
C
C
C
C
C
C
C
C
2' - 0"3" 3"*5'-0" (4) #4 REBAR (<15' POLE)*6'-0" (4) #4 REBAR (15'-25' POLE)*7'-0" (5) #4 REBAR (26'-40' POLE)30"48"12"SUB GRADE
FINISHED
PAVEMENT
PROVIDE VENDOR BASE COVERS
TO MATCH POLE IN COLOR
POLE GROUNDING LUG
OPPOSITE OF HANDHOLE
TYPICAL COIL EXCESS TO
ALLOW FUSES AND
CONNECTORS TO BE
REMOVED THRU HANDHOLE
#10 GROUND
AND NEUTRAL
KEEP SPACE BETWEEN BOLT COVERS
AND FOUNDATION TO A MINIMUM. CAULK
NEATLY ALL AROUND TO FILL GAPS.
GROUT COLOR SHALL MATCH POLE
1/2" PVC CONDUIT
YELLOW, METAL BACKED
POLYETHELENE TAPE
MARKED "ELECTRIC"
#6 BARE STRANDED
COPPER GROUND
CABLE
EXOTHERMIC WELD
SCHEDULE 40 PVC CONDUIT
TO NEXT POLE (1" MINIMUM)
EXCEPT WHERE NOTED
REINFORCING STEEL
REQUIRED, BUT NOT
COMPLETELY SHOWN
LEVELING NUTS WITH WASHERS. PROTECT
NUTS AND THREADS DURING CONCRETE POUR.
TYPICAL FOURWAY BOLTED CONNECTOR WITH
WATERPROOF INSULATION (MAX. 4 #10 COPPER)
HANDHOLE WITH COVERPLATE
TYPICAL WATERTIGHT IN LINE FUSE HOLDER
WITH FUSE SIZED PER MANUFACTURER
RECOMMENDATION FOR EACH PHASE CONDUCTOR
#10 PHASE CONDUCTORS UP TO
LUMINAIRE (1 OR 2 CONDUCTORS)
FINISHED GRADE
TOP OF BOX TO BE NO
MORE THAN +48" AFF
BOTTOM OF BOX TO BE
NO LESS THAN +16" AFF
OPEN BOX MOUNTING BRACKET TO
BE USED WHEN BOX LARGER THAN 2-
GANG IS REQUIRED
WALL STUD (TYP)
TYPICAL BOX MOUNTING
BRACKET
NOTES:
1. BOX MOUNTING BRACKETS ARE TO BE USED WHEN MOUNTING
MULTIPLE BOXES WITHIN THE SAME STUD SPACE.
2. WHEN RECEPTACLES ARE SHOWN BELOW SWITCHES ALIGN
VERTICALLY.
DATA OUTLET AT +90" AFF TO HAVE
(6) RJ45 PORTS BEHIND SINGLE WALL
PLATE. PROVIDE CAT-6 HOMERUN TO
DATA ROOM ON ASSOCIATED FLOOR.
PROVIDE ADDITIONAL CAT-6 CABLE
TO EACH DATA OUTLET SHOWN
WITHIN APARTMENT UNIT.
MIKROTIK
RB260GS
(OR EQUAL)
DATA SWTICH
A/C ADAPTER
DUPLEX
RECEPTACLE
+90" AFF.ARCHITECTCLIENT CONSULTANT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONSKBSO Consulting1344 S Rangeline Rd. Suite 202CARMEL, INDIANA 46032P: 317-344-8044PERMIT SET
APRIL 28TH, 2021
20005THE AVANTPHASE IIE501ELECTRICAL DETAILS CARMEL,INNOT TO SCALE
GROUNDING SYSTEM DETAIL2
NOT TO SCALE
SERVICE GROUNDING ELECTRODE ARRANGEMENT3
3/8" = 1'-0"
TYPICAL ELECTRICAL ELEVATION1
12" = 1'-0"
TYPICAL ELEVATOR WIRING DIAGRAM4
1" = 1'-0"
LIGHT POLE BASE5
1/2" = 1'-0"
TYPICAL BOX SUPPORT DETAIL 6
12" = 1'-0"
TYPICAL APARTMENT DATA SWITCH7
# DESCRIPTION DATE
10/11/21