HomeMy WebLinkAboutM404 - ENLARGED MECHANICAL PLANS09/A440
TEW3dwrefim02/A440
01/A440
T
3
M404
5
M404
CLUBHOUSE
LOUNGE
110
1 2
11
6
7
10
6
6
6
6
3
110 CFM
1 2 120 CFM
9
FCU-4
FCU-4
6ø
SR-2SR -2 -200
SR-2SR -2 -200
SR-2SR -2 -200
SR-2SR -2 -200
SR-2SR -2 -200
6ø
18/12
16/12
4ø
4ø
6ø
EF-1
EF-1
L-1
8ø
ø8
ø8
ø8
ø 8
ø8
16/1210/10
6ø
SR-1SR -1 -100
6
16/12
SR-1SR -1 -50
SR-1SR -1 -50 SR-1SR -1 -50 SR-1SR -1 -50
SR-2SR -2 -150
SR-2SR -2 -150 SR-2SR -2 -150 SR-2SR -2 -250
SR-2SR -2 -150
SR-2SR -2 -150
14/10
1 4
3
6
6 6
6
6
6 6 6
6
6
2
280 CFM
4
M404
SOCIAL HUB
101
FOCUS BOOTH
104
FOCUS BOOTH
105
FOCUS BOOTH
106
FOCUS BOOTH
107
CONFERENCE
ROOM
103
CONFERENCE
ROOM
102
L-1
FCU-5
ø6
ø8
ø 6
ø8
ø 6
26/6 16/14 16/12 12/10
ø6
ø8
ø8
ø8
ø8
RG-213
12/18
20/16
6ø
RG-2
FCU-4
12/16
20/16
14/14
FCU-4
8ø
20/16
FCU-5FCU-4 8ø
16/12 FD
20/16
FD24/24 ARCHITECTCLIENT CONSULTANT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONSKBSO Consulting1344 S Rangeline Rd. Suite 202CARMEL, INDIANA 46032P: 317-344-8044PERMIT SET
APRIL 28TH, 2021
20005THE AVANTPHASE IIM404ENLARGEDMECHANICAL PLANSCARMEL,INGENERAL NOTES
A REFER TO SHEET P-000 FOR GENERAL PLUMBING NOTES, SYMBOLS AND
ABBREVIATIONS.
B REFER TO SHEET M500 SERIES DRAWINGS FOR MECHANICAL DETAILS.
C REFER TO SHEET M600 SERIES DRAWINGS FOR MECHANICAL SCHEDULES.
D COORDINATE WITH STRUCTURAL AND FRAMING PLANS PRIOR TO
COMMENCING WORK. COORDINATE ALL ROUTING WITH ALL TRADES PRIOR TO
FABRICATION.
E SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND TYPES OF RATED
CONSTRUCTION. CONSTRUCTION RATINGS ARE TO BE MAINTAINED.
F SEAL ALL FLOOR, CEILING, AND WALL PENETRATIONS. USE FIRE CAULK AT
RATED ASSEMBLIES AND GENERAL SEALANT ELSEWHERE. WHERE
NON-METALLIC COMPONENTS LARGER THAN 4" DIA.(I.E. PVC OR CONDUIT)
PENETRATES RATED ASSEMBLIES, INSTALL INTUMESCENT COLLAR. WHERE
DUCTWORK LARGER THAN 4" DIA. PENETRATES RATED ASSEMBLIES, INSTALL
FIRE DAMPER.
G SIZE AND INSTALL REFRIGERANT PIPING AND ACCESSORIES PER
MANUFACTURERS RECOMMENDATIONS.
H ALL EXTERIOR VENT CAP AND VENT HOOD COLLARS TO BE VERIFIED IN SHOP
DRAWINGS.
I ALL FAN COIL UNITS TO BE WALL MOUNTED UNLESS OTHERWISE INDICATED.
COORDINATE MOUNTING HEIGHT WITH OTHER DICIPLINES AND SPACE.
J THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SIGN
ATTACHED TO THE DRYER BOW IN EACH APARTMENT. THE TAG SHALL
DOCUMENT THE ASSOCIATED INSTALLED DRYER VENT AND READ AS
FOLLOWS: CONNECTED VENT DUCT: STRAIGHT DUCT: X FEET, 90 DEG. ELBOW:
COUNT=X, 45 DEG. ELBOW: COUNT=X.
K THERMOSTATS TO BE MOUNTED 48-INCHES A.F.F. TO TOP OF
SENSOR, OR ALIGNED WITH ADJACENT SWITCHES UNLESS
OTHERWISE NOTED.
L DRYER EXHAUST DUCTWORK TO BE MINIMUM 28 GAUGE.
M PROVIDE MECHANICAL SYSTEMS IN COMPLIANCE WITH STATE
AND LOCAL CODES.
SHEET KEYNOTES
1 FCU TO BE MOUNTED ON WALL PER MANUFACTURERS RECOMMENDATIONS
ABOVE WATER HEATER. SEE DETAIL ON SHEET M501.
2 ROUTE REFRIGERANT LINES THRU WALL FROM CONDENSING UNIT ON ROOF
TO FCU. COORDINATE EXACT ROUTE WITH PLUMBING LINES. ALL
PENETRATIONS THROUGH RATED ASSEMBLIES ARE TO BE FIRE SEALED.
3 THERMOSTAT EQUAL TO HONEYWELL MODEL #RLV4305 TO BE MOUNTED IN
THIS APPROXIMATE LOCATION 48-INCHES A.F.F. OR ALIGNED TO ADJACENT
LIGHT SWITCHES.
4 ROUTE SUPPLY AIR DUCT MAIN BETWEEN TRUSSES.
5 PROVIDE WALL CAP BY BUILDER'S BEST MODEL "110113" WITH BACK-DRAFT
DAMPER. FINAL COLOR TO BE DETERMINED BY ARCHITECT. TERMINATE A
MINIMUM OF 3-FEET FROM ANY OPERABLE OPENING.
6 PROVIDE CEILING RADIATION DAMPER.
7 INSTALL EXHAUST FAN IN WALL 7' A.F.F. PER MANUFACTURERS
RECOMMENDATIONS.
8 SEE CONTINUATION ON SHEET M101B.
9 SEE CONTINUATION ON SHEET M101A.
10 PROVIDE WALL CAP BY BUILDER'S BEST MODEL "111777" WITH BACK-DRAFT
DAMPER. FINAL COLOR TO BE DETERMINED BY ARCHITECT. TERMINATE A
MINIMUM OF 3-FEET FROM ANY OPERABLE OPENING.
11 ROUTE SUPPLY AIR DUCT MAIN IN BULKHEAD.
13 MOUNT RETURN GRILLE ABOVE DOOR.
1/4" = 1'-0"
ENLARGED CLUBHOUSE MECHANICAL PLAN11/4" = 1'-0"
ENLARGED SOCIAL CLUB MECHANICAL PLAN2
3/8" = 1'-0"
CLUBHOUSE MECHANICAL SYSTEM3
3/8" = 1'-0"
SOUTH CORRIDOR MECHANICAL SYSTEM 5 3/8" = 1'-0"
SOCIAL HUB MECHANICAL ROOM 4
# DESCRIPTION DATE
3/8" = 1'-0"
NORTH CORRIDOR MECHANICAL SYSTEM. 6
10/11/21