HomeMy WebLinkAboutP501 - PLUMBING DETAILSBALL VALVE
REDUCED PRESSURE BACKFLOW
PREVENTER, MAXIMUM MOUNTING
HEIGHT OF 5'-0" ABOVE FLOOR.
BALL VALVE
TO SYSTEM
FROM WATER
SUPPLY SOURCE
AIR GAP DRAIN FUNNEL
PIPE DISCHARGE TO FLOOR DRAIN
TYPE AND SIZE.
REFER TO PLANS AND SPECIFICATIONS FOR
BRASS CLEANOUT PLUG WITH COUNTERSUNK HEAD
1/8" BEND IF CLEANOUT OCCURS AT END OF LINE.
18"X18"X4" SQUARE CONCRETE PAD.
TROWEL SMOOTH AND EDGE
WASTE LINE
1/8" BEND
1 1/2" VENT
1/2"CW
1/2"HW
SHUTOFF VALVE WITH THREADED
HOSE CONNECTION. PROVIDE WITH
WATER HAMMER ARRESTOR
2" WASTE
P-TRAP WITH UNION
CONNECTIONS
FLOOR LINE
CLOTHES WASHER RECESSED
WALL BOX WITH FACE PLATE;
EQUAL TO GUY GRAY SERIES
RECESSED WALL BOXES.
TRAP SHALL NOT BE INSTALLED
BELOW FLOOR BUT SHALL
BE ROUGHED IN NOT LESS
THAN 6" AND NOT MORE
THAN 18" ABOVE FLOOR.
NO STANDPIPE RECEPTOR SHALL
EXTEND MORE THAN 30" NOR
LESS THEN 18" ABOVE ITS TRAP.
TEES, PLUGS & HYDRANTS
TEES, PLUGS & HYDRANTS ELBOWS
4. A BEARING CAPACITY OF 2000# PER FOOT WAS USED IN DETERMINING THE MINIMUM
1. THRUST BLOCK SHALL BE FC'=2500 PSI @ 28 DAYS (SEE SPECIFICATIONS SECTION 03300)
BEARING AREA (SQUARE FEET)
ELBOWS
5. THE CROSS SECTION OF THE THRUST BLOCKS SHALL BE SQUARE.
"BEARING AREAS" IN THE ABOVE TABLES.
3. BOLTS, FITTING & JOINTS SHALL BE KEPT CLEAR OF CONCRETE.
2. ALL THRUST BLOCKS SHALL BE POURED AGAINST UNDISTURBED EARTH."A"3.518 21.0
20 4.0 26.0
2.0 6
8
16
12
10
2.5
2.5
3.0
3.0
4
INCHES
PIPE DIA.
2.0
"A"
FEET
2.9
4.8
17.1
10.0
7.1
1.5
SQUARE FEET
BEARING AREA
18 3.0 30.0
20 3.0 36.8
4
INCHES
8
10
12
16
6
PIPE DIA.
2.0
3.0
3.0
2.5
2.0
6.8
4.1
10.1
14.1
24.2
FEET
"A"
1.5
90°
2.1
8.316.3 4.2
19.9 10.1 5.1
3.7
13.0
7.6
5.5
2.2
1.9
2.8
3.9
6.7
1.1
45°
1.1 0.6
22-1/2°
0.9
1.4
0.6
3.3
2.0
11-1/4°
0.3
"A"
SINK
(SK-1)
SHUT-OFF VALVE
REDUCER
GARBAGE
DISPOSAL
(WD-1)
5/8" DRAIN
HOSE
1 1/2" VENT
2" SAN
DISHWASHER
1/2" HW
CW SUPPLY
HW SUPPLY
CODE APPROVED
AIR ADMITTANCE
VALVE (AAV)
COUNTERTOP
4" MIN.
INSTALL AS HIGH AS
POSSIBLE UNDER
THE COUNTERTOP
SYSTEM RISER
CAST IRON FLANGE
AND SPIGOT PIECE.
CAST IRON BELL
AND SPIGOT PIPE.
THRUST BLOCKING.
RODS
FIRE SERVICE
MAIN
RESTRAINT
BUILDING SLAB
PIPE
DOUBLE SUPPORT NUT
LOCKING NUT
HANGER ROD HANGER ROD
LOCKING NUT
SUPPORT NUTCLEVIS HANGER
14 GAUGE ZINC COATED
SHEET STEEL SADDLE
AT LEAST 12" LONG
PIPE
INSULATION
INSULATION
PREFORMED PIPE SUPPORT INSERT,
SAME THICKNESS AS INSULATION MANUFACTURED FOR THIS PURPOSE.
RPBP-1A
METER
RPBP-1B
METER
REDUCED PRESSURE ZONE
TYPE BACKFLOW PREVENTER
4"CW TO BUILDING
SERVICE
PROVIDE REMOTE WATER
METER READ OUTS
NEEDLE VALVE
PRESSURE GAUGE
FINISHED FLOOR
SUPPORT PIPING AS REQUIRED
TYPICAL DRAIN FUNNEL WITH AIR
GAP, TERMINATE DRAIN LINE OVER
NEAREST FLOOR DRAIN
4"CW INCOMING WATER SERVICE
FLOOR SLEEVE
COUPLING ADAPTOR (TYP)
GATE VALVE (TYP)MAXIMUM MOUNTINGHEIGHT OF 5'-0"ABOVE FLOOR.1. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH UTILITY COMPANY'S
REQUIREMENTS. WATER METER FURNISHED BY LOCAL UTILITY, CONTRACTOR INSTALLED.
NOTE:
4"CW 4"CW
FINISH HEIGHT OF
ROOF HYDRANT TO BE
MIN OF 3'-0" A.F.R.
ROOF MEMBRANE
3/4" COLD WATER
PENETRATION BOOT & FLASHING TO
MEMBRANE ROOFING BY ROOFING
CONTRACTOR. REFER TO MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION
PROVIDE STAINLESS STEEL
CLAMPING BAND
SURE SEAL WATER CUT-OFF MASTIC
ROOF DECK - SEE ARCHITECTURAL
DRAWINGS FOR CONSTRUCTION
OPENING IN DECK BY PLUMBING
CONTRACTOR
HEAD CASTING
DUAL CHECK
VALVE
3/4" HOSE CONNECTION
HANDLE
WATER TIGHT SEAL
UNDER DECK FLANGE
MOUNTING BOLTS (4)MIN OF 10"OR CUSHION STRIP
NEOPRENE ISOLATORTHREADED STEEL HANGER ROD
SYSTEM PIPE (REFER TO
DRAWINGS FOR TYPE OF
STRUT PIPE CLAMP
UNI-STRUT TRAPEZE SUPPORTINSULATION
PIPE INSULATION MATERIAL
(REFER TO SPECIFICATIONS)
STEEL ROD COUPLING SYSTEM AND PIPE SIZE)
BLOCKING
ASME T&P RELIEF VALVE
HEAT TRAPS
BALL VALVE WITH RELIEF VALVE
EQUAL TO WATTS #LFBRV
HW
HVAC FURNACE
CW HW
CWHWCWR
WALL
THERMOMETER
WALL
SEE FLOOR PLANS
FOR SIZE OF COLD
WATER PIPE MAINS
CEILING
3"X2" OPEN SITE
DRAIN (OSD)
FINISH FLOOR
DRAIN PAN
FULL SIZE DRAIN VALVE
FULL SIZE TO OSD
DRAIN TUBE TO OSD
NOTE:
WHERE CONNECTING DISSIMILAR
MATERIALS, FITTINGS ARE TO BE
DIELECTRIC.
DOMESTIC
TANK TYPE
ELEC. WATER
HEATER
(DWH-1)
UNIT
MECHANICAL
CLOSET
TO FIXTURES
IN UNIT
3/4"CW
3/4"HW 3/4"CW
3/4"CW
3/4"HW
3/4"CW
USB-1 TET-1
(DWH-2)
TET-2
(SEE ENLARGED
FLOOR PLANS)
PENETRATION BOOT & FLASHING TO
MEMBRANE ROOFING BY ROOFING
CONTRACTOR BASED ON CARLISLE U-8-A.
REFER TO MANUFACTURER'S
RECOMMENDATIONS FOR INSTALLATION.
PROVIDE STAINLESS STEEL
CLAMPING BAND
SURE SEAL WATER CUT-OFF MASTIC
ROOK DECK - SEE ARCHITECTURAL
DRAWINGS FOR CONSTRUCTION.
OPENING IN DECK BY PLUMBING
CONTRACTOR.
SEE DRAWINGS FOR SIZE
REDUCER AS REQUIRED
PIPE SIZE PER DRAWINGS12"ARCHITECTCLIENT CONSULTANT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONSKBSO Consulting1344 S Rangeline Rd. Suite 202CARMEL, INDIANA 46032P: 317-344-8044PERMIT SET
APRIL 28TH, 2021
20005THE AVANTPHASE IIP501PLUMBING DETAILS CARMEL,INNOT TO SCALE
BACKFLOW PREVENTER DETAIL 1
NOT TO SCALE
CLEANOUT DETAIL2
NOT TO SCALE
CLOTHES WASHER BOX PIPING DETAIL3
NOT TO SCALE
CONCRETE THRUST BLOCK DETAIL4
NOT TO SCALE
DISHWASHER/DISPOSAL/SINK DEATIL5
NOT TO SCALE
INCOMING FIRE SERVICE CONNECTION DETAIL6
NOT TO SCALE
PIPE HANGER DETAIL7
NOT TO SCALE
INCOMING DOMESTIC WATER SERVICE DETAIL9
NOT TO SCALE
ROOF HYDRANT DETAIL10
NOT TO SCALE
TRAPEZE DETAIL 11
NOT TO SCALE
UNIT WATER HEATER DETAIL12
NOT TO SCALE
VENT THRU ROOF DETAIL13
# DESCRIPTION DATE
10/11/21