HomeMy WebLinkAboutE104-BGENERAL COMMON AREA NOTES 1. ALL EXTERIOR LIGHTING CONTROLLED BY PHOTOCELL UNLESS OTHERWISE NOTED. 2. VERIFY ALL EQUIPMENT REQUIREMENTS AND LOCATIONS WITH INSTALLERS PRIOR TO ROUGH IN. 3. PROVIDE (1) 2OA 12OV gfci PROTECTED RECEPTACLE WITHIN 25' OF ALL EXTERIOR MECHANICAL EQUIPMENT. USE "IN-USE" STYLE WEATHER PROOF COVERS IDENTIFIED AS "EXTRA-DUTY". USE EXTERIOR RATED RECEPTACLES. 4. EXHAUST FAN IN RESTROOMS BY M.C., PROVIDE WIRING AND CONNECTION. POWER WITH LOCAL AREA SWITCHED LIGHTING CIRCUIT. 1 HEATER BY M.C., PROVIDE CIRCUIT AND CONNECTION. 2 EXHAUST FAN BY M.C., PROVIDE CIRCUIT, DISCONNECT (IF SHOWN) AND CONNECTION. CONTROL WIRING IF REQUIRED, BY OTHERS. 3 24/7 EXHAUST FAN BY M.C., PROVIDE WIRING AND CONNECTION. POWER WITH LOCAL AREA LIGHTING CIRCUIT. 4 ABOVE CEILING HEATER BY M.C., PROVIDE CIRCUIT, DISCONNECT AND CONNECTION. 5 WATER HEATER BY M.C., PROVIDE CIRCUIT, DISCONNECT AND CONNECTION. 6 FURNACE BY M.C., PROVIDE CIRCUIT, DISCONNECT (IF REQUIRED) AND CONNECTION. 7 BOOSTER PUMP BY M.C., PROVIDE CIRCUIT, DISCONNECT (IF REQUIRED) AND CONNECTION. 8 rtu by m.c., provide circuit, disconnect and connection. 9 a/c by m.c., provide circuit, disconnect and connection. 1o split unit by m.c., provide circuit, disconnect FOR EXTERIOR UNIT and connections. 11 CEILING HEATER BY M.C., PROVIDE CIRCUIT, DISCONNECT AND CONNECTION. 12 PROVIDE (2) CAT6 CABLE FROM NEAREST IT ROOM TO ELEVATOR CONTROL BOX. VERIFY LOCATION WITH ELEVATOR CONTRACTOR. 13 MAIN GARAGE ENTRY TYPE G LIGHT FIXTURES (4) ON DURING DAYLIGHT HOURS ONLY. PROVIDE CONTROLLER FOR OPERATION. 14 OVERHEAD DOOR BY OTHERS. PROVIDE CIRCUIT AND CONNECTION. VERIFY NEEDS WITH OVERHEAD DOOR CONTRACTOR. 15 CAR CHARGING STATION BY E.C., PROVIDE CIRCUIT, (1) CAT6 FROM NEAREST IT ROOM AND CONNECTION. 16 FUTURE CAR CHARGING STATION. PROVIDE CIRCUIT AND (1) CAT6 FROM NEAREST IT ROOM, IN JUNCTION BOXES. 17 provide gfci protected circuit for drinking fountains. verify requirements with installer. 18 SIGN BY OTHERS. PROVIDE CIRCUIT AND DISCONNECT (IF REQUIRED). verify requirements with installer. 19 PROVISION FOR IRRIGATION. VERIFY FINAL LOCATIONS WITH IRRIGATION CONTRACTOR. 2O provide power and (1) CAT6 for VEHICLE VACUUM STATION. VERIFY FINAL LOCATION AND NEEDS WITH G.C. 21 provide power and data for door intercom. (1) CAT6, (1) 18-2 AND (1) 16-2, 14-2 OR 12-2 DEPENDING ON DISTANCE. (1OO', 18O'AND 3OO' RESPECTIVELY). VERIFY REQUIREMENTS WITH INSTALLER. 22 PROVIDE and install heating green home yoga heating package for 1oosf in HOT YOGA ROOM. VERIFY final location WITH G.C. 23 for mdf room provide (2) dedicated quad receptacle, (2) 4x8 sheet of fire rated plywood, (1) terminal strip with #6 copper conductor from electrical system for intersystem bonding and (2) 4" conduit with pull string to exterior service location. 24 for idf room provide (2) dedicated quad receptacle, (1) 4x8 sheet of fire rated plywood, (1) terminal strip with #6 copper conductor from electrical system for intersystem bonding. interconnect mdf ROOM to each idf room with 6-strand multi-mode fiber. KEY COMMON AREA NOTES DH DH DH DH BB B B BB B B B B B B B B OC s Ss S s S s S s s S s S s S s S OS OS OS OS OS OS OCHS HS HS HS HS HS HS HS s S F1 F1 3/1OO CR CR CR G s S 12 1/2O1 OC OCA A A A A A A A A A A A A A A A A A A A A A A A A A A A A OS OS OS OSs S s S A 1A s S A A A A s S B B B HS F1 F1 F1 F1 ARCHITECT CLIENT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS2OO1O april 23, 2o21THE SIGNATURECARMELCARMEL, INpermit SET ENGINEERSCALE: O1 SELECTRICAL PLAN - AREA B FOURTH FLOOR 1/8" = 1'-O" NORTH FOURTH floorelectrical planarea bE1O4-b B C E AAREA BAREA BAREA CAREA CAREA BAREA B AREA AAREA A D 04/15/22