HomeMy WebLinkAboutA343 - INTERIOR WALL SECTIONSINTERIOR WALLSECTIONSA343 ARCHITECTCLIENT PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
# DESCRIPTION DATENORTH ENDMULTIFAMILYCARMEL, INDIANABID DOCUMENTS GC/CM
SCALE:
02 WALL SECTION
RADON VENT
3/8" = 1'-0"F1 F2a R3F1 R3FIRST FLOOR
EL: ± 0'-0"
SECOND FLOOR
EL: 10'-8"
ROOF PLATE
EL: 30'-5 1/8"
3" PVC DWV PIPE LOCATED
IN 2X6 STUD WALL, SEE
PLANS FOR LOCATION
JUNCTION BOX FOR FUTURE
ACTIVE VENT FAN BY
ELECTRICAL CONTRACTOR -
SEE ELECTRICAL PLANS12"MIN.F2a SCALE:
03 WALL SECTION
RADON VENT
3/8" = 1'-0" F1 F3 R3F1 R3FIRST FLOOR
EL: ± 0'-0"
SECOND FLOOR
EL: 10'-8"
THIRD FLOOR
EL: 21'-4"
ROOF PLATE
EL: 30'-5 1/8"
3" PVC DWV PIPE LOCATED
IN 2X6 STUD WALL, SEE
PLANS FOR LOCATION
JUNCTION BOX FOR FUTURE
ACTIVE VENT FAN BY
ELECTRICAL CONTRACTOR -
SEE ELECTRICAL PLANS12"MIN.F3 FOURTH FLOOR
EL: 32'-0"
LOWER LEVEL
EL: -10'-8"
THIRD FLOOR
EL: 21'-4"F3F3FOURTH FLOOR
EL: 32'-0"
THIRD FLOOR
EL: 21'-4"
SCALE:
01 WALL SECTION
RADON VENT
3/8" = 1'-0" F1 F2a F2 R3F1 R3FIRST FLOOR
EL: ± 0'-0"
SECOND FLOOR
EL: 14'-0"
ROOF PLATE
EL: 33'-9"
3" PVC DWV PIPE LOCATED
IN 2X6 STUD WALL, SEE
PLANS FOR LOCATION
1. MAINTAIN 10' FROM BUILDING OPENINGS.
2. PIPES SHALL BE INSTALLED SO
RAINWATER OR CONDENSATION DRAINS
DOWNWARD INTO THE GROUND BENEATH
THE SLAB AND VAPOR BARRIER.
3. RADON VENT PIPES TO BE INSTALLED IN
ACCORDANCE W/ASTM E1465 - 08A FOR
SOIL GAS COLLECTOR TYPE 5 SYSTEM.
4. COORDINATE FINAL LOCATION OR RADON
VENTING WITH ARCHITECTURAL PLAN
JUNCTION BOX FOR FUTURE
ACTIVE VENT FAN BY
ELECTRICAL CONTRACTOR -
SEE ELECTRICAL PLANS12"MIN.F2a F2 F3F3LOWER LEVEL
EL: -10'-8"
THIRD FLOOR
EL: 24'-8"F3 F3 F3 F3 F3 F3 F3F31 BID DOCUMENTS 01-15-21
1
04/15/22