HomeMy WebLinkAboutE501 - ELECTRICAL DETAILSEXIT NOTES: 1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. 2. CONCEAL RECEPTACLE BEHIND WATER COOLER. VERIFY EXACT MOUNTING HEIGHTS. 3. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COARSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED. 4. ALL RECEPTACLES ABOVE COUNTERTOPS SHALL BE INSTALLED AT +44" AFF TO CENTER OF THE BOX. CEILING F H S F STV96"96"48"48"72"48"18"18"18"18"72"84"SYMBOLS: FLOOR J D M WHEN WALL MOUNTED ABOVE DOOR (ALSO APPLIES TO CONCRETE ENCASED CONDUITS) (2) 1/2" DIA. X 3-1/2" EXPANSION ANCHOR (COORD. ANCHOR LOCATION WITH REINFORCING) TYPICAL COLUMN/WALL TYPICAL FLANGED-UP TYPE CHANNEL TYPICAL RISER TYPICAL B-LINE SYSTEMS FIGURE B3149 PIPE CLAMP NOTES: 1. 2. IF ADDITIONAL DISTANCE FROM COLUMN OR WALL IS REQUIRED OR IF RISER IS CHANNEL OR CLAMP ARE NOT TO EXTEND PAST EDGE OF COLUMN OR WALL. 3. ALL MATERIALS AND HARDWARE SHALL BE HOT DIPPED GALVANIZED OR MOUNTED AT EDGE OF COLUMN, USE B-LINE SYSTEMS FIGURE B3149 CLAMP. BEND AND DRILL HOLES IN LEGS AS REQUIRED. IF OUTSIDE DIMENSION OF CLAMP IS GREATER THAN THICKNESS OF WALL OR COLUMN, USE A B-LINE SYSTEMS FIGURE B3149 HANGER, BEND LEGS INWARD AND DRILL HOLES AS REQUIRED. STAINLESS STEEL. 4. SPECIFY TYPE OF PIPE FOR SIZING PIPE CLAMPS. FINISHE D FLOOR THREADED PLUG THREADED COUPLING CONDUIT = STUB UP SYMBOL ROOFING (BY OTHERS) BUILT-UP ROOF DECK. (BY OTHERS) STEPPED PVC BOOT CONDUIT STAINLESS STEEL CLAMPS SPUN ALUMINUM FLASHING BASE CONDUIT FIRE/SMOKE RATED OR UNRATED PARTITION OF VARIOUS CONSTRUCTIONS-REFER TO ARCHITECTURAL PLANS OR FIELD VERIFY TYPE CEILING STRUCTURE SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH INSULATED THROAT CONDUIT TERMINATORS EACH END-PROVIDE A THREADED CAP ON EACH END IF NOT USED FOR WIRING. LINE-UP WITH "BRIDLE RINGS" WHERE APPLICABLE. AFTER CABLE INSTALLATION, PROVIDE FIRESTOPPING IN SLEEVE. ACCESSIBLE CEILING EACH SIDE OF SLEEVE CU GRD. BAR RACKS #6 AWG INSULATED GROUND CONDUCTOR MDF & IDF'S MAIN EQUIPMENT BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) N G COMMUNICATIONS SYSTEMS EQUIPMENT CABINET GROUND COMMUNICATIONS PLYWOOD BACKBOARD GROUND BAR TELEPHONE SERVICE DEMARK GROUND BAR 3/4"X10' CU GROUND ROD AS REQUIRED (SEE SECTION 260526) EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS G NEUTRAL BUS GROUND BUS #3/0 CU EQUIPMENT BONDING JUMPER BONDING BUSHING (TYPICAL) SERVICE EQUIPMENT ENCLOSURE (MAIN SWITCHBOARD) MAIN BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) PANELBOARD BUILDING FOUNDATION REBAR INCOMING METAL WATER SERVICE BUILDING STEEL INCOMING SERVICE METAL CONDUITS #4/0 BARE CU GROUNDING ELECTRODE CONDUCTOR TRANSFORMER C N B A NTL AS SHOWN ON DRAWINGS NO GROUND CABLE UTILITY TRANSFORMER CU CLAD GROUND ROD RATING 'F' DIMENSION 'G' DIMENSION 'H' DIMENSION WEIGHT 300 KVA 69" 84" 63" 4450 LBS 500 KVA 69" 101" 65" 5700 LBS 750 KVA 69" 101" 69" 8200 LBS 1000 KVA 69" 101" 71" 10,100 LBS 1500 KVA 69" 101" 98" 13,950 LBS 2000 KVA 69" 84" 99" 15,000 LBS 2500 KVA 69" 84" 111" 18,850 LBS 3000 KVA 69" 96" 111" 19,000 LBS AA 1. THE TOP OF FOUNDATION SHALL BE SMOOTH AND LEVEL. 2. MAXIMUM SPACE AVAILABLE FOR LOW VOLTAGE CONDUITS. 3. HIGH VOLTAGE CONDUIT AREA. 4. CONDUIT SHALL BE NOT LESS THAN 36". 5. WHERE POSSIBLE DO NOT INSTALL CONDUITS UNDERNEATH THIS AREA. 6. BACKFILL UNDER FOUNDATION SHALL NOT BE EARTH. CONDUITS SHALL BE INSTALLED PRIOR TO FOUNDATION. ALL CONDUITS SHALL BE EXTENDED NOT LESS THAN 3'-0" FROM EDGE OF PAD. 7. GROUND SLOPE AWAY FROM PAD SHALL BE 36:1. 8. REINFORCING BAR SHALL BE #4 DEFORMED BAR. 9. DIMENSIONS SHOWN BASED ON AVAILABLE COOPER POWER SYSTEMS DATA. 10. CONTRACTOR SHALL FIELD VERIFY EXACT EQUIPMENT DIMENSIONS AND CONDUIT STUBUP LOCATIONS PRIOR TO INSTALLATION. NOTES: PLAN SECTION A-A H7 1/2"G F SEE NOTE 5 SEE NOTE 3 SEE NOTE 2 FRONT OF PAD GROUND ROD FINISHED GRADE NO. 63 STONE, 3/4" TO DUSTWET SAND BED TAMPED WITH MECHANICAL TAMPER HOT NEUTRAL LOCAL THREE-WAY SWITCHES BLK LOADWHT BLU BLK RED CONTROL COMMON +24VDC OCCUPANCY SENSOR 24VDC RED RED LOADLOCAL SWITCH EMERGENCY CIRCUIT (HOT + NEUTRAL) WHERE INDICATED PROVIDE ADDITIONAL SENSOR POWER/ SWITCHING PACKS AS REQUIRED FOR ADDITIONAL ROOM LIGHT SWITCHING. PROVIDE OTHER RELAY PACKS AS INDICATED. SENSOR POWER/ SWITCHING PACK (UNSWITCHED) SIDE BY SIDE JUNCTION BOXES STACKED JUNCTION BOXES JUNCTION BOXES HIGH VOLTAGE WIRING LOW VOLTAGE WIRING POWER PACK POWER PACK HIGH VOLTAGE WIRING JUNCTION BOX JUNCTION BOX EXTENSION BOX LOW VOLTAGE WIRING GENERAL NOTES: A. DO NOT INSTALL POWER PACKS CLOSER THAN 6-12 INCHES FROM SENSOR. DO NOT INSTALL POWER PACKS WITHOUT JUNCTION BOXES. 4" OCTAGONAL JUNCTION BOX (AT LEAST 1.5" DEEP). DO NOT INSTALL SENSOR WITHOUT JUNCTION BOX. CEILING DEPLUGGABLE TERMINAL SENSOR (2) MOUNTING SCREWS FRONT COVER 24" DIA 6"60" #6 AWG GROUND WIRE FINISH GRADE BASE COVER HANDHOLEPOLE MOUNTING BOLT LAYOUT PER MFGR. TEMPLATE GROUT BASE GROUND ROD (8) #4 VERT. BARS W/ #4 TIES @ 16" O.C. CONDUIT CONC. BASE WITH 1" CHAMFER: PROVIDE VERY HIGH QUALITY SMOOTH FINISH 36"ANCHOR BOLTS 24" DIA 30"60" #6 AWG GROUND WIRE FINISH GRADE BASE COVER HANDHOLEPOLE MOUNTING BOLT LAYOUT PER MFGR. TEMPLATE GROUT BASE GROUND ROD (8) #4 VERT. BARS W/ #4 TIES @ 16" O.C. CONDUIT CONC. BASE WITH 1" CHAMFER: PROVIDE VERY HIGH QUALITY SMOOTH FINISH 36"ANCHOR BOLTS ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031 JANUARY 15, 2021 BID SET E501ELECTRICAL DETAILS NORTH ENDAPARTMENTSCARMEL, INNOT TO SCALE ELECTRICAL ELEVATION1 NOT TO SCALE CONDUIT SUPPORT DETAIL2 NOT TO SCALE CONDUIT STUB-UP DETAIL3 NOT TO SCALE CONDUIT ROOF PENETRATION DETAIL4 NOT TO SCALE CABLING SLEEVE INSTALLATION DETAIL5 NOT TO SCALE TYPICAL GROUNDING DETAIL7 NOT TO SCALE TYPICAL TRANSFORMER PAD DETAIL6 NOT TO SCALE TYPICAL OCCUPANCY SENSOR WIRING DETAIL8 NOT TO SCALE TYPICAL OCCUPANCY SENSOR POWER PACK MOUNTING9 NOT TO SCALE TYPICAL OCCUPANCY SENSOR MOUNTING DETAIL 10 NOT TO SCALE POLE BASE DETAIL -6in AFG 11 NOT TO SCALE POLE BASE DETAIL -30in AFG 12 # DESCRIPTION DATE 07/08/21