NOTES:
1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS
INDICATED UNLESS OTHERWISE NOTED ON
THE DRAWINGS OR IN THE SPECIFICATIONS.
2. CONCEAL RECEPTACLE BEHIND WATER COOLER.
VERIFY EXACT MOUNTING HEIGHTS.
3. WHERE DEVICES ARE LOCATED IN MASONRY
WALLS LOCATE DEVICE WITHIN COARSING SO
THAT MOUNTING INDICATED HERE IN IS NOT
EXCEEDED.
4. ALL RECEPTACLES ABOVE COUNTERTOPS SHALL
BE INSTALLED AT +44" AFF TO CENTER OF THE BOX.
CEILING
F
H
S
F STV96"96"48"48"72"48"18"18"18"18"72"84"SYMBOLS:
FLOOR
J
D
M
WHEN WALL MOUNTED ABOVE DOOR
(ALSO APPLIES TO CONCRETE ENCASED CONDUITS)
(2) 1/2" DIA. X 3-1/2"
EXPANSION ANCHOR
(COORD. ANCHOR LOCATION
WITH REINFORCING) TYPICAL
COLUMN/WALL
TYPICAL
FLANGED-UP TYPE
CHANNEL TYPICAL
RISER
TYPICAL B-LINE SYSTEMS
FIGURE B3149 PIPE
CLAMP
NOTES:
1.
2.
IF ADDITIONAL DISTANCE FROM COLUMN OR WALL IS REQUIRED OR IF RISER IS
CHANNEL OR CLAMP ARE NOT TO EXTEND PAST EDGE OF COLUMN OR WALL.
3. ALL MATERIALS AND HARDWARE SHALL BE HOT DIPPED GALVANIZED OR
MOUNTED AT EDGE OF COLUMN, USE B-LINE SYSTEMS FIGURE B3149 CLAMP. BEND
AND DRILL HOLES IN LEGS AS REQUIRED.
IF OUTSIDE DIMENSION OF CLAMP IS GREATER THAN THICKNESS OF WALL OR COLUMN,
USE A B-LINE SYSTEMS FIGURE B3149 HANGER, BEND LEGS INWARD AND DRILL HOLES
AS REQUIRED.
STAINLESS STEEL.
4. SPECIFY TYPE OF PIPE FOR SIZING PIPE CLAMPS.
FINISHE
D
FLOOR
THREADED
PLUG
THREADED
COUPLING
CONDUIT
= STUB UP SYMBOL
ROOFING
(BY OTHERS)
BUILT-UP ROOF DECK.
(BY OTHERS)
STEPPED PVC BOOT
CONDUIT
STAINLESS STEEL CLAMPS
SPUN ALUMINUM
FLASHING BASE
CONDUIT
FIRE/SMOKE RATED OR UNRATED PARTITION
OF VARIOUS CONSTRUCTIONS-REFER TO
ARCHITECTURAL PLANS OR FIELD VERIFY TYPE
CEILING STRUCTURE
SIZE CONDUIT SLEEVE (SIZE AS INDICATED)
WITH INSULATED THROAT CONDUIT TERMINATORS
EACH END-PROVIDE A THREADED CAP ON
EACH END IF NOT USED FOR WIRING. LINE-UP
WITH "BRIDLE RINGS" WHERE APPLICABLE.
AFTER CABLE INSTALLATION, PROVIDE
FIRESTOPPING IN SLEEVE.
ACCESSIBLE CEILING EACH SIDE OF SLEEVE
CU GRD. BAR
RACKS
#6 AWG INSULATED
GROUND CONDUCTOR
MDF & IDF'S
MAIN EQUIPMENT BONDING
JUMPER (SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
N
G
COMMUNICATIONS SYSTEMS
EQUIPMENT CABINET GROUND
COMMUNICATIONS PLYWOOD
BACKBOARD GROUND BAR
TELEPHONE SERVICE
DEMARK GROUND BAR
3/4"X10' CU GROUND
ROD AS REQUIRED
(SEE SECTION 260526)
EQUIPMENT
GROUND -
SIZE AS
SHOWN ON
DRAWINGS
G
NEUTRAL BUS
GROUND BUS
#3/0 CU EQUIPMENT
BONDING JUMPER
BONDING BUSHING (TYPICAL)
SERVICE EQUIPMENT ENCLOSURE
(MAIN SWITCHBOARD)
MAIN BONDING JUMPER
(SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
PANELBOARD
BUILDING
FOUNDATION
REBAR
INCOMING
METAL
WATER
SERVICE
BUILDING
STEEL
INCOMING SERVICE
METAL CONDUITS
#4/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
TRANSFORMER
C
N
B A
NTL AS SHOWN
ON DRAWINGS
NO GROUND CABLE
UTILITY
TRANSFORMER
CU CLAD GROUND ROD
RATING 'F' DIMENSION 'G' DIMENSION 'H' DIMENSION WEIGHT
300 KVA 69" 84" 63" 4450 LBS
500 KVA 69" 101" 65" 5700 LBS
750 KVA 69" 101" 69" 8200 LBS
1000 KVA 69" 101" 71" 10,100 LBS
1500 KVA 69" 101" 98" 13,950 LBS
2000 KVA 69" 84" 99" 15,000 LBS
2500 KVA 69" 84" 111" 18,850 LBS
3000 KVA 69" 96" 111" 19,000 LBS
AA
1. THE TOP OF FOUNDATION SHALL BE SMOOTH AND LEVEL.
2. MAXIMUM SPACE AVAILABLE FOR LOW VOLTAGE CONDUITS.
3. HIGH VOLTAGE CONDUIT AREA.
4. CONDUIT SHALL BE NOT LESS THAN 36".
5. WHERE POSSIBLE DO NOT INSTALL CONDUITS UNDERNEATH THIS AREA.
6. BACKFILL UNDER FOUNDATION SHALL NOT BE EARTH. CONDUITS SHALL BE INSTALLED PRIOR TO
FOUNDATION. ALL CONDUITS SHALL BE EXTENDED NOT LESS THAN 3'-0" FROM EDGE OF PAD.
7. GROUND SLOPE AWAY FROM PAD SHALL BE 36:1.
8. REINFORCING BAR SHALL BE #4 DEFORMED BAR.
9. DIMENSIONS SHOWN BASED ON AVAILABLE COOPER POWER SYSTEMS DATA.
10. CONTRACTOR SHALL FIELD VERIFY EXACT EQUIPMENT DIMENSIONS AND CONDUIT STUBUP
LOCATIONS PRIOR TO INSTALLATION.
NOTES:
PLAN
SECTION A-A
H7 1/2"G
F
SEE NOTE 5
SEE NOTE 3
SEE NOTE 2
FRONT OF PAD
GROUND ROD
FINISHED GRADE
NO. 63
STONE,
3/4" TO DUSTWET SAND BED TAMPED
WITH MECHANICAL
TAMPER
HOT
NEUTRAL
LOCAL
THREE-WAY
SWITCHES
BLK LOADWHT BLU
BLK
RED
CONTROL
COMMON
+24VDC
OCCUPANCY
SENSOR
24VDC
RED
RED LOADLOCAL SWITCH
EMERGENCY CIRCUIT (HOT + NEUTRAL) WHERE INDICATED
PROVIDE ADDITIONAL SENSOR POWER/
SWITCHING PACKS AS REQUIRED FOR
ADDITIONAL ROOM LIGHT SWITCHING.
PROVIDE OTHER RELAY PACKS AS
INDICATED.
SENSOR
POWER/
SWITCHING
PACK
(UNSWITCHED)
SIDE BY SIDE JUNCTION BOXES
STACKED JUNCTION BOXES
JUNCTION
BOXES
HIGH VOLTAGE
WIRING
LOW VOLTAGE
WIRING
POWER
PACK
POWER
PACK
HIGH VOLTAGE WIRING
JUNCTION BOX
JUNCTION BOX
EXTENSION BOX
LOW VOLTAGE WIRING
GENERAL NOTES:
A. DO NOT INSTALL POWER PACKS
CLOSER THAN 6-12 INCHES FROM
SENSOR. DO NOT INSTALL
POWER PACKS WITHOUT
JUNCTION BOXES.
4" OCTAGONAL JUNCTION BOX
(AT LEAST 1.5" DEEP). DO
NOT INSTALL SENSOR WITHOUT
JUNCTION BOX.
CEILING
DEPLUGGABLE
TERMINAL
SENSOR
(2) MOUNTING SCREWS
FRONT COVER
24" DIA 6"60" #6 AWG GROUND WIRE
FINISH GRADE
BASE
COVER
HANDHOLEPOLE
MOUNTING BOLT LAYOUT
PER MFGR. TEMPLATE
GROUT BASE
GROUND ROD
(8) #4 VERT. BARS W/
#4 TIES @ 16" O.C.
CONDUIT
CONC. BASE WITH 1" CHAMFER:
PROVIDE VERY HIGH QUALITY
SMOOTH FINISH
36"ANCHOR
BOLTS
24" DIA 30"60" #6 AWG GROUND WIRE
FINISH GRADE
BASE
COVER
HANDHOLEPOLE
MOUNTING BOLT LAYOUT
PER MFGR. TEMPLATE
GROUT BASE
GROUND ROD
(8) #4 VERT. BARS W/
#4 TIES @ 16" O.C.
CONDUIT
CONC. BASE WITH 1" CHAMFER:
PROVIDE VERY HIGH QUALITY
SMOOTH FINISH
36"ANCHOR
BOLTS ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
E501ELECTRICAL DETAILS NORTH ENDAPARTMENTSCARMEL, INNOT TO SCALE
ELECTRICAL ELEVATION1
NOT TO SCALE
CONDUIT SUPPORT DETAIL2
NOT TO SCALE
CONDUIT STUB-UP DETAIL3
NOT TO SCALE
CONDUIT ROOF PENETRATION DETAIL4
NOT TO SCALE
CABLING SLEEVE INSTALLATION DETAIL5
NOT TO SCALE
TYPICAL GROUNDING DETAIL7
NOT TO SCALE
TYPICAL TRANSFORMER PAD DETAIL6
NOT TO SCALE
TYPICAL OCCUPANCY SENSOR WIRING DETAIL8
NOT TO SCALE
TYPICAL OCCUPANCY SENSOR POWER PACK MOUNTING9
NOT TO SCALE
TYPICAL OCCUPANCY SENSOR MOUNTING DETAIL 10
NOT TO SCALE
POLE BASE DETAIL -6in AFG 11
NOT TO SCALE
POLE BASE DETAIL -30in AFG 12
# DESCRIPTION DATE
07/08/21