HomeMy WebLinkAboutE602 - ELECTRICAL SCHEDULESARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031 JANUARY 15, 2021 BID SET E602ELECTRICALSCHEDULESNORTH ENDAPARTMENTSCARMEL, IN# DESCRIPTION DATE 1 BID DOCUMENT 01/15/2021 Notes: HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA Dwelling Unit Load 16820 VA 75.67% 12728 VA DWELLING UNIT 4500 VA 100.00% 4500 VA Total Est. Demand: 137 A FRACTIONAL HP MOTOR 528 VA 100.00% 528 VA Total Conn.: 157 A Miscellaneous Power 0 VA 0.00% 0 VA Total Est. Demand: 28541 VA LIGHTING 308 VA 125.00% 385 VA Total Conn. Load: 32556 VA HVAC 7488 VA 100.00% 7488 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 164 A 147 A Total Load: 17296 VA 15260 VA 23 24 21 1456 1500 1 20 A MICROWAVE 22 19 CU-2 20 A 2 1456 180 1 20 A DATA 20 17 3744 265 1 20 A LIGHTING 18 15 FCU-2 50 A 2 3744 2250 16 13 BATHROOM LIGHTING 20 A 1 751 2250 2 30 A WH-1 14 11 RECEPT-LIVING ROOM 20 A 1 900 900 1 20 A RECEPT-ROOM 12 9 DISPOSAL 20 A 1 180 900 1 20 A RECEPT-BEDROOM 10 7 DISHWASHER 20 A 1 1000 1080 1 20 A RECEPT-KITCHEN 8 5 1750 1000 1 20 A REFRIGERATOR 6 3 RANGE 50 A 2 1750 2000 4 1 WASHER 20 A 1 1500 2000 2 30 A DRYER 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Enclosure: NEMA 1 MCB Rating: 200 A Mounting: RECESSED Wires: 3 Mains Rating: 200 A Supply From: Phases: 1 Mains Type: MCB Location: Volts: 120/208 Single A.I.C. Rating: 18KA Branch Panel:PNL-A5 Notes: HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA Dwelling Unit Load 18300 VA 72.79% 13320 VA DWELLING UNIT 4500 VA 100.00% 4500 VA FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 145 A Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 168 A RECEPT 360 VA 100.00% 360 VA Total Est. Demand: 30164 VA LIGHTING 423 VA 125.00% 528 VA Total Conn. Load: 35039 VA HVAC 7488 VA 100.00% 7488 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 166 A 170 A Total Load: 17236 VA 17803 VA 23 1456 24 21 2250 1456 2 20 A CU-2 22 19 WH-1 20 A 2 2250 3744 20 17 DATA 20 A 1 180 3744 2 50 A FCU-2 18 15 DISHWASHER 20 A 1 1500 800 1 20 A DISPOSAL 16 13 RECEPT-KITCHEN 20 A 1 1260 1000 1 20 A REFRIGERATOR 14 11 RECEPT- LIVING ROOM/HALLWAY 20 A 1 1080 900 1 20 A RECEPT-BEDROOM 12 9 1750 1080 1 20 A RECEPT-BEDROOM 10 7 RANGE 50 A 2 1750 1500 1 20 A microwave 8 5 WASHER 20 A 1 1500 2000 6 3 BATHROOM LIGHTING 20 A 1 823 2000 2 30 A DRYER 4 1 LIGHTING 20 A 1 246 770 1 20 A BATHROOM LIGHTING 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Enclosure: MCB Rating: 1 A Mounting: Wires: 3 Mains Rating: Supply From: Phases: 1 Mains Type: MCB Location: Volts: 120/208 Single A.I.C. Rating: Branch Panel:PNL-B1 Notes: HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA Dwelling Unit Load 18300 VA 72.79% 13320 VA DWELLING UNIT 4500 VA 100.00% 4500 VA FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 144 A Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 167 A RECEPT 180 VA 100.00% 180 VA Total Est. Demand: 29919 VA LIGHTING 370 VA 125.00% 463 VA Total Conn. Load: 34806 VA HVAC 7488 VA 100.00% 7488 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 173 A 160 A Total Load: 18201 VA 16606 VA 23 WASHER 20 A 1 1500 24 21 MICROWAVE 20 A 1 1500 900 1 20 A RECEPT-KITCHEN 22 19 BATHROOM LIGHTING 20 A 1 770 3744 20 17 RECEPT-BEDROOM 20 A 1 900 3744 2 50 A FCU-2 18 15 2250 1750 16 13 WH-1 30 A 2 2250 1750 2 50 A RANGE 14 11 1456 2000 12 9 CU-2 25 A 2 1456 2000 2 30 A DRYER 10 7 RECEPT-BEDROOM 20 A 1 1080 1000 1 20 A REFRIGERATOR 8 5 DISHWASHER 20 A 1 1500 761 1 20 A BATHROOM LIGHTING 6 3 LIGHTING 20 A 1 256 800 1 20 A DISPOSAL 4 1 DATA 20 A 1 180 1260 1 20 A RECEPT- LIVING ROOM/HALLWAY 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Enclosure: MCB Rating: 1 A Mounting: Wires: 3 Mains Rating: Supply From: Phases: 1 Mains Type: MCB Location: Volts: 120/208 Single A.I.C. Rating: Branch Panel:PNL-B2 Notes: HVAC-NON COINCIDENTAL 0 VA 0.00% 0 VA Dwelling Unit Load 18840 VA 71.85% 13536 VA DWELLING UNIT 4500 VA 100.00% 4500 VA FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 133 A Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 158 A RECEPT 540 VA 100.00% 540 VA Total Est. Demand: 27660 VA LIGHTING 432 VA 125.00% 540 VA Total Conn. Load: 32856 VA HVAC 7488 VA 100.00% 7488 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 166 A 147 A Total Load: 17587 VA 15270 VA 23 RECEPT-BEDROOM 20 A 1 1080 24 21 MICROWAVE 20 A 1 1500 1500 1 20 A WASHER 22 19 3744 1750 20 17 FCU-2 50 A 2 3744 1750 2 50 A RANGE 18 15 2000 2250 16 13 DRYER 30 A 2 2000 2250 2 30 A WH-1 14 11 RECEPT-KITCHEN 20 A 1 1440 0 12 9 RECEPT-BEDROOM 20 A 1 1080 0 2 20 A CU-2 10 7 DISPOSAL 20 A 1 800 1000 1 20 A REFRIGERATOR 8 5 RECEPT-LIVING ROOM 20 A 1 1260 1500 1 20 A DISHWASHER 6 3 LIGHTING 20 A 1 265 941 1 20 A BATHROOM LIGHTING 4 1 DATA 20 A 1 180 823 1 20 A BATHROOM LIGHTING 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Enclosure: MCB Rating: 1 A Mounting: Wires: 3 Mains Rating: Supply From: Phases: 1 Mains Type: MCB Location: Volts: 120/208 Single A.I.C. Rating: Branch Panel:PNL-B3 Notes: HVAC-NON COINCIDENTAL 0 VA 0.00% 0 VA Dwelling Unit Load 18840 VA 71.85% 13536 VA DWELLING UNIT 4500 VA 100.00% 4500 VA FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 133 A Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 158 A RECEPT 540 VA 100.00% 540 VA Total Est. Demand: 27660 VA LIGHTING 432 VA 125.00% 540 VA Total Conn. Load: 32856 VA HVAC 7488 VA 100.00% 7488 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 158 A 158 A Total Load: 16452 VA 16405 VA 23 0 24 21 CU-2 20 A 2 0 180 1 20 A DATA 22 19 RECEPT-BEDROOM 20 A 1 1080 1080 1 20 A RECEPT-BEDROOM 20 17 WASHER 20 A 1 1500 2000 18 15 3744 2000 2 30 A DRYER 16 13 FCU-2 50 A 2 3744 2250 14 11 DISPOSAL 20 A 1 800 2250 2 30 A WH-1 12 9 1750 1500 1 20 A DISHWASHER 10 7 RANGE 50 A 2 1750 1500 1 20 A MICROWAVE 8 5 RECEPT- LIVING ROOM/HALLWAY 20 A 1 1440 1000 1 20 A REFRIGERATOR 6 3 BATHROOM LIGHTING 20 A 1 941 1260 1 20 A RECEPT-KITCHEN 4 1 BATHROOM LIGHTING 20 A 1 823 265 1 20 A LIGHTING 2 CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT Enclosure: MCB Rating: 1 A Mounting: Wires: 3 Mains Rating: Supply From: Phases: 1 Mains Type: MCB Location: Volts: 120/208 Single A.I.C. Rating: Branch Panel:PNL-B3b Notes: Total Est. Demand: 50 A Total Conn.: 47 A Miscellaneous Power 3424 VA 100.00% 3424 VA Total Est. Demand: 18136 VA RECEPT 8220 VA 100.00% 8220 VA Total Conn. Load: 16832 VA LIGHTING 5268 VA 125.00% 6585 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 41 A 37 A 63 A Total Load: 4890 VA 4475 VA 7487 VA 41 42 39 40 37 38 35 36 33 LIGHTING - STAIRWELL 20 A 1 262 88 1 20 A LIGHTING - ELEVATOR 34 31 262 1 20 A LIGHTING - STAIRWELL 32 29 90 1560 1 20 A UH-1 - LOBBY 100 30 27 UH-2 - RISER ROOM 20 A 2 90 28 25 GEF-1 20 A 1 720 901 26 23 RECEPT OFFICE-1 XXX-1 20 A 1 720 901 24 21 901 3 20 A GEF-2 22 19 20 17 GARAGE LIGHTING 20 A 1 1197 18 15 1323 1 20 A GARAGE LIGHTING 16 13 LIGHTING - EXTERIOR 20 A 1 909 647 1 20 A LIGHTING - STAIRWELL 14 11 CO PANEL 20 A 1 180 1500 1 20 A UH-1 BIKE ROOM 12 9 RECEPT - ELEV. SUMP 20 A 1 180 0 1 20 A ELEV CAB PWR & LTG 10 7 RECEPT - FIRST FLOOR AREA B 20 A 1 720 180 1 20 A RECEPT - ELEV. SUMP 8 5 RECEPT - GARAGE LEVEL 20 A 1 1260 180 1 20 A RECEPT - FIRST FLOOR AREA A 6 3 LIGHTING - RM C002 20 A 1 165 1560 1 20 A UH-1 - STAIRWELL 4 1 LIGHTING - RM 103, 104 20 A 1 275 275 1 20 A LIGHTING - RM 100 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Enclosure: NEMA 1 Mounting: SURFACE Wires: 4 Mains Rating: 225 A Supply From: Phases: 3 Mains Type: MLO Location: GARAGE 001 Volts: 120/208 Wye A.I.C. Rating: 18,000 Branch Panel:HA0 Notes: Total Est. Demand: 114 A Total Conn.: 117 A Miscellaneous Power 26317 VA 100.00% 26317 VA Total Est. Demand: 41044 VA RECEPT 13200 VA 87.88% 11600 VA Total Conn. Load: 42019 VA LIGHTING 2502 VA 125.00% 3127 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps: 126 A 131 A 100 A Total Load: 14732 VA 15283 VA 12004 VA 41 42 39 40 37 38 35 36 33 LIGHTING - RM M201, S201 20 A 1 220 220 1 20 A LIGHTING - RM E202, M202 34 31 0 591 1 20 A LIGHTING - CORRIDOR, S202 32 29 FCU-4 20 A 2 0 110 1 20 A LIGHTING - RM E201 30 27 RECEPT - SECOND FLOOR AREA B 20 A 1 900 1560 1 20 A UH-1 28 25 UH-1 - STAIRWELL 20 A 1 1560 2350 26 23 RECEPT ELEC. ROOM-4 E202-4 20 A 1 180 2350 2 30 A FCU-4 2ND FLOOR AREA A 24 21 UH-1 - STAIRWELL 20 A 1 1560 1080 1 20 A RECEPT - SECOND FLOOR AREA A 22 19 ACCESS CONTROL 20 A 1 540 0 20 17 RECEPT - SECOND FLOOR AREA A 20 A 1 1080 0 2 30 A FCU-4 2ND FLOOR AREA A 18 15 LIGHTING - RM 203 20 A 1 55 244 1 20 A LIGHTING - CORRIDOR 16 13 LIGHTING - ELEVATOR 20 A 1 88 401 1 20 A LIGHTING - RM C008 14 11 7205 358 1 20 A LIGHTING - RM C005, C009, RM C010 12 9 7205 190 1 20 A RECEPT - RM C006 10 7 FCU-6 90 A 3 7205 197 1 20 A LIGHTING - STAIRWELL 8 5 RECEPT AMENITIES-1 A101-1 20 A 1 540 180 1 20 A FACP 6 3 RECEPT - WORK ROOM 20 A 1 1500 550 1 20 A RECEPT - RM C007 4 1 RECEPT - OFFICE-2 XXX-2 20 A 1 900 900 1 20 A RECEPT - AMENITIES A101-1 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Enclosure: NEMA 1 MCB Rating: 225 A Mounting: RECESSED Wires: 4 Mains Rating: 225 A Supply From: Phases: 3 Mains Type: MCB Location: AMENITIES-1 A101-1 Volts: 120/208 Wye A.I.C. Rating: 18,000 Branch Panel:HA1 1 07/08/21