HomeMy WebLinkAboutE602 - ELECTRICAL SCHEDULESARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
E602ELECTRICALSCHEDULESNORTH ENDAPARTMENTSCARMEL, IN# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021
Notes:
HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA
Dwelling Unit Load 16820 VA 75.67% 12728 VA
DWELLING UNIT 4500 VA 100.00% 4500 VA Total Est. Demand: 137 A
FRACTIONAL HP MOTOR 528 VA 100.00% 528 VA Total Conn.: 157 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Est. Demand: 28541 VA
LIGHTING 308 VA 125.00% 385 VA Total Conn. Load: 32556 VA
HVAC 7488 VA 100.00% 7488 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 164 A 147 A
Total Load: 17296 VA 15260 VA
23 24
21 1456 1500 1 20 A MICROWAVE 22
19 CU-2 20 A 2 1456 180 1 20 A DATA 20
17 3744 265 1 20 A LIGHTING 18
15 FCU-2 50 A 2 3744 2250 16
13 BATHROOM LIGHTING 20 A 1 751 2250 2 30 A WH-1 14
11 RECEPT-LIVING ROOM 20 A 1 900 900 1 20 A RECEPT-ROOM 12
9 DISPOSAL 20 A 1 180 900 1 20 A RECEPT-BEDROOM 10
7 DISHWASHER 20 A 1 1000 1080 1 20 A RECEPT-KITCHEN 8
5 1750 1000 1 20 A REFRIGERATOR 6
3 RANGE 50 A 2 1750 2000 4
1 WASHER 20 A 1 1500 2000 2 30 A DRYER 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 200 A
Mounting: RECESSED Wires: 3 Mains Rating: 200 A
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/208 Single A.I.C. Rating: 18KA
Branch Panel:PNL-A5
Notes:
HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA
Dwelling Unit Load 18300 VA 72.79% 13320 VA
DWELLING UNIT 4500 VA 100.00% 4500 VA
FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 145 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 168 A
RECEPT 360 VA 100.00% 360 VA Total Est. Demand: 30164 VA
LIGHTING 423 VA 125.00% 528 VA Total Conn. Load: 35039 VA
HVAC 7488 VA 100.00% 7488 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 166 A 170 A
Total Load: 17236 VA 17803 VA
23 1456 24
21 2250 1456 2 20 A CU-2 22
19 WH-1 20 A 2 2250 3744 20
17 DATA 20 A 1 180 3744 2 50 A FCU-2 18
15 DISHWASHER 20 A 1 1500 800 1 20 A DISPOSAL 16
13 RECEPT-KITCHEN 20 A 1 1260 1000 1 20 A REFRIGERATOR 14
11 RECEPT- LIVING ROOM/HALLWAY 20 A 1 1080 900 1 20 A RECEPT-BEDROOM 12
9 1750 1080 1 20 A RECEPT-BEDROOM 10
7 RANGE 50 A 2 1750 1500 1 20 A microwave 8
5 WASHER 20 A 1 1500 2000 6
3 BATHROOM LIGHTING 20 A 1 823 2000 2 30 A DRYER 4
1 LIGHTING 20 A 1 246 770 1 20 A BATHROOM LIGHTING 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Enclosure: MCB Rating: 1 A
Mounting: Wires: 3 Mains Rating:
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/208 Single A.I.C. Rating:
Branch Panel:PNL-B1
Notes:
HVAC-NON COINCIDENTAL 2912 VA 100.00% 2912 VA
Dwelling Unit Load 18300 VA 72.79% 13320 VA
DWELLING UNIT 4500 VA 100.00% 4500 VA
FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 144 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 167 A
RECEPT 180 VA 100.00% 180 VA Total Est. Demand: 29919 VA
LIGHTING 370 VA 125.00% 463 VA Total Conn. Load: 34806 VA
HVAC 7488 VA 100.00% 7488 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 173 A 160 A
Total Load: 18201 VA 16606 VA
23 WASHER 20 A 1 1500 24
21 MICROWAVE 20 A 1 1500 900 1 20 A RECEPT-KITCHEN 22
19 BATHROOM LIGHTING 20 A 1 770 3744 20
17 RECEPT-BEDROOM 20 A 1 900 3744 2 50 A FCU-2 18
15 2250 1750 16
13 WH-1 30 A 2 2250 1750 2 50 A RANGE 14
11 1456 2000 12
9 CU-2 25 A 2 1456 2000 2 30 A DRYER 10
7 RECEPT-BEDROOM 20 A 1 1080 1000 1 20 A REFRIGERATOR 8
5 DISHWASHER 20 A 1 1500 761 1 20 A BATHROOM LIGHTING 6
3 LIGHTING 20 A 1 256 800 1 20 A DISPOSAL 4
1 DATA 20 A 1 180 1260 1 20 A RECEPT- LIVING ROOM/HALLWAY 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Enclosure: MCB Rating: 1 A
Mounting: Wires: 3 Mains Rating:
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/208 Single A.I.C. Rating:
Branch Panel:PNL-B2
Notes:
HVAC-NON COINCIDENTAL 0 VA 0.00% 0 VA
Dwelling Unit Load 18840 VA 71.85% 13536 VA
DWELLING UNIT 4500 VA 100.00% 4500 VA
FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 133 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 158 A
RECEPT 540 VA 100.00% 540 VA Total Est. Demand: 27660 VA
LIGHTING 432 VA 125.00% 540 VA Total Conn. Load: 32856 VA
HVAC 7488 VA 100.00% 7488 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 166 A 147 A
Total Load: 17587 VA 15270 VA
23 RECEPT-BEDROOM 20 A 1 1080 24
21 MICROWAVE 20 A 1 1500 1500 1 20 A WASHER 22
19 3744 1750 20
17 FCU-2 50 A 2 3744 1750 2 50 A RANGE 18
15 2000 2250 16
13 DRYER 30 A 2 2000 2250 2 30 A WH-1 14
11 RECEPT-KITCHEN 20 A 1 1440 0 12
9 RECEPT-BEDROOM 20 A 1 1080 0 2 20 A CU-2 10
7 DISPOSAL 20 A 1 800 1000 1 20 A REFRIGERATOR 8
5 RECEPT-LIVING ROOM 20 A 1 1260 1500 1 20 A DISHWASHER 6
3 LIGHTING 20 A 1 265 941 1 20 A BATHROOM LIGHTING 4
1 DATA 20 A 1 180 823 1 20 A BATHROOM LIGHTING 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Enclosure: MCB Rating: 1 A
Mounting: Wires: 3 Mains Rating:
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/208 Single A.I.C. Rating:
Branch Panel:PNL-B3
Notes:
HVAC-NON COINCIDENTAL 0 VA 0.00% 0 VA
Dwelling Unit Load 18840 VA 71.85% 13536 VA
DWELLING UNIT 4500 VA 100.00% 4500 VA
FRACTIONAL HP MOTOR 1056 VA 100.00% 1056 VA Total Est. Demand: 133 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Conn.: 158 A
RECEPT 540 VA 100.00% 540 VA Total Est. Demand: 27660 VA
LIGHTING 432 VA 125.00% 540 VA Total Conn. Load: 32856 VA
HVAC 7488 VA 100.00% 7488 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 158 A 158 A
Total Load: 16452 VA 16405 VA
23 0 24
21 CU-2 20 A 2 0 180 1 20 A DATA 22
19 RECEPT-BEDROOM 20 A 1 1080 1080 1 20 A RECEPT-BEDROOM 20
17 WASHER 20 A 1 1500 2000 18
15 3744 2000 2 30 A DRYER 16
13 FCU-2 50 A 2 3744 2250 14
11 DISPOSAL 20 A 1 800 2250 2 30 A WH-1 12
9 1750 1500 1 20 A DISHWASHER 10
7 RANGE 50 A 2 1750 1500 1 20 A MICROWAVE 8
5 RECEPT- LIVING ROOM/HALLWAY 20 A 1 1440 1000 1 20 A REFRIGERATOR 6
3 BATHROOM LIGHTING 20 A 1 941 1260 1 20 A RECEPT-KITCHEN 4
1 BATHROOM LIGHTING 20 A 1 823 265 1 20 A LIGHTING 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Enclosure: MCB Rating: 1 A
Mounting: Wires: 3 Mains Rating:
Supply From: Phases: 1 Mains Type: MCB
Location: Volts: 120/208 Single A.I.C. Rating:
Branch Panel:PNL-B3b
Notes:
Total Est. Demand: 50 A
Total Conn.: 47 A
Miscellaneous Power 3424 VA 100.00% 3424 VA Total Est. Demand: 18136 VA
RECEPT 8220 VA 100.00% 8220 VA Total Conn. Load: 16832 VA
LIGHTING 5268 VA 125.00% 6585 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 41 A 37 A 63 A
Total Load: 4890 VA 4475 VA 7487 VA
41 42
39 40
37 38
35 36
33 LIGHTING - STAIRWELL 20 A 1 262 88 1 20 A LIGHTING - ELEVATOR 34
31 262 1 20 A LIGHTING - STAIRWELL 32
29 90 1560 1 20 A UH-1 - LOBBY 100 30
27 UH-2 - RISER ROOM 20 A 2 90 28
25 GEF-1 20 A 1 720 901 26
23 RECEPT OFFICE-1 XXX-1 20 A 1 720 901 24
21 901
3 20 A GEF-2
22
19 20
17 GARAGE LIGHTING 20 A 1 1197 18
15 1323 1 20 A GARAGE LIGHTING 16
13 LIGHTING - EXTERIOR 20 A 1 909 647 1 20 A LIGHTING - STAIRWELL 14
11 CO PANEL 20 A 1 180 1500 1 20 A UH-1 BIKE ROOM 12
9 RECEPT - ELEV. SUMP 20 A 1 180 0 1 20 A ELEV CAB PWR & LTG 10
7 RECEPT - FIRST FLOOR AREA B 20 A 1 720 180 1 20 A RECEPT - ELEV. SUMP 8
5 RECEPT - GARAGE LEVEL 20 A 1 1260 180 1 20 A RECEPT - FIRST FLOOR AREA A 6
3 LIGHTING - RM C002 20 A 1 165 1560 1 20 A UH-1 - STAIRWELL 4
1 LIGHTING - RM 103, 104 20 A 1 275 275 1 20 A LIGHTING - RM 100 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: GARAGE 001 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HA0
Notes:
Total Est. Demand: 114 A
Total Conn.: 117 A
Miscellaneous Power 26317 VA 100.00% 26317 VA Total Est. Demand: 41044 VA
RECEPT 13200 VA 87.88% 11600 VA Total Conn. Load: 42019 VA
LIGHTING 2502 VA 125.00% 3127 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 126 A 131 A 100 A
Total Load: 14732 VA 15283 VA 12004 VA
41 42
39 40
37 38
35 36
33 LIGHTING - RM M201, S201 20 A 1 220 220 1 20 A LIGHTING - RM E202, M202 34
31 0 591 1 20 A LIGHTING - CORRIDOR, S202 32
29 FCU-4 20 A 2 0 110 1 20 A LIGHTING - RM E201 30
27 RECEPT - SECOND FLOOR AREA B 20 A 1 900 1560 1 20 A UH-1 28
25 UH-1 - STAIRWELL 20 A 1 1560 2350 26
23 RECEPT ELEC. ROOM-4 E202-4 20 A 1 180 2350 2 30 A FCU-4 2ND FLOOR AREA A 24
21 UH-1 - STAIRWELL 20 A 1 1560 1080 1 20 A RECEPT - SECOND FLOOR AREA A 22
19 ACCESS CONTROL 20 A 1 540 0 20
17 RECEPT - SECOND FLOOR AREA A 20 A 1 1080 0 2 30 A FCU-4 2ND FLOOR AREA A 18
15 LIGHTING - RM 203 20 A 1 55 244 1 20 A LIGHTING - CORRIDOR 16
13 LIGHTING - ELEVATOR 20 A 1 88 401 1 20 A LIGHTING - RM C008 14
11 7205 358 1 20 A LIGHTING - RM C005, C009, RM C010 12
9 7205 190 1 20 A RECEPT - RM C006 10
7
FCU-6 90 A 3
7205 197 1 20 A LIGHTING - STAIRWELL 8
5 RECEPT AMENITIES-1 A101-1 20 A 1 540 180 1 20 A FACP 6
3 RECEPT - WORK ROOM 20 A 1 1500 550 1 20 A RECEPT - RM C007 4
1 RECEPT - OFFICE-2 XXX-2 20 A 1 900 900 1 20 A RECEPT - AMENITIES A101-1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 225 A
Mounting: RECESSED Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: AMENITIES-1 A101-1 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HA1
1
07/08/21