HomeMy WebLinkAboutE603 - ELECTRICAL SCHEDULESARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
E603ELECTRICALSCHEDULESNORTH ENDAPARTMENTSCARMEL, IN# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021
Notes:
Total Est. Demand: 76 A
Total Conn.: 75 A
Miscellaneous Power 19926 VA 100.00% 19926 VA Total Est. Demand: 27233 VA
RECEPT 5580 VA 100.00% 5580 VA Total Conn. Load: 26888 VA
LIGHTING 1382 VA 125.00% 1727 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 65 A 89 A 71 A
Total Load: 7837 VA 10637 VA 8414 VA
41 42
39 LIGHTING 20 A 1 110 40
37 38
35 36
33 34
31 LIGHTING - CORRIDOR ARA B 20 A 1 251 32
29 LIGHTING - RM E301, M301 20 A 1 220 581 1 20 A LIGHTING - CORRIDOR AREA A 30
27 RECEPT - ROOF 20 A 1 720 220 1 20 A LIGHTING - RM E302, M302 28
25 LIGHTING - ELEVATOR 20 A 1 540 180 1 20 A RECEPT 26
23 0 0 24
21 CU-1 - ON ROOF 20 A 2 0 0 2 20 A CU-1 - ON ROOF 22
19 PEV-1 20 A 1 0 0 1 20 A PEV-1 20
17 1456 0 18
15 CU-2 ON ROOF 20 A 2 1456 0 2 20 A CU-1 - ON ROOF 16
13 1456 0 14
11 CU-2 ON ROOF 25 A 2 1456 0 2 20 A CU-1 - ON ROOF 12
9 RECEPT - ROOF 20 A 1 1080 2350 10
7 RECEPT - THIRD FLOOR AREA B 20 A 1 900 2350 2 30 A FCU-4 3RD FLOOR AREA B 8
5 2350 2350 6
3 FCU-4 3RD FLOOR AREA A 30 A 2 2350 2350 2 30 A FCU-4 3RD FLOOR AREA A 4
1 RECEPT - THIRD FLOOR AREA A 20 A 1 1080 1080 1 20 A RECEPT - THIRD FLOOR AREA A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 1 A
Mounting: SURFACE Wires: 4 Mains Rating:
Supply From: Phases: 3 Mains Type:
Location: Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HA3
Notes:
Total Est. Demand: 1 A
Total Conn.: 1 A
Total Est. Demand: 360 VA
Miscellaneous Power 0 VA 0.00% 0 VA Total Conn. Load: 360 VA
RECEPT 360 VA 100.00% 360 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 3 A 0 A 0 A
Total Load: 360 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 ELEV CAB PWR & LTG 20 A 1 0 4
1 RECEPT - ELEV. SUMP 20 A 1 180 180 1 20 A RECEPT ELV-1-2 ELV-1-2 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 1 A
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: GARAGE 001 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HAE
Notes:
Total Est. Demand: 104 A
Total Conn.: 103 A
Miscellaneous Power 28226 VA 100.00% 28226 VA Total Est. Demand: 37629 VA
RECEPT 6840 VA 100.00% 6840 VA Total Conn. Load: 37117 VA
LIGHTING 2051 VA 125.00% 2564 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 93 A 101 A 117 A
Total Load: 11203 VA 11957 VA 13957 VA
41 42
39 UH-1 - BIKE ROOM-2 A102-2 20 A 1 180 180 1 20 A RECEPT Room A103-2, 115, A101-3 40
37 180 1 20 A UH-1 - RISER ROOM 38
35 180 1 20 A RECEPT Space E201-4 36
33 LIGHTING 20 A 1 577 1040 1 20 A LIGHTING 34
31 ELEV CAB PWR & LTG 20 A 1 0 32
29 ACCESS CONTROL 20 A 1 360 360 1 20 A ACCESS CONTROL 30
27 2350 0 28
25 Miscellaneous Power MECH. ROOM-1 M202-1 30 A 2 2350 0 2 30 A FCU-4 26
23 RECEPT - SECOND FLOOR 20 A 1 720 180 1 20 A RECEPT ELEC. ROOM-1 E202-1 24
21 RECEPT - ELEV. PIT 20 A 1 180 900 1 20 A RECEPT - SECOND FLOOR 22
19 180 1 20 A RECEPT - ELEV. SUMP 20
17 RECEPT - ELEV. SUMP 20 A 1 180 110 1 20 A LIGHTING - RM M202 18
15 RECEPT - ELEV. PIT 20 A 1 180 110 1 20 A LIGHTING - RM E202 16
13 RECEPT Space E201-5 20 A 1 180 110 1 20 A LIGHTING - RM M201 14
11 5720 105 1 20 A LIGHTING - C008 12
9 Miscellaneous Power STORAGE S101 70 A 2 5720 180 1 20 A RECEPT 10
7 2350 3692 8
5 FCU-4 30 A 2 2350 3692 2 20 A FCU-5 6
3 RECEPT - ELEC. ROOM-2 E102-2 20 A 1 180 180 1 20 A FACP 4
1 RECEPT - FIRST FLOOR 20 A 1 1080 1080 1 20 A RECEPT - FIRST FLOOR 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. ROOM-2 E101-2 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HB1
Notes:
Total Est. Demand: 84 A
HVAC-NON COINCIDENTAL 0 VA 0.00% 0 VA Total Conn.: 83 A
Miscellaneous Power 18803 VA 100.00% 18803 VA Total Est. Demand: 30246 VA
RECEPT 9060 VA 100.00% 9060 VA Total Conn. Load: 29770 VA
LIGHTING 1907 VA 125.00% 2383 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 92 A 61 A 104 A
Total Load: 10562 VA 7261 VA 11947 VA
41 LIGHTING - RM E302 20 A 1 110 88 1 20 A LIGHTING - ELEVATOR 42
39 LIGHTING - RM M301 20 A 1 110 110 1 20 A LIGHTING - RM 302 40
37 0 110 1 20 A LIGHTING - RM E301 38
35 HVAC-NON COINCIDENTAL 20 A 2 0 0 36
33 0 0 2 20 A HVAC-NON COINCIDENTAL 34
31 CU-1 - ON ROOF 20 A 2 0 0 32
29 RECEPT - ROOF 20 A 1 1080 0 2 20 A CU-1 - ON ROOF 30
27 0 0 28
25 HVAC-NON COINCIDENTAL 20 A 2 0 0 2 20 A HVAC-NON COINCIDENTAL 26
23 0 0 24
21 CU-1 - ON ROOF 20 A 2 0 0 2 20 A CU-1 - ON ROOF 22
19 2350 472 1 20 A LIGHTING 20
17 FCU-4 30 A 2 2350 907 1 20 A LIGHTING 18
15 RECEPT - TELECOM 20 A 1 180 360 1 20 A ACCESS CONTROL 16
13 2350 900 1 20 A RECEPT - THIRD FLOOR 14
11 FCU-4 30 A 2 2350 2350 12
9 RECEPT - THIRD FLOOR 20 A 1 900 2350 2 30 A FCU-4 10
7 UH-1 - STAIRWELL 20 A 1 1560 1560 1 20 A UH-1 - STAIRWELL 8
5 2350 360 1 20 A RECEPT - TELECOM 6
3 FCU-4 30 A 2 2350 900 1 20 A RECEPT - FOURTH FLOOR 4
1 RECEPT - FOURTH FLOOR 20 A 1 900 360 1 20 A ACCESS CONTROL 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 400 A
Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. ROOM E401 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HB4
Notes:
Total Est. Demand: 51 A
Total Conn.: 48 A
Miscellaneous Power 7384 VA 100.00% 7384 VA Total Est. Demand: 18474 VA
RECEPT 5376 VA 100.00% 5376 VA Total Conn. Load: 17327 VA
LIGHTING 4637 VA 125.00% 5796 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 69 A 52 A 30 A
Total Load: 7935 VA 5908 VA 3583 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 LIGHTING 20 A 1 88 18
15 LIGHTING - STAIRWELL 20 A 1 328 328 1 20 A LIGHTING - STAIRWELL 16
13 LIGHTING 20 A 1 516 991 1 20 A LIGHTING - EXTERIOR 14
11 LIGHTING - GARAGE 20 A 1 1204 1274 1 20 A LIGHTING - GARAGE 12
9 3692 0 10
7 Miscellaneous Power PARKING GARAGE 001 20 A 2 3692 0 8
5 RECEPT - GARAGE LEVEL 20 A 1 1080 0
3 20 A Miscellaneous Power PARKING GARAGE 001
6
3 ELEV CAB PWR & LTG 20 A 1 0 1560 4
1 SE-1 20 A 1 1176 1560 2 20 A UH-2 - RISER ROOM 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 100 A
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type:
Location: PARKING GARAGE 001 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HB0
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 110 VA
Total Conn. Load: 88 VA
LIGHTING 88 VA 125.00% 110 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 1 A 0 A 0 A
Total Load: 88 VA 0 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 LIGHTING - ELEV PIT 20 A 1 88 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 100 A
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type:
Location: PARKING GARAGE 001 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HBE
Notes:
Total Est. Demand: 122 A
Total Conn.: 119 A
Miscellaneous Power 32698 VA 100.00% 32698 VA Total Est. Demand: 43984 VA
RECEPT 6300 VA 100.00% 6300 VA Total Conn. Load: 42986 VA
LIGHTING 3989 VA 125.00% 4986 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 170 A 77 A 124 A
Total Load: 19650 VA 9223 VA 14113 VA
41 42
39 LIGHTING - RM M202 20 A 1 110 110 1 20 A LIGHTING - RM E202 40
37 LIGHTING - RM E201 20 A 1 110 165 1 20 A LIGHTING - RM E101 38
35 LIGHTING - SECOND FLOOR CORRIDOR 20 A 1 473 110 1 20 A LIGHTING - RM M201 36
33 LIGHTING - RM E102 20 A 1 110 110 1 20 A LIGHTING - RM101 34
31 LIGHTING - CORRIDOR 20 A 1 433 110 1 20 A LIGHTING - RM M102 32
29 262 1 20 A LIGHTING 30
27 LIGHTING 20 A 1 262 88 1 20 A LIGHTING - ELEVATOR 28
25 LIGHTING - RM A101, RM C010 20 A 1 121 203 1 20 A LIGHTING Room R101 26
23 ELEVATOR CONV. 20 A 1 180 180 1 20 A ELEVATOR PIT 24
21 LIGHTING - EXTERIOR 20 A 1 1212 0 1 20 A ELEVATOR CAB 22
19 5720 2964 20
17 FCU-5 70 A 2 5720 2964 2 20 A Miscellaneous Power MECH. ROOM-1 M102-1 18
15 2350 2350 16
13 FCU-4 30 A 2 2350 2350 2 30 A FCU-4 14
11 RECEPT - SECOND FLOOR 20 A 1 900 180 1 20 A RECEPT - TELECOM 12
9 ACCESS CONTROL 20 A 1 360 1080 1 20 A RECEPT - SECOND FLOOR 10
7 ACCESS CONTROL 20 A 1 540 2964 8
5 FACP 20 A 1 180 2964 2 40 A FCU-4 6
3 RECEPT - FIRST FLOOR 20 A 1 900 180 1 20 A RECEPT - TELECOM 4
1 RECEPT - RM A102, E101, M101 20 A 1 1440 180 1 20 A RECEPT - TELECOM 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 225 A
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: ELEC. ROOM-1 E101-1 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HC1
Notes:
Total Est. Demand: 134 A
HVAC-NON COINCIDENTAL 17472 VA 100.00% 17472 VA Total Conn.: 132 A
Miscellaneous Power 20030 VA 100.00% 20030 VA Total Est. Demand: 48254 VA
RECEPT 8100 VA 100.00% 8100 VA Total Conn. Load: 47724 VA
LIGHTING 2122 VA 125.00% 2652 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 144 A 128 A 126 A
Total Load: 17195 VA 15357 VA 15172 VA
41 42
39 LIGHTING - M301, E301, E302, M302 20 A 1 440 88 1 20 A LIGHTING - ELEVATOR 40
37 LIGHTING Room M401, E401, E402, M402 20 A 1 440 533 1 20 A LIGHTING - CORRIDOR 38
35 LIGHTING - CORRIDOR 20 A 1 621 2350 36
33 RECEPT - ROOF 20 A 1 1260 2350 2 30 A FCU-4 34
31 1248 1248 32
29 HVAC-NON COINCIDENTAL 20 A 2 1248 1248 2 20 A HVAC-NON COINCIDENTAL 30
27 1248 1248 28
25 HVAC-NON COINCIDENTAL 20 A 2 1248 1248 2 20 A HVAC-NON COINCIDENTAL 26
23 0 1248 24
21 CU-1 - ON ROOF 20 A 2 0 1248 2 20 A HVAC-NON COINCIDENTAL 22
19 1248 1248 20
17 CU-1 - ON ROOF 20 A 2 1248 1248 2 20 A CU-1 - ON ROOF 18
15 UH-1 20 A 1 720 360 1 20 A RECEPT - TELECOM 16
13 RECEPT - THIRD FLOOR 20 A 1 900 360 1 20 A RECEPT - TELECOM 14
11 2350 360 1 20 A ACCESS CONTROL 12
9 FCU-4 30 A 2 2350 720 1 20 A UH-1 10
7 RECEPT - THIRD FLOOR 20 A 1 1080 2350 8
5 RECEPT - FOURTH FLOOR 20 A 1 900 2350 2 30 A FCU-4 6
3 ACCESS CONTROL 20 A 1 360 2964 4
1 RECEPT - FOURTH FLOOR 20 A 1 1080 2964 2 30 A FCU-4 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 400 A
Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. ROOM E401 Volts: 120/208 Wye A.I.C. Rating: 18,000
Branch Panel:HC4
Notes:
Total Est. Demand: 1 A
Total Conn.: 1 A
Miscellaneous Power 0 VA 0.00% 0 VA Total Est. Demand: 470 VA
RECEPT 360 VA 100.00% 360 VA Total Conn. Load: 448 VA
LIGHTING 88 VA 125.00% 110 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 3 A 1 A 0 A
Total Load: 360 VA 88 VA 0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 ELEVATOR CAB 20 A 1 0 88 1 20 A LIGHTING - ELEVATOR 4
1 ELEVATOR PIT 20 A 1 180 180 1 20 A ELEVATOR CONV. 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: MCB Rating: 225 A
Mounting: Wires: 4 Mains Rating:
Supply From: Phases: 3 Mains Type: MLO
Location: ELEC. ROOM-1 E101-1 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel:HC1E
1
07/08/21