HomeMy WebLinkAboutE901 - ELECTRICAL DIAGRAMSMC2
METER CENTER
208/120V
1000A/3
MCB
NEMA
3R
65KAIC
(30) TOTAL
METERS
208/120V
125A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 1BR
APARTMENT
UNITS
125A CB (TYP.) FOR 1 BR UNITS
200A CB (TYP.) FOR 2 BR UNITS
'F2'
PAD MOUNTED
UTILITY
TRANSFORMER
(SIZED BY UTILITY)
T1
'F2'
LOCATED IN
BLDG A
(WEST WING)
MC1
METER CENTER
208/120V
800A/3
MCB
NEMA
3R
65KAIC
(20) TOTAL
METERS
208/120V
125A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 1BR
APARTMENT
UNITS
125A CB (TYP.) FOR 1 BR UNITS
200A CB (TYP.) FOR 2 BR UNITS 'F3'
LOCATED IN
BLDG A
(NORTH WING)
'F3' 'F4'
'F4'
CT1
METER
CABINET
208/120V
600A/3
NEMA
3R
65KAIC
'F4'
SEE SHEET E-902
FOR HOUSE
RISER DIAGRAM
PAD MOUNTED
UTILITY
TRANSFORMER
(SIZED BY UTILITY)
T2
'F4' 'F4'
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 2BR
APARTMENT
UNITS
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 2BR
APARTMENT
UNITS
CT2
METER
CABINET
208/120V
600A/3
NEMA
3R
65KAIC
'F4'
'F4'
CT3
METER
CABINET
208/120V
600A/3
NEMA
3R
65KAIC
OFFICE
OFFICE
'F7'
FIRE
PUMP
'F7'
20
PAD MOUNTED
UTILITY
TRANSFORMER
(SIZED BY UTILITY)
T3
MC3
METER CENTER
208/120V
1600A/3
MCB
NEMA
3R
65KAIC
(55) TOTAL
METERS
208/120V
125A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
1BR
APARTMENT
UNITS
'F1'
LOCATED IN
BLDG B
'F1' 'F3'
125A CB (TYP.) FOR 1BR UNITS
200A CB (TYP.) FOR 2 & 3 BR UNITS
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
2BR & 3BR
APARTMENT
UNITS
'F3'
CT4
METER
CABINET
208/120V
800A/3
NEMA
3R
65KAIC
'F3'
SEE SHEET E-903
FOR HOUSE
RISER DIAGRAM
'F7'
'F7'
FIRE
PUMP
20
PAD MOUNTED
UTILITY
TRANSFORMER
(SIZED BY UTILITY)
T4
MC6
METER CENTER
208/120V
1000A/3
MCB
NEMA
3R
65KAIC
(28) TOTAL
METERS
125A CB (TYP.) FOR 1 BR UNITS
200A CB (TYP.) FOR 2 & 3 BR UNITS
'F2'
LOCATED IN
BLDG C
(WEST WING)
'F2'
MC5
METER CENTER
208/120V
1000A/3
MCB
NEMA
3R
65KAIC
(34) TOTAL
METERS
208/120V
125A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
1BR
APARTMENT
UNITS
125A CB (TYP.) FOR 1 BR UNITS
200A CB (TYP.) FOR 2 BR UNITS 'F2'
LOCATED IN
BLDG C
(EAST WING)
'F2'
'F4'
CT5
METER
CABINET
208/120V
600A/3
NEMA
3R
65KAIC
'F4'
SEE SHEET E-903
FOR HOUSE
RISER DIAGRAM
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
1BR
APARTMENT
UNITS
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 2BR & 3BR
APARTMENT
UNITS
208/120V
200A/1
MCB
30 CKT
NEMA 1
TYPICAL LOAD
CENTER FOR
ALL 2BR & 3BR
APARTMENT
UNITS
'F4''F7'
'F7'
FIRE
PUMP
20 ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
E901ELECTRICALDIAGRAMSNORTH ENDAPARTMENTSCARMEL, IN12" = 1'-0"
LOAD CENTER DIAGRAM -BLDG A1
12" = 1'-0"
LOAD CENTER DIAGRAM -BLDG B 2
12" = 1'-0"
LOAD CENTER DIAGRAM -BLDG C 3
F9 20 1 3 #10 #10 3/4"
F8 40A 1 3 #8 #10 3/4"
F7 100A 1 4 #1 #8 1-1/2"
F6 225A 1 4 #4/0 #4 2-1/2"
F3B 400A 2 4 #3/0 #3 2"
F3A 400A 1 4 600 KCM #3 4"
F4 600 2 4 600 KCM N/A 4"
F3 800A 2 4 600 KCM N/A 4"
F2 1000A 3 4 600 KCM N/A 4"
F1 1600A 4 4 600 KCM N/A 4"
FEEDER AMPACITY # OF
SETS
# OF
WIRES WIRE SIZE GND
SIZE
CONDUIT
SIZE
250' - 315'(3) 500 KCM, (1) #6
GND 200A
200' - 250'(3) 350 KCM, (1) #6
GND 200A
175' - 200'(3) 250 KCM, (1) #6
GND 200A
150' - 175' (3) #4/0, (1) #6 GND 200A
200A UP TO 150' (3) #3/0, (1) #6 GND 200A
280' - 320'(3) 250 KCM, (1) #6
GND 125a
235' - 280' (3) #4/0, (1) #6 GND 125A
190' - 235' (3) #3/0, (1) #6 GND 125A
160' -190' (3) #2/0, (1) #6GND 125A
100A UP TO 160' (3) #1/0, (1) #6G 125A
DWELLING
UNIT LOAD
FEEDER
DISTANCE FEEDER (CU) SER BREAKER
LOAD CENTER FEEDER SCHEDULE
# DESCRIPTION DATE
07/08/21