HomeMy WebLinkAboutE901 - ELECTRICAL DIAGRAMSMC2 METER CENTER 208/120V 1000A/3 MCB NEMA 3R 65KAIC (30) TOTAL METERS 208/120V 125A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 1BR APARTMENT UNITS 125A CB (TYP.) FOR 1 BR UNITS 200A CB (TYP.) FOR 2 BR UNITS 'F2' PAD MOUNTED UTILITY TRANSFORMER (SIZED BY UTILITY) T1 'F2' LOCATED IN BLDG A (WEST WING) MC1 METER CENTER 208/120V 800A/3 MCB NEMA 3R 65KAIC (20) TOTAL METERS 208/120V 125A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 1BR APARTMENT UNITS 125A CB (TYP.) FOR 1 BR UNITS 200A CB (TYP.) FOR 2 BR UNITS 'F3' LOCATED IN BLDG A (NORTH WING) 'F3' 'F4' 'F4' CT1 METER CABINET 208/120V 600A/3 NEMA 3R 65KAIC 'F4' SEE SHEET E-902 FOR HOUSE RISER DIAGRAM PAD MOUNTED UTILITY TRANSFORMER (SIZED BY UTILITY) T2 'F4' 'F4' 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 2BR APARTMENT UNITS 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 2BR APARTMENT UNITS CT2 METER CABINET 208/120V 600A/3 NEMA 3R 65KAIC 'F4' 'F4' CT3 METER CABINET 208/120V 600A/3 NEMA 3R 65KAIC OFFICE OFFICE 'F7' FIRE PUMP 'F7' 20 PAD MOUNTED UTILITY TRANSFORMER (SIZED BY UTILITY) T3 MC3 METER CENTER 208/120V 1600A/3 MCB NEMA 3R 65KAIC (55) TOTAL METERS 208/120V 125A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR 1BR APARTMENT UNITS 'F1' LOCATED IN BLDG B 'F1' 'F3' 125A CB (TYP.) FOR 1BR UNITS 200A CB (TYP.) FOR 2 & 3 BR UNITS 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR 2BR & 3BR APARTMENT UNITS 'F3' CT4 METER CABINET 208/120V 800A/3 NEMA 3R 65KAIC 'F3' SEE SHEET E-903 FOR HOUSE RISER DIAGRAM 'F7' 'F7' FIRE PUMP 20 PAD MOUNTED UTILITY TRANSFORMER (SIZED BY UTILITY) T4 MC6 METER CENTER 208/120V 1000A/3 MCB NEMA 3R 65KAIC (28) TOTAL METERS 125A CB (TYP.) FOR 1 BR UNITS 200A CB (TYP.) FOR 2 & 3 BR UNITS 'F2' LOCATED IN BLDG C (WEST WING) 'F2' MC5 METER CENTER 208/120V 1000A/3 MCB NEMA 3R 65KAIC (34) TOTAL METERS 208/120V 125A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR 1BR APARTMENT UNITS 125A CB (TYP.) FOR 1 BR UNITS 200A CB (TYP.) FOR 2 BR UNITS 'F2' LOCATED IN BLDG C (EAST WING) 'F2' 'F4' CT5 METER CABINET 208/120V 600A/3 NEMA 3R 65KAIC 'F4' SEE SHEET E-903 FOR HOUSE RISER DIAGRAM 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR 1BR APARTMENT UNITS 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 2BR & 3BR APARTMENT UNITS 208/120V 200A/1 MCB 30 CKT NEMA 1 TYPICAL LOAD CENTER FOR ALL 2BR & 3BR APARTMENT UNITS 'F4''F7' 'F7' FIRE PUMP 20 ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031 JANUARY 15, 2021 BID SET E901ELECTRICALDIAGRAMSNORTH ENDAPARTMENTSCARMEL, IN12" = 1'-0" LOAD CENTER DIAGRAM -BLDG A1 12" = 1'-0" LOAD CENTER DIAGRAM -BLDG B 2 12" = 1'-0" LOAD CENTER DIAGRAM -BLDG C 3 F9 20 1 3 #10 #10 3/4" F8 40A 1 3 #8 #10 3/4" F7 100A 1 4 #1 #8 1-1/2" F6 225A 1 4 #4/0 #4 2-1/2" F3B 400A 2 4 #3/0 #3 2" F3A 400A 1 4 600 KCM #3 4" F4 600 2 4 600 KCM N/A 4" F3 800A 2 4 600 KCM N/A 4" F2 1000A 3 4 600 KCM N/A 4" F1 1600A 4 4 600 KCM N/A 4" FEEDER AMPACITY # OF SETS # OF WIRES WIRE SIZE GND SIZE CONDUIT SIZE 250' - 315'(3) 500 KCM, (1) #6 GND 200A 200' - 250'(3) 350 KCM, (1) #6 GND 200A 175' - 200'(3) 250 KCM, (1) #6 GND 200A 150' - 175' (3) #4/0, (1) #6 GND 200A 200A UP TO 150' (3) #3/0, (1) #6 GND 200A 280' - 320'(3) 250 KCM, (1) #6 GND 125a 235' - 280' (3) #4/0, (1) #6 GND 125A 190' - 235' (3) #3/0, (1) #6 GND 125A 160' -190' (3) #2/0, (1) #6GND 125A 100A UP TO 160' (3) #1/0, (1) #6G 125A DWELLING UNIT LOAD FEEDER DISTANCE FEEDER (CU) SER BREAKER LOAD CENTER FEEDER SCHEDULE # DESCRIPTION DATE 07/08/21