HomeMy WebLinkAboutEL110a - BUILDING LIGHTING PLANS - BUILDING AM
GARAGE
001
ST2-0
ST2-0
ST1-0
ST1-0
G1 G1 G1 G1
G1 G1 G1 G1
G1 G1 G1 G1
G1
G1
G1 G1
G1
G1 G1
G1
G1 G1
G1
G1 G1
G1
G1 G1
G1
G1 G1
G1
G1
G1
G1
G1
G1
G1 G1
G1
HA0 -16 HA0 -16
HA0 -16 HA0 -16 HA0 -16
HA0 -16 HA0 -16 HA0 -16 HA0 -16 HA0 -16
HA0 -16 HA0 -16
HA0 -16 HA0 -16 HA0 -16 HA0 -16
HA0 -16
HA0 -16 HA0 -16
HA0 -16
HA0 -16 HA0 -17 HA0 -17
HA0 -17 HA0 -17
HA0 -17 HA0 -17 HA0 -17
HA0 -17
HA0 -17 HA0 -17
HA0 -17
HA0 -17 HA0 -17
HA0 -17
HA0 -17 HA0 -17
HA0 -17HA0 -17
HA0 -17
H2
H2 H4
H4
H2
H2
H3
H3
H3
EM EM EM EM EM EM
HA0 -32
X2
HA0 -33
G1
ELV-1
ELV-1
ST2-0
ST2-0
HA0 -34
RISER ROOM
002
HA0 -3
HAE
HA0
MDPA
1 LC ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
EL110aBUILDING LIGHTINGPLANS -BUILDING ANORTH ENDAPARTMENTSCARMEL, INSHEET KEYNOTES
1 PROVIDE LIGHTING CONTACTOR WITH PROGRAMMABLE TIME CLOCK FOR
EXTERIOR LIGHTING CONTROL.
1/8" = 1'-0"
BUILDING A LIGHTING LOWER FLOOR PLAN -AREA A 1
GENERAL NOTES
A REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
B REFER TO E601 FOR LIGHTING FIXTURE SCHEDULES
C EMERGENCY LIGHT FIXTURE LOCATIONS SHOWN ARE NEOT EXACT. SPACE
FIXTURES AT APPROXIMATELY 42'-0" ON CENTER OR ACCORDING TO
MANUFACTURERS RECOMENDATIONS.
D OCCUPANCY SENSOR LOCATIONS SHOWN ARE NOT EXACT. CENTER
SENSORS WITHIN HALLWAY AND SPACE AT APPROXIMATELY 30'-0" ON
CENTER OR ACCORDING TO MANNUFACTURERS RECOMENDATION. MOUNT TO
BOTTOM OF DUCT SUPPORTS. COORDINATE WITH MECHANICAL.
E CORRIDOR LIGHTING FIXTURES ARE TO DIM TO 50% OUTPUT WHEN NO
OCCUPANCY IS DETECTED.
F FIXTURE MARKED WITH 'EM' SHOULD BE SUPPLIED WITH INTEGRAL BATTERY
BACK-UP.
G RECESSED FIXTURES INSTALLED WITHIN THE THERMAL ENVELOPE MUST BE
SEALED TO LIMIT AIR LEAKAGE.
# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021
1
07/08/21