HomeMy WebLinkAboutEL111b - BUILDING LIGHTING PLANS - BUILDING AMMM M M MM M M ELV2-1 ELV2-1 ST3-1 ST3-1 OFFICE 101 H2 H2H4 H4 H3 TH3 H3 H3 H1 H1 H1 H1 H1 H1 X1 H1 H1H1 X1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1H1 H1 T2AMDP-T2 HA1 XR X1 1 1 XR XR XR XR H1 H1 H1 H1 H1 H1 H1 H1 S4 S4 XR S4 S4 S4 S4 S4 X1 S4 AMENITIES C008 HA1 -8 RESTROOM C007 HA1 -4 RESTROOM C006 HA1 -10 BIKE ROOM C009 CORRIDOR C005 MAIL ROOM C010 HA1 -12 HA1 -12 HA1 -12 HA1 -12 MECH. ROOM M101 HA1 -13 OFFICE C001 OFFICE C002 HA1 -14 HA1 -14 HA1 -14 HA1 -14 WORK ROOM C004 ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031 JANUARY 15, 2021 BID SET EL111bBUILDING LIGHTINGPLANS -BUILDING ANORTH ENDAPARTMENTSCARMEL, INSHEET KEYNOTES 1 WALL SENSOR NEEDS TO BE RATED FOR FAN OPERATION. 1/8" = 1'-0" BUILDING A LIGHTING FIRST FLOOR PLAN -AREA B 1 GENERAL NOTES A REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS, AND ABBREVIATIONS. B REFER TO E601 FOR LIGHTING FIXTURE SCHEDULES C EMERGENCY LIGHT FIXTURE LOCATIONS SHOWN ARE NEOT EXACT. SPACE FIXTURES AT APPROXIMATELY 42'-0" ON CENTER OR ACCORDING TO MANUFACTURERS RECOMENDATIONS. D OCCUPANCY SENSOR LOCATIONS SHOWN ARE NOT EXACT. CENTER SENSORS WITHIN HALLWAY AND SPACE AT APPROXIMATELY 30'-0" ON CENTER OR ACCORDING TO MANNUFACTURERS RECOMENDATION. MOUNT TO BOTTOM OF DUCT SUPPORTS. COORDINATE WITH MECHANICAL. E CORRIDOR LIGHTING FIXTURES ARE TO DIM TO 50% OUTPUT WHEN NO OCCUPANCY IS DETECTED. F FIXTURE MARKED WITH 'EM' SHOULD BE SUPPLIED WITH INTEGRAL BATTERY BACK-UP. G RECESSED FIXTURES INSTALLED WITHIN THE THERMAL ENVELOPE MUST BE SEALED TO LIMIT AIR LEAKAGE. # DESCRIPTION DATE 1 BID DOCUMENT 01/15/2021 1 07/08/21