HomeMy WebLinkAboutEL123 - BUILDING LIGHTING PLANS - BUILDING BM M M M M M M
M
M
H2
H2
H5
H5
H1 H1
H1 H1 H1X1
H1
H1
H1
X2
X2H5
H5
H1 X1
X2
H2
H2 H1 H1
H1
H1
H1
X2
H1H1H1
H1
H1H1
H1
H1H1 H1
H1
H1 H1 H1 H1H1 H1 H1H1 H5
H5
H5
H5
H5
H5
H5
H5 H5
X1 X2 X2 X2
X2 X2
X2
H5
X1
T
H3H3
T
H3H3
T
H3 H3
T
H3 H3
HB4 -20
HB4 -38
HB4 -39
HB4 -40
HB4 -41
UNIT B2
302
UNIT A4
304
UNIT A1
306
UNIT A2
308
UNIT A2
310
UNIT A1 IDD
312
UNIT B2
316
UNIT B2
315
UNIT A4
313
ELEC. ROOM
E302
MECH. ROOM
M302
UNIT A1 IDD
311
UNIT A2
309
UNIT A2
307
UNIT A1
305
ELEC. ROOM
E301
MECH. ROOM
M301
UNIT B2
301
3 / E403
3 / E402 1 / E401 3 / E401 3 / E401 2 / E401
3 / E403
3 / E403
3 / E4022 / E401 3 / E401 3 / E401 1 / E401
3 / E403
HB4 -40
HB4 -20
HB4 -20
HB4 -20
HB4 -20
HB0 -15
HB0 -16 ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
EL123BUILDING LIGHTINGPLANS -BUILDING BNORTH ENDAPARTMENTSCARMEL, INSHEET KEYNOTES
1/8" = 1'-0"
BUILDING B LIGHTING THIRD FLOOR PLAN1
GENERAL NOTES
A REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
B REFER TO E601 FOR LIGHTING FIXTURE SCHEDULES
C EMERGENCY LIGHT FIXTURE LOCATIONS SHOWN ARE NEOT EXACT. SPACE
FIXTURES AT APPROXIMATELY 42'-0" ON CENTER OR ACCORDING TO
MANUFACTURERS RECOMENDATIONS.
D OCCUPANCY SENSOR LOCATIONS SHOWN ARE NOT EXACT. CENTER
SENSORS WITHIN HALLWAY AND SPACE AT APPROXIMATELY 30'-0" ON
CENTER OR ACCORDING TO MANNUFACTURERS RECOMENDATION. MOUNT TO
BOTTOM OF DUCT SUPPORTS. COORDINATE WITH MECHANICAL.
E CORRIDOR LIGHTING FIXTURES ARE TO DIM TO 50% OUTPUT WHEN NO
OCCUPANCY IS DETECTED.
F FIXTURE MARKED WITH 'EM' SHOULD BE SUPPLIED WITH INTEGRAL BATTERY
BACK-UP.
G RECESSED FIXTURES INSTALLED WITHIN THE THERMAL ENVELOPE MUST BE
SEALED TO LIMIT AIR LEAKAGE.
# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021
1
07/08/21