HomeMy WebLinkAboutM000 - SYMBOLS AND ABBREVIATIONSNOT ALL NOTES, DESIGNATORS, SYMBOLS OR ABBREVIATIONS MAY APPLY TO THIS PROJECTRECTANGULAR DUCTWORK
DESIGNATION IN INCHES, FIRST
DIMENSION IS SIDE SHOWN
ROUND SPIRAL DUCTWORK
DESIGNATION IN INCHES
FLAT OVAL DUCTWORK
DESIGNATION IN INCHES, FIRST
DIMENSION IS SIDE SHOWN
RECTANGULAR SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
ROUND SPIRAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE
RECTANGULAR SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
ROUND SPIRAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK
DROP
RECTANGULAR RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
ROUND SPIRAL RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK
RISE
RECTANGULAR RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
ROUND SPIRAL RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK
DROP
RECTANGULAR EXHAUST AIR,
RELIEF AIR DUCTWORK RISE
ROUND SPIRAL EXHAUST
AIR, RELIEF AIR DUCTWORK
RISE
FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK RISE
RECTANGULAR EXHAUST AIR,
RELIEF AIR DUCTWORK DROP
ROUND SPIRAL EXHAUST
AIR, RELIEF AIR DUCTWORK
DROP
FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK DROP
DUCTWORK CONSTRUCTED
OF ALUMINUM, STAINLESS
STEEL
DUCTWORK RISE IN
DIRECTION OF FLOW
DUCTWORK DROP IN
DIRECTION OF FLOW
STANDARD DEGREE ANGLE
TRANSITION IN DIRECTION
OF FLOW
SUPPLY AIR, OUTSIDE AIR IN
DIRECTION OF FLOW
RETURN AIR, EXHAUST AIR,
TRANSFER AIR, RELIEF AIR
IN DIRECTION OF FLOW
ECCENTRIC DUCT TRANSITION CONCENTRIC DUCT
TRANSITION
RECTANGULAR TO ROUND,
FLAT OVAL DUCT TRANSITION
VOLUME DAMPER ACCESS DOOR DUCTWORK CAP
MOTORIZED DAMPER WITH
ACCESS DOOR
FIRE DAMPER WITH ACCESS
DOOR
SMOKE DAMPER WITH
ACCESS DOOR
BACK DRAFT DAMPER WITH
ACCESS DOOR
AIRFLOW MEASURING STATION
WITH ACCESS DOOR
FIRE AND SMOKE DAMPER
WITH ACCESS DOOR
PRESSURE SENSOR WITH
ACCESS DOOR
TEMPERATURE SENSOR WITH
ACCESS DOOR
SMOKE DETECTOR WITH
ACCESS DOOR
STATIC PRESSURE CHANGE
IN INCHES
FLEXIBLE DUCTWORK
CONNECTION
DUCTWORK LINING OR
DOUBLE WALL DUCTWORK,
DESIGNATION SHOWN IS
FREE AREA
45° BEVELED FITTING FOR
RECTANGULAR TO
RECTANGULAR DUCTWORK
RADIUS DUCTWORK ELBOW
(CENTERLINE RADIUS 1.5xW)SOUND ATTENUATOR
CONICAL FITTING FOR
ROUND OR FLAT OVAL TO
RECTANGULAR DUCTWORK
RADIUS DUCTWORK ELBOW
WITH TURNING VANES MITERED DUCTWORK ELBOW
CONICAL FITTING FOR
ROUND OR FLAT OVAL TO
ROUND OR FLAT OVAL
DUCTWORK
WYE RADIUS DUCTWORK
ELBOW
MITERED DUCTWORK ELBOW
WITH TURNING VANES
45° RADIUS DUCTWORK
ELBOW (CENTERLINE RADIUS
1.5xW)
TRANSFER AIR ELBOW WITH
DUCTWORK STUBS FOR
SOUND ATTENUATION
SPIN-IN FITTING FOR
ROUND TO RECTANGULAR
DUCTWORK, LOW PRESSURE
DUCTWORK
CEILING PANEL SUPPLY AIR
DIFFUSER ROUND SUPPLY AIR DIFFUSER
FLEXIBLE DUCTWORK
CONNECTION TO DIFFUSER,
MAXIMUM SIX FEET
RECTANGULAR SUPPLY AIR
REGISTER
RETURN AIR, EXHAUST AIR,
TRANSFER AIR REGISTER OR
GRILLE
SIDEWALL SUPPLY AIR
REGISTER OR GRILLE
SIDEWALL RETURN AIR,
EXHAUST AIR, TRANSFER AIR
REGISTER OR GRILLE
LINEAR SLOT SUPPLY AIR
DIFFUSER
THERMOSTAT WITH
ASSOCIATED EQUIPMENT
DESIGNATION (OPTIONAL)
TEMPERATURE SENSOR DOOR GRILLE OR UNDERCUT
DOOR
HUMIDISTAT WITH
ASSOCIATED EQUIPMENT
DESIGNATION (OPTIONAL)
CARBON DIOXIDE SENSOR CEILING DESTRATIFICATION
FAN
TEMPERATURE CONTROL
PANEL VARIABLE FREQUENCY DRIVE CENTRIFUGAL ROOF
EXHAUST FAN
HYDRONIC REHEAT COIL
WITH ACCESS DOOR
TERMINAL UNIT WITH
HYDRONIC REHEAT COIL INLINE FAN
ELECTRIC REHEAT COIL
WITH ACCESS DOOR
TERMINAL UNIT WITH
ELECTRIC REHEAT COIL
SERIES/PARALLEL FAN
POWERED TERMINAL UNIT
BASE MOUNTED PUMP UNIT VENTILATOR UNIT HEATER
HEAT EXCHANGER AIR SEPARATOR FINNED TUBE RADIATION
HVAC IDENTITY SYMBOLS
GENERAL NOTES
HIGH PRESSURE STEAM (>61 PSIG)
MEDIUM PRESSURE STEAM (16-60 PSIG)
LOW PRESSURE STEAM (<15 PSIG)
HIGH PRESSURE CONDENSATE
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
BOILER FEED
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
HUMIDIFICATION
MAKE UP WATER
AIR RELIEF VENT
HEAT RECLAIM PIPING
HEATING WATER SUPPLY
HEATING WATER RETURN
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DUAL TEMPERATURE SUPPLY
DUAL TEMPERATURE RETURN
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
GLYCOL HEATING SUPPLY
GLYCOL HEATING RETURN
CONDENSATE DRAIN
CONTROL WIRING
SECTION INDICATOR: REFERENCE SECTION LOCATION THROUGH AN AREA
FOR ADDITIONAL INFORMATION.
KEYNOTE INDICATOR: REFERENCE SHEET KEYNOTE LOCATION FOR
ADDITIONAL INFORMATION.
DETAIL INDICATOR: REFERENCE DETAIL LOCATION FOR ADDITIONAL
INFORMATION.
DRAWING BLOCK TITLE
INDICATOR:
REFERENCE DRAWING MODULE LOCATION FOR
ADDITIONAL INFORMATION.
MATCH LINE INDICATOR: REFERENCE SHEET LOCATION FOR ADDITIONAL
INFORMATION.
REVISION INDICATOR: REFERENCE TITLE BLOCK LOCATION FOR
ADDITIONAL INFORMATION.
EQUIPMENT INDICATOR: REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
DIFFUSER, GRILLE,
REGISTER INDICATOR:
REFERENCE SCHEDULE LOCATION FOR
ADDITIONAL INFORMATION.
TU-XL.##
ø DIAMETER, PHASE ET EXPANSION TANK OAT OUTSIDE AIR TEMPERATURE (°F)
°F DEGREES FAHRENHEIT EW EMERGENCY EYEWASH OBD OPPOSED BLADE DAMPER
A/C AIR CONDITIONING EWC ELECTRIC WATER COOLER OD OUTSIDE DIAMETER, OVERFLOW DRAIN
ACC AIR COOLED CONDENSER EWT ENTERING WATER TEMPERATURE (°F) OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
ACCU AIR COOLED CONDENSING UNIT EXH EXHAUST OSD OPEN SITE DRAIN
AD AREA DRAIN, ACCESS DOOR EXIST EXISTING OZ OUNCE
AFF ABOVE FINISHED FLOOR F FURNACE P PUMP
AFMS AIR FLOW MEASURING STATION F&T FLOAT AND THERMOSTATIC STEAM TRAP PBD PARALLEL BLADE DAMPER
AGA AMERICAN GAS ASSOCIATION FCO FLOOR CLEANOUT PC PLUMBING CONTRACTOR
AHU AIR HANDLING UNIT FCU FAN COIL UNIT PD PRESSURE DROP
AL ACOUSTICALLY LINED, ALUMINUM FD FLOOR DRAIN, FIRE DAMPER PE PNEUMATIC ELECTRIC
AMB AMBIENT FDC FIRE DEPARTMENT CONNECTION PH PHASE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE FDTN FOUNDATION PIV POST INDICATOR VALVE
AO ANALOG OUTPUT FE FIRE EXTINGUISHER PPM PARTS PER MILLION
AP ACID PROOF, ACCESS PANEL FHC FIRE HOSE CABINET PRV PRESSURE REDUCING VALVE
APD AIR PRESSURE DROP (IN. WC.) FLR FLOOR PSI POUNDS PER SQUARE INCH
ARCH ARCHITECT FM FACTORY MUTUAL PSIA POUNDS PER SQUARE INCH ABSOLUTE
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE FOV FUEL OIL VENT PSIG POUNDS PER SQUARE INCH GAUGE
ARV AIR RELIEF VALVE FPM FEET PER MINUTE PTAC PACKAGED TERMINAL AIR CONDITIONER
AS AIR SEPARATOR FPVAV FAN POWERED VAV UNIT PVC POLYVINYL CHLORIDE
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING FS FLOOR SINK R REGISTER
AND AIR CONDITIONING ENGINEERS FSC FIRE SUPPRESSION CONTRACTOR R12 REFRIGERANT (12, 22, ETC.)
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS FSD COMBINATION FIRE/SMOKE DAMPER RA RETURN AIR
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS FT FOOT, FEET RADN RADIATION
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS FTG FOOTING RAT RETURN AIR TEMPERATURE (°F)
ATM ATMOSPHERE FTR FINNED TUBE RADIATION RCP REINFORCED CONCRETE PIPE
AUTO AUTOMATIC G NATURAL GAS RD ROOF DRAIN
AVG AVERAGE GA GAGE OR GAUGE REV REVOLUTIONS
AVS ACID VENT STACK GAL GALLON RF RETURN FAN
AW ACID WASTE GC GENERAL CONTRACTOR RG RETURN GRILLE
AWWA AMERICAN WATER WORKS ASSOCIATION GIV GRAVITY INTAKE VENTILATOR RH RELATIVE HUMIDITY, RODDING HOLE
BD BUTTERFLY DAMPER GPD GALLONS PER DAY RM ROOM
BDD BACKDRAFT DAMPER GPH GALLONS PER HOUR RP RADIANT PANEL
BE BOTTOM ELEVATION GPM GALLONS PER MINUTE RPM REVOLUTIONS PER MINUTE
BF BARRIER FREE GR GRILLE, GRAINS RPS REVOLUTIONS PER SECOND
BFC BELOW FINISHED CEILING GRV GRAVITY RELIEF VENTILATOR RTU ROOF TOP UNIT
BHP BRAKE HORSEPOWER GT GREASE TRAP RV RELIEF VALVE, ROOF VENT
BLDG BUILDING HB HOSE BIBB SA SUPPLY AIR
BOD BOTTOM OF DUCT HD HEAD (FT.) SAN SANITARY
BOP BOTTOM OF PIPING Hg MERCURY SD SUPPLY DIFFUSER, SMOKE DAMPER
BSMT BASEMENT HHWP HEATING HOT WATER PUMP SEER SEASONAL ENERGY EFFICIENCY RATIO
BT BATHTUB HO HUB OUTLET SF SQUARE FOOT, SUPPLY FAN, SAFETY FACTOR
BTM BOTTOM HORIZ HORIZONTAL SG SUPPLY GRILLE
BtuH BRITISH THERMAL UNIT PER HOUR HP HORSEPOWER, HEAT PUMP SU SHOWER UNIT
CA COMPRESSED AIR HR HOUR(S) SK SINK
CAV CONSTANT AIR VOLUME HRTU HEATING ONLY ROOFTOP UNIT SMACNA SHEET METAL AND AIR CONDITIONING
CB CATCH BASIN HX HEAT EXCHANGER CONTRACTORS NATIONAL ASSOCIATION
CCW COUNTERCLOCKWISE
Hz HERTZ SP STATIC PRESSURE
CD CONDENSATE DRAIN
IB INVERTED BUCKET STEAM TRAP SPEC SPECIFICATION
CO CARBON DIOXIDE
ID INSIDE DIAMETER SQ SQUARE
CF CEILING FAN
IE INVERT ELEVATION SR SUPPLY REGISTER
CFM CUBIC FEET PER MINUTE
IN INCH, INCHES SRV SAFETY RELIEF VALVE
CH CHILLER
INT INTERIOR SS SERVICE SINK, STAINLESS STEEL
CHWP CHILLED WATER PUMP
INV INVERT STD STANDARD
CI CAST IRON
IPS INTERNATIONAL PIPE STANDARD SV STEAM VENT
CMP CORRUGATED METAL PIPE
IW INDIRECT WASTE TCC TEMPERATURE CONTROL CONTRACTOR
CO CLEANOUT
K KELVIN TCP TEMPERATURE CONTROL PANEL
COMPR COMPRESSOR
KEC KITCHEN EQUIPMENT CONTRACTOR TD TEMPERATURE DIFFERENCE
COND CONDENSER
kW KILOWATT TE TOP ELEVATION
CONV CONVECTOR
LAB LABORATORY TEMP TEMPERATURE
CP CONDENSATE PUMP
LAT LEAVING AIR TEMPERATURE (°F) TF TRANSFER FAN
CPVC CHLORINATED POLYVINYL CHLORIDE
L LAVATORY TG TRANSFER GRILLE
CT COOLING TOWER
LBS POUNDS TMV THERMOSTATIC MIXING VALVE
CU CONDENSING UNIT
LD LINEAR DIFFUSER TONS TONS OF REFRIGERATION
CUH CABINET UNIT HEATER
LP LIQUID PETROLEUM TP TRAP PRIMER
CUV CLASSROOM UNIT VENTILATOR
LTG LIGHTING TRANS TRANSITION
CV CONTROL VALVE
LWT LEAVING WATER TEMPERATURE (°F) TS TAMPER SWITCH
CW CLOCKWISE
MA MIXED AIR TSP TOTAL STATIC PRESSURE (IN. WC.)
CWP CONDENSER WATER PUMP
MAT MIXED AIR TEMPERATURE (°F) TXV THERMAL EXPANSION VALVE
dB DECIBEL
MAX MAXIMUM TYP TYPICAL
DB DRY BULB
MB MOP BASIN UCD UNDERCUT DOOR
DF DRINKING FOUNTAIN
MBH THOUSAND Btu PER HOUR UH UNIT HEATER
DG DOOR GRILLE
MC MECHANICAL CONTRACTOR UL UNDERWRITERS LABORATORIES
DH DUCT HEATER
MCA MINIMUM CIRCUIT AMPS UON UNLESS OTHERWISE NOTED
DI DIGITAL INPUT
MCC MOTOR CONTROL CENTER UR URINAL
DIA DIAMETER
MD MOTORIZED DAMPER US UP STREAM
DIFF DIFFUSER
MFR MANUFACTURER UV UNIT VENTILATOR
DN DOWN
MH MANHOLE V VOLTS, VENT
DO DIGITAL OUTPUT
MIN MINIMUM VAC VACUUM
DS DOWNSPOUT, DOWN STREAM
MISC MISCELLANEOUS VAV VARIABLE AIR VOLUME
DW DISTILLED WATER
MS MOP SINK VB VACUUM BREAKER
DWG DRAWING
MTD MOUNTED VD VOLUME DAMPER
DWH DOMESTIC WATER HEATER
MV MANUAL VENT VEL VELOCITY
DWV DRAIN, WASTE & VENT
N NITROGEN VERT VERTICAL
DX DIRECT EXPANSION
NA NOT APPLICABLE VF VENTILATION FAN
EA EXHAUST AIR
NC NOISE CRITERIA, NORMALLY CLOSED VFD VARIABLE FREQUENCY DRIVE
EAT ENTERING AIR TEMPERATURE (°F)
NEC NATIONAL ELECTRIC CODE VTR VENT THROUGH ROOF
EC ELECTRICAL CONTRACTOR
NFC NATIONAL FIRE CODE VUV VERTICAL UNIT VENTILATOR
ECO EXTERIOR CLEANOUT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION W WASTE, WATT
EDR EQUIVALENT DIRECT RADIATION
NFWH NON-FREEZE WALL HYDRANT
WC WATER COLUMN, WATER CLOSET, WALL
CASSETTEEER ENERGY EFFICIENCY RATIO
NIC NOT IN CONTRACT
EF EXHAUST FAN
NO NORMALLY OPEN, NITROUS OXIDE
EFF EFFICIENCY
NOM NOMINAL WCO WALL CLEANOUT
EG EXHAUST GRILLE
NPW NON-POTABLE WATER WH WALL HYDRANT
EL ELEVATION
NTS NOT TO SCALE WPD WATER PRESSURE DROP (FT. HD.)
EOM END OF MAIN DRIP
O OXYGEN WSHP WATER SOURCE HEAT PUMP
ES EMERGENCY SHOWER
OA OUTSIDE AIR YD YARD DRAIN
ESP EXTERNAL STATIC PRESSURE (IN. WG.)
OAI OUTSIDE AIR INTAKE
FLOW DIRECTION ARROW, PITCH DIRECTION ARROW
PIPE RISE
PIPE DROP
PIPE CAP
PIPE CONTINUES (REFERENCE ELSEWHERE)
PIPE GUIDE
PIPE ANCHOR
FLEXIBLE CONNECTOR
EXPANSION COMPENSATOR
EXPANSION LOOP
CONCENTRIC, ECCENTRIC FITTINGS
UNION, FLANGED UNION
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
PLUG VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
ANGLE VALVE
RELIEF VALVE
VALVE WITH OUTSIDE STEM & YOKE
PNEUMATIC TWO-WAY CONTROL VALVE
PNEUMATIC THREE-WAY CONTROL VALVE
ELECTRIC TWO-WAY CONTROL VALVE
ELECTRIC THREE-WAY CONTROL VALVE
SOLENOID VALVE
FLOW SWITCH
PRESSURE SWITCH
AQUASTAT
ORIFICE FLOW METER
VENTURI FLOW METER
TURBINE FLOW METER
CALIBRATED BALANCE VALVE
AUTOMATIC FLOW CONTROL VALVE
STRAINER
STRAINER WITH CAPPED BLOWDOWN
MANUAL AIR VENT
AUTOMATIC AIR VENT
VACUUM BREAKER
TEMPERATURE/PRESSURE TAP
THERMOMETER
PRESSURE GAUGE
STEAM TRAP WITH DESIGNATION
REFRIGERATION SIGHT GLASS
AIR FILTER/DRYER
REFRIGERATION THERMAL EXPANSION VALVE
INLINE PUMP
DIFFERENTIAL PRESSURE TRANSMITTER
WATER METER
GAS METER
GENERAL NOTES: NOTES THAT APPLY EQUALLY TO ALL DISCIPLINES
WITHIN THE DRAWING SET.
GENERAL
MECHANICAL NOTES:
NOTES THAT APPLY EQUALLY TO ALL SHEETS WITHIN
THE DISCIPLINE.
GENERAL SHEET
NOTES:
NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR.
SHEET KEYNOTES:NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET
ON WHICH THEY APPEAR AND USE A KEYNOTE
INDICATOR TO IDENTIFY ITEMS.
THIN CONTINUOUS LINETYPE INDICATE EXISTING ITEMS TO
REMAIN.
INTERMEDIATE DASHED LINETYPE INDICATE EXISTING ITEMS
TO BE REMOVED.
INTERMEDIATE OR WIDE CONTINUOUS LINETYPE INDICATE
NEW ITEMS.
THIN HALFTONE LINETYPE INDICATE ITEMS BY OTHER
DISCIPLINE.
INDICATES POINT OF NEW CONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
INDICATES POINT OF DISCONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
PIPING LINE SYMBOLS
REFERENCE SYMBOLS
ABBREVIATIONS AND TERMS PIPING IDENTITY SYMBOLS
NOTATION DESIGNATORS
LINETYPE DESIGNATORS
DRAWING BLOCK TITLE
SECTION LOCATION
IN DRAWING MODULE
SECTION LOCATION AT SUBSET SHEET
DETAIL LOCATION IN
DRAWING MODULE
DETAIL LOCATION AT
SUBSET SHEET
LARGE SCALE VIEW LOCATION IN
DRAWING MODULE
LARGE SCALE VIEW
LOCATION AT SUBSET SHEET
KEYNOTE INDICATORS
SCHEDULE TYPE AIRFLOW (CUBIC FEET PER MINUTE)
EQUIPMENT TYPE
NUMERIC CHARACTER RELATES TO ITEM
ALPHANUMERIC CHARACTER RELATES
TO ASSOCIATED AIR HANDLER (OPTIONAL)
AREA LEADER
LINE LEADER
POINT LEADER
DRAWING MODULE LOCATION
(IDENTIFYING LOWER LEFT OF MULTIPLE MODULES)
REVISION CLOUD
REVISION INDICATOR
NUMERIC SCALE
SEE M-102
REFER TO ADDITIONAL
SHEET FOR CONTINUATION
FLOOR PLAN OVERLAP
BEYOND AREA
EXTENSION
PLAN
PLAN
NUMERIC CHARACTER
RELATES TO ITEM
NORTH ARROW
BEYOND AREA
EXTENSION
ALPHANUMERIC CHARACTER RELATES TO
BUILDING LEVEL (OPTIONAL)
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY
STANDARDS OF THE TRADE, AND SHALL CONFORM WITH ALL FEDERAL,
STATE, AND LOCAL CODES AND STANDARDS. THE SAME ARE MADE A
PART OF THESE CONTRACT DOCUMENTS AS IF REPEATED HEREIN.
B. CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND
DRAWINGS, AND BOTH ARE INTENDED TO BE COMPLEMENTARY.
ANYTHING APPEARING ON EITHER MUST BE EXECUTED THE SAME AS
IF SHOWN ON BOTH.
C. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS
REQUIRED TO COMPLETELY AND PROPERLY INSTALL ALL WORK
REQUIRED FOR THE PROJECT, AND SHALL EXAMINE THE SCOPE OF
WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
D. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS
POSSIBLE, HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMATICALLY
AND IN SOME CASES, ENLARGED FOR CLARITY. ANY OFFSETS,
ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE
A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE
CONTRACTOR.
E. THE ENGINEERING DRAWINGS ARE OF EQUAL IMPORTANCE WITH THE
ARCHITECTURAL DRAWINGS IN DEFINING THE WORK OF THE CONTRACT
DOCUMENTS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO CHECK WITH THE ARCHITECTURAL DRAWINGS BEFORE THE
INSTALLATION OF ENGINEERING WORK. SHOULD THERE BE A
DISCREPANCY BETWEEN THE ARCHITECTURAL DRAWINGS AND THE
ENGINEERING DRAWINGS THAT WOULD CAUSE AN AWKWARD OR
IMPROPER INSTALLATION, THE DISCREPANCY SHALL BE BROUGHT TO
THE ARCHITECTS/ENGINEERS ATTENTION FOR CLARIFICATION PRIOR TO
INSTALLATION OF SAID WORK. ANY WORK INSTALLED IN CONFLICT
WITH THE ARCHITECTURAL DRAWINGS SHALL BE CORRECTED BY THE
CONTRACTOR AT HIS EXPENSE AND AT NO ADDITIONAL COST TO THE
OWNER OR ARCHITECT/ENGINEER.
F. DO NOT SCALE THE DRAWINGS. THE DRAWINGS ARE NOT NECESSARILY
TO SCALE. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE PRIOR TO THE START OF
CONSTRUCTION. IF DISCREPANCIES ARE FOUND, THE
ARCHITECT/ENGINEER SHALL BE NOTIFIED FOR CLARIFICATION BEFORE
COMMENCING THE WORK. EXPLICIT DIMENSIONS SHALL HAVE
PRECEDENCE OVER SCALE.
G. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
BIDDING OR BEGINNING WORK ON THIS PROJECT.
H. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN.
WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE
DETERMINED, CONSULT THE ARCHITECT/ENGINEER BEFORE
PROCEEDING WITH THE WORK.
I. ANY DETAILS, SYSTEMS AND/OR MATERIALS WHICH ARE PROPOSED TO
BE CHANGED MUST FIRST BE REVIEWED BY THE OWNER AND
ARCHITECT/ENGINEER PRIOR TO THE PREPARATION OF SHOP DRAWINGS.
J. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
TEMPLATE DRAWINGS FOR ALL MECHANICAL EQUIPMENT SUPPORTS,
BOLT SETTING TEMPLATES, ISOLATORS, SPRING ISOLATION, ETC., NOT
SHOWN ON THE DRAWINGS.
K. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LOCATION OF CEILING MOUNTED MATERIALS INCLUDING ALL DIFFUSERS,
GRILLES, AND REGISTERS.
L. CONTRACTOR SHALL CLOSE ALL UNUSED OPENINGS IN EXISTING
DUCTWORK.
M. ALL DUCTWORK DESIGNATIONS REFER TO NET FREE AREA INSIDE THE
DUCTWORK.
N. VOLUME DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO
THE MAIN.
O. A MAXIMUM OF SIX FEET OF FLEXIBLE DUCTWORK MAY BE USED AT
ALL SUPPLY DIFFUSERS. BRANCH DUCTWORK TO DIFFUSER SHALL
BE SAME SIZE AS DIFFUSER INLET UNLESS SPECIFICALLY LABELED
OTHERWISE. REFER TO DIFFUSER SCHEDULE FOR INLET SIZES.
AVOID SHARP BENDS IN FLEXIBLE DUCTWORK WHICH MAY CAUSE
EXCESSIVE NOISE.
P. BRANCH DUCTWORK TO TERMINAL UNITS SHALL BE SAME SIZE AS
TERMINAL UNIT INLET UNLESS SPECIFICALLY LABELED OTHERWISE.
REFER TO TERMINAL UNIT SCHEDULE FOR INLET SIZES.
SCALE: 1/8" = 1'-0"
SA
R DAL SS
AD
M
G
24/12 24ø 24/12
HR
DTR
BF
DTS
GHR
GHS
RHG
CDHPWR
HPWS
RL
HCWR
CWS
CR
CS
RS
RD
HHR
HHS
ARV
MU
VPD
PC
BBD
LPC
MPC
HPC
LPS
MPS
HPS
F&T
(TU-12.34)
(TU-12.34)
30°20° øFSD
SD
SD
CO
TS
H
T
TS
AMS
FD
AD
PS
BDD
M
S
P
T
F
DPT
XXX-XXX
X
XX X X
X
X
X
X
X X
2
STANDOFF DAMPER FORROUND TO
RECTANGULAR DUCTWORK, LOW
PRESSURE DUCTWORK
M-000 SYMBOLS AND ABBREVIATIONS
M-001 SPECS
M-401 ENLARGED PLANS
MD100 MECHANICAL DEMOLITION
MH100 MECHANICAL DUCTWORK
MP100 MECHANICAL PIPING
M-301 SECTION AND ELEVATIONS
M-501 DETAILS
M-601 SCHEDULES
M-901 FLOW DIAGRAMS AND TEMPERATURE CONTROL DIAGRAMS
DISCIPLINE DESIGNATORS
N
WB WET BULB
CC CEILING CASSETTE ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
M000SYMBOLS ANDABBREVIATIONSNORTH ENDAPARTMENTSCARMEL, IN# DESCRIPTION DATE
07/08/21