HomeMy WebLinkAboutM131 - BUILDING MECHANICAL PLANS - BUILDING CT
T
2
M406
SG2SG2 -150
SG2SG2 -150
SG2SG2 -200
SG2SG2 -200
SG2SG2 -200
8ø
8ø
8ø
12/10 RG1
SG2SG2 -200
SG2SG2 -200
RG1
FCU-4
12/10 SG2SG2 -200
FCU-4
UNIT A4
103
UNIT A1 IDD
105
UNIT B1
107
UNIT A2 IDD
109
UNIT A2 IDD
108
UNIT B1
106
UNIT A1 IDD
104
UNIT A2 IDD
110
UNIT A2
111 UNIT A1
113
UNIT A1
112
UNIT A4
115
UNIT B2
117
UNIT B2
116
RISER ROOM
R101
MECH. ROOM
M101
ELEC. ROOM
E101
ELEC. ROOM
E102MECH. ROOM
M102 FCU-4
UH-1
SG2SG2 -200
12/10
8ø
8ø
8ø
1
1 1
2
2 2
2
2
2
2
2
2
8ø
8ø
8ø
6
3
ENTRY LOBBY
A101
6ø 4
5
5
3
45 1
M406FD
FD
UNIT A3
101
BIKE STORAGE
C009
MAIL ROOM
C010
SG2SG2 -100
2
8ø
UH-1
1
FD
RG1
FD
FD
FD ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
M131BUILDING MECHANICALPLANS -BUILDING CNORTH ENDAPARTMENTSCARMEL, INGENERAL NOTES
A REFER TO SHEET M000 FOR GENERAL MECHANICAL NOTES, SYMBOLS AND
ABBREVIATIONS.
B REFERENCE M501 SERIES FOR MECHANICAL DETAILS.
C REFERENCE M601 SERIES FOR MECHANICAL SCHEDULES.
D COORDINATE WITH STRUCTURAL AND FRAMING PLANS PRIOR TO
COMMENCING WORK. COORDINATE ALL ROUTING WITH ALL TRADES PRIOR TO
FABRICATION.
E SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND TYPES OF RATED
CONSTRUCTION TO MAINTAIN CONSTRUCTION RATING.
F THERMOSTATS TO BE 44" A.F.F. OR ALIGNED TO ADJACENT SWITCHES UNLESS
OTHERWISE NOTED.
G SEAL ALL FLOOR, CEILING, AND WALL PENETRATIONS. USE FIRE CAULK AT
RATED ASSEMBLIES AND GENERAL SEALANT ELSEWHERE. WHERE
NON-METALLIC COMPONENTS LARGER THAN 4"Ø (I.E. PVC OR CONDUIT)
PENETRATES RATED ASSEMBLIES, INSTALL INTUMESCENT COLLAR. WHERE
DUCTWORK LARGER THAN 4"Ø PENETRATES RATED ASSEMBLIES, INSTALL
FIRE DAMPER.
H SIZE AND INSTALL REFRIGERANT PIPING AND ACCESSORIES PER
MANUFACTURES RECOMMENDATIONS.
I ALL EXTERIOR VENT CAP AND VENT HOOD COLORS TO BE VERIFIED IN SHOP
DRAWINGS.
J ALL FAN COIL UNITS TO BE WALL MOUNTED UNLESS OTHERWISE INDICATED.
COORDINATE MOUNTING HEIGHT WITH OTHER DISCIPLINES AND SPACE.
K THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SIGN
ATTACHED TO THE DRYER BOX IN EACH APARTMENT. THE TAG SHALL
DOCUMENT THE ASSOCIATED INSTALLED DRYER VENT AND READ AS
FOLLOWS: CONNECTED VENT DUCT: STRAIGHT DUCT: X FEET 90 DEG. ELBOW:
COUNT=X 45 DEGREE ELBOWS: COUNT=X
L PROVIDE MECHANICAL SYSTEMS IN COMPLIANCE WITH STATE AND LOCAL
CODES.
M DRYER AND BATHROOM EXHAUST DUCTWORK TO BE MINIMUM 28 GAUGE.
N ALL HVAC SUPPLY REGISTERS, RETURN GRILLES AND DUCT TERMINATIONS
ARE TO BE PROTECTED DURING CONSTRUCTION ACTIVITIES AGAINST THE
INTRODUCTION OF DUST AND POLLUTANTS FROM ENTERING THE SYSTEM.
O ALL DUCTS ARE TO BE AIR SEALED AS PER UL181A OR UL181B.
P ALL DUCT SYSTEMS ARE TO BE TESTED IN ACCORDANCE WITH 2015 IECC
R403.3.2 THROUGH R403.3.5.
SHEET KEYNOTES
1 PROVIDE AND INSTALL RECESSED WALL MOUNTED UNIT HEATER 8-INCHES
AF.F..
2 PROVIDE CEILING RADIATION DAMPER.
3 RETURN AIR GRILLE LOW IN THE WALL DUCTED TO THE FCU.
4 OUTSIDE AIR DUCT RISER UP TO LEVEL ABOVE. PROVIDE FIRE DAMPER AT
FIRE RATED FLOOR PENETRATIONS. SEE RISER SECTION DETAIL.
5 INSTALL FCU VERTICALLY PER MANUFACTURER'S RECOMMENDATION TO
WALL PER M-501 DETAIL. ROUTE REFRIGERANT LINES THRU WALL AND UP TO
ROOF LEVEL TO CORRESPONDING CONDENSING UNIT. FIRE SEAL ANY
OPENINGS THROUGH FIRE RATED ASSEMBLIES. ROUTE CONDENSATE PVC
PIPING TO NEAREST FLOOR DRAIN.
6 RETURN AIR GRILLE HIGH IN THE WALL DUCTED TO THE FCU.
1/8" = 1'-0"
BUILDING C MECHANICAL FIRST FLOOR PLAN 1
# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021
1
1
07/08/21