HomeMy WebLinkAboutM404 - MECHANICAL ENLARGED SECTIONSFCU-4
FCU-4
RG1
RG1
FD
FD
FD
FD
5ø
6ø
55 CFM
55 CFMMIN.3' - 0"HP-1
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
HP-2
MECH. ROOM
M203
MECH. ROOM
M303
MECH. ROOM
M202
MECH. ROOM
M302
FCU-4
FCU-4
6ø
5ø
60 CFM
60 CFM MIN.3' - 0"5ø
FD
FD
FD
FD
HP-2 HP-2
LOWER LEVEL
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
LOWER LEVEL
FIRST FLOOR
SECOND FLOOR
THIRD FLOORMIN.3 ' - 0"6ø
5ø FCU-4
FCU-4
FD
FD
FD
FD
60 CFM
60 CFM ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
M404MECHANICALENLARGED SECTIONSNORTH ENDAPARTMENTSCARMEL, IN1/4" = 1'-0"
BUILDING A MECHANICAL CLOSET NORTH3
1/4" = 1'-0"
BUILDING A ENLARGED MECHANICAL CLOSET - MID2
GENERAL NOTES
A REFER TO SHEET M000 FOR GENERAL MECHANICAL NOTES, SYMBOLS AND
ABBREVIATIONS.
B REFERENCE M501 SERIES FOR MECHANICAL DETAILS.
C REFERENCE M601 SERIES FOR MECHANICAL SCHEDULES.
D COORDINATE WITH STRUCTURAL AND FRAMING PLANS PRIOR TO
COMMENCING WORK. COORDINATE ALL ROUTING WITH ALL TRADES PRIOR TO
FABRICATION.
E SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND TYPES OF RATED
CONSTRUCTION TO MAINTAIN CONSTRUCTION RATING.
F THERMOSTATS TO BE 44" A.F.F. OR ALIGNED TO ADJACENT SWITCHES UNLESS
OTHERWISE NOTED.
G SEAL ALL FLOOR, CEILING, AND WALL PENETRATIONS. USE FIRE CAULK AT
RATED ASSEMBLIES AND GENERAL SEALANT ELSEWHERE. WHERE
NON-METALLIC COMPONENTS LARGER THAN 4"Ø (I.E. PVC OR CONDUIT)
PENETRATES RATED ASSEMBLIES, INSTALL INTUMESCENT COLLAR. WHERE
DUCTWORK LARGER THAN 4"Ø PENETRATES RATED ASSEMBLIES, INSTALL
FIRE DAMPER.
H SIZE AND INSTALL REFRIGERANT PIPING AND ACCESSORIES PER
MANUFACTURES RECOMMENDATIONS.
I ALL EXTERIOR VENT CAP AND VENT HOOD COLORS TO BE VERIFIED IN SHOP
DRAWINGS.
J ALL FAN COIL UNITS TO BE WALL MOUNTED UNLESS OTHERWISE INDICATED.
COORDINATE MOUNTING HEIGHT WITH OTHER DISCIPLINES AND SPACE.
K THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SIGN
ATTACHED TO THE DRYER BOX IN EACH APARTMENT. THE TAG SHALL
DOCUMENT THE ASSOCIATED INSTALLED DRYER VENT AND READ AS
FOLLOWS: CONNECTED VENT DUCT: STRAIGHT DUCT: X FEET 90 DEG. ELBOW:
COUNT=X 45 DEGREE ELBOWS: COUNT=X
L PROVIDE MECHANICAL SYSTEMS IN COMPLIANCE WITH STATE AND LOCAL
CODES.
M DRYER AND BATHROOM EXHAUST DUCTWORK TO BE MINIMUM 28 GAUGE.
N ALL HVAC SUPPLY REGISTERS, RETURN GRILLES AND DUCT TERMINATIONS
ARE TO BE PROTECTED DURING CONSTRUCTION ACTIVITIES AGAINST THE
INTRODUCTION OF DUST AND POLLUTANTS FROM ENTERING THE SYSTEM.
O ALL DUCTS ARE TO BE AIR SEALED AS PER UL181A OR UL181B.
P ALL DUCT SYSTEMS ARE TO BE TESTED IN ACCORDANCE WITH 2015 IECC
R403.3.2 THROUGH R403.3.5.
1/4" = 1'-0"
BUILDING A ENLARGED MECHANICAL CLOSET WEST 1
# DESCRIPTION DATE
1 BID DOCUMENT 01/15/2021