HomeMy WebLinkAboutM405 - MECHANICAL ENLARGED SECTIONS10ø 10ø 12ø 12ø FD FD FD FD FCU-4 FCU-4 FCU-4 FCU-4 50 CFM 50 CFM 50 CFM 50 CFM MIN.3' - 0"MECH. ROOM M102 MECH. ROOM M202 MECH. ROOM M302 MECH. ROOM M402 FCU-4 FCU-4 FCU-4 FCU-4 FD FD FD FD FD FD FD FD FD FD FD FD 4ø 6ø 4ø 4ø 8ø 4ø 8ø MIN.3' - 0"MECH. ROOM M101 MECH. ROOM M201 MECH. ROOM M301 MECH. ROOM M401 50 CFM 50 CFM 50 CFM 50 CFM ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031 JANUARY 15, 2021 BID SET M405MECHANICALENLARGED SECTIONSNORTH ENDAPARTMENTSCARMEL, IN1/4" = 1'-0" BUILDING B ENLARGED MECHANICAL CLOSET -EAST1 1/4" = 1'-0" BUILDING B ENLARGED MECHANICAL CLOSET -WEST2 # DESCRIPTION DATE 1 BID DOCUMENT 01/15/2021 GENERAL NOTES A REFER TO SHEET M000 FOR GENERAL MECHANICAL NOTES, SYMBOLS AND ABBREVIATIONS. B REFERENCE M501 SERIES FOR MECHANICAL DETAILS. C REFERENCE M601 SERIES FOR MECHANICAL SCHEDULES. D COORDINATE WITH STRUCTURAL AND FRAMING PLANS PRIOR TO COMMENCING WORK. COORDINATE ALL ROUTING WITH ALL TRADES PRIOR TO FABRICATION. E SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND TYPES OF RATED CONSTRUCTION TO MAINTAIN CONSTRUCTION RATING. F THERMOSTATS TO BE 44" A.F.F. OR ALIGNED TO ADJACENT SWITCHES UNLESS OTHERWISE NOTED. G SEAL ALL FLOOR, CEILING, AND WALL PENETRATIONS. USE FIRE CAULK AT RATED ASSEMBLIES AND GENERAL SEALANT ELSEWHERE. WHERE NON-METALLIC COMPONENTS LARGER THAN 4"Ø (I.E. PVC OR CONDUIT) PENETRATES RATED ASSEMBLIES, INSTALL INTUMESCENT COLLAR. WHERE DUCTWORK LARGER THAN 4"Ø PENETRATES RATED ASSEMBLIES, INSTALL FIRE DAMPER. H SIZE AND INSTALL REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURES RECOMMENDATIONS. I ALL EXTERIOR VENT CAP AND VENT HOOD COLORS TO BE VERIFIED IN SHOP DRAWINGS. J ALL FAN COIL UNITS TO BE WALL MOUNTED UNLESS OTHERWISE INDICATED. COORDINATE MOUNTING HEIGHT WITH OTHER DISCIPLINES AND SPACE. K THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A SIGN ATTACHED TO THE DRYER BOX IN EACH APARTMENT. THE TAG SHALL DOCUMENT THE ASSOCIATED INSTALLED DRYER VENT AND READ AS FOLLOWS: CONNECTED VENT DUCT: STRAIGHT DUCT: X FEET 90 DEG. ELBOW: COUNT=X 45 DEGREE ELBOWS: COUNT=X L PROVIDE MECHANICAL SYSTEMS IN COMPLIANCE WITH STATE AND LOCAL CODES. M DRYER AND BATHROOM EXHAUST DUCTWORK TO BE MINIMUM 28 GAUGE. N ALL HVAC SUPPLY REGISTERS, RETURN GRILLES AND DUCT TERMINATIONS ARE TO BE PROTECTED DURING CONSTRUCTION ACTIVITIES AGAINST THE INTRODUCTION OF DUST AND POLLUTANTS FROM ENTERING THE SYSTEM. O ALL DUCTS ARE TO BE AIR SEALED AS PER UL181A OR UL181B. P ALL DUCT SYSTEMS ARE TO BE TESTED IN ACCORDANCE WITH 2015 IECC R403.3.2 THROUGH R403.3.5. 1 07/08/21