HomeMy WebLinkAboutM501 - MECHANICAL DETAILSFINISHED
INTERIOR MIN.
32" SQUARE
DOOR MIN. 30"
WATER
HEATER PAN
WATER HEATER
MECHANICAL
EQUIPMENT
PLENUM
CLEARANCE
CPVC CONDENSATE DRAIN
W/ TRAP; ROUTE TO HUB
DRAIN WITH AIR GAP
MAIN SHUT-OFF
WATER HEATER
PAN
SLEEVE
FLEX
CONN.
FIRE DAMPER SIMILAR TO
RUSKIN CFD7
FAN
COIL
WATER HEATER
HW CW
VALVE
SIDE VIEW
TOP VIEW
NOTE: TYPICAL CONDITION SHOWN FOR UNITS, REFER
TO MECHANICAL AND PLUMBING FLOOR PLANS FOR
ADDITIONAL REQUIREMENTS.
CEILING
RADIATION
DAMPER (TYP.)
MIN. 20"
REFRIGERANT SUCTION /
LIQUID; ROUTE TO
CONDENSING UNIT
METAL SHELF
RETURN AIR GRILLE,
SEE PLANS
SECURE AIR HANDLER TO
WALL WITH Z PANEL CLIPS /
HANGERS AND ANGLE
BRACKETS
10"X10" ACCESS PANEL
NOTES:
1. ROUTE CONDENSATE PIPING (SIZE PER
MANUFACTURER) TO HUB DRAIN.
2. REFER TO REFRIGERANT PIPING DETAIL ON
MECHANICAL DETAIL SHEET FOR ASSOCIATED
REQUIREMENTS.
3. REFER TO STRUTURAL UNIT PLAN DRAWINGS FOR
ACTUAL CONDITION AT EACH CLOSET. HARD DUCT
MAIN ALWAYS ROUTES PARALLEL TO JOISTS.
4. COORDINATE HARD DUCT ELEVATION AT JOIST
SPACE WITH FIRE AND PLUMBING PIPING PRIOR TO
INSTALLATION.
5. FIRESTOP ALL PENETRATIONS AT CEILING AND
FLOOR.
6. WOOD SHELF/DRYWALL DIVIDER CAN BE OMITEED
IF ALL MATERIALS CONTAINED WITHIN MECHANICAL
CLOSET HAVE A FLAME SPREAD INDEX OF NOT
MORE THAN 25 AND A SMOKE DEVELOPED INDEX
OF NOT MORE THAN 50 WHEN TESTED IN
ACCORDANCE WITH ASTM E 84 OR UL 723.
FINISHED
INTERIOR MIN.
32" SQUARE
DOOR MIN. 30"MECHANICAL
EQUIPMENT
PLENUM
CLEARANCE
CPVC CONDENSATE
DRAIN; ROUTE TO HUB
DRAIN
FLEX CONN.
DUCT
FIRE DAMPER
W/ACCESS PANEL
FAN
COIL
SIDE VIEW
TOP VIEW
NOTE: TYPICAL CONDITION SHOWN FOR UNITS, REFER TO
MECHANICAL AND PLUMBING FLOOR PLANS FOR
ADDITIONAL REQUIREMENTS.
CEILING
RADIATION
DAMPER (TYP.)
MIN. 20"
NOTES:
1. ROUTE CONDENSATE PIPING (SIZE PER
MANUFACTURER) TO HUB DRAIN.
2. REFER TO REFRIGERANT PIPING DETAIL
ON MECHANICAL DETAIL SHEET FOR
ASSOCIATED REQUIREMENTS.
3. REFER TO STRUTURAL UNIT PLAN
DRAWINGS FOR ACTUAL CONDITION AT
EACH CLOSET. HARD DUCT MAIN ALWAYS
ROUTES PARALLEL TO JOISTS.
4. COORDINATE HARD DUCT ELEVATION AT
JOIST SPACE WITH FIRE AND PLUMBING
PIPING PRIOR TO INSTALLATION.
5. FIRESTOP ALL PENETRATIONS AT CEILING
AND FLOOR AND THROUGH AHU
SUPPORT.
6. ALL MATERIALS CONTAINED WITHIN
MECHANICAL CLOSET HAVE A FLAME
SPREAD INDEX OF NOT MORE THAN 25
AND A SMOKE DEVELOPED INDEX OF NOT
MORE THAN 50 WHEN TESTED IN
ACCORDANCE WITH ASTM E 84 OR UL 723.
REFRIGERANT SUCTION / LIQUID;
ROUTE TO CONDENSING UNIT
RETURN GRILLE, SEE
PLANS
10" X 10"
ACCESS PANEL
R.A.
DUCT
WALL MOUNT
EQUIPMENT
OUTSIDE AIR
CONNECTIONRSRLEVAPORATOR COIL
THERMAL EXPANSION VALVE
SIGHTGLASS
REFER TO AIR COOLED
CONDENSING UNIT SCHEDULE
FOR REFRIGERANT LINE SIZES
AIR COOLED CONDENSING UNIT
WITH FACTORY INSTALLED:
1. LIQUID LINE FILTER DRIER
2. SUCTION AND DISCHARGE
LINE REFRIGERATION
CHARGING CONNECTIONS
FIELD BRAZED
CONNECTIONS
ISOLATION VALVE, TYP.
WALL
WALL
PULL OUT DOOR
DRYER BOX
FLOOR
4"Ø ALUMINUM OR FOIL
FLEX DUCT TO DRYER
4"Ø RIGID DUCT
SECONDARY LENT
TRAP IN VERTICAL
DUCT RISER
CAULK AROUND DUCT PENETRATION.
RIGID DUCT UP WALL
WALL EXHAUST FAN,
SEE PLANS
WALL
CAULK/SEAL
LINESET (1 PER SLEEVE)
3" MIN.
FIRECAULK (INSIDE AND
OUTSIDE SLEEVE)
3" METAL SLEEVE 20 GA
MIN. TAPE CUT ENDS
(TO PREVENT SHARP
EDGES)
FLOOR
ASSEMBLY
SUBFLOOR
WOOD TRUSS CEILING
ASSEMBLYFIRECAULK (INSIDE AND
OUTSIDE PIPE)
8"
MIN.2"2"GENERAL NOTES:
1. DO NOT INSTALL IN CORNERS
2. SLEEVES AT TOP FLOOR CEILING ROD
3. SLEEVES TO BE FASTENED IN PLACE
BEFORE DRYWALL / LINESET INSTALL
4. MIN 8" FROM SIDEWALL AND 4" FROM BACK
WALL.
16GA. GALV. DISCHARGE PLENUM
STORM COLLAR SECURED
& CAULKED TO DUCT
CURB BY G.C.
CURB CAP-SECURE TO
DUCT & CAULK WATER TIGHT
SEE PLAN FOR DUCT CONT.
COVER OPENING WITH
1/2"x1/2" MESH HARDWARE
HOLE THRU ROOF TO BE 1"
LARGER THAN DUCT (BOTH WAYS)36"(PRIMARY) CONDENSATE DRAIN WITH
VENTED P-TRAP. TYPICAL ALL UNITS.
PROVIDE VENT @ TOP
OF CONDENSATE
3/4"
3/4"
FIFTH FLOOR
CEILING
FCU
CEILING
FLOOR PENETRATIONS TO BE FIRE
RATED TYPICAL ALL UNITS.
3/4"
3/4"
FOURTH FLOOR
FCU
CEILING
3/4"
3/4"
THIRD FLOOR
FCU
CEILING
3/4"
3/4"
SECOND FLOOR
FCU
CEILING
NOTE:
CONDENSATE PIPING IN PLENUM
TO BE COPPER. ALL WIRING AND
PIPING TO BE PLENUM RATED.
INSTALL BOT. OF UNIT NOM. 7"
ABOVE CEILING, SAME AT ALL
LOCATIONS
EXH. VENT TERMINATION, SEE PLANS
CAULK/SEAL
WALL FLANGE & WATER -TIGHT SEAL
REFER TO ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION ARCHITECTCLIENT GC/CM PROJECT DRAWING TITLE SEAL SHEET PROJECT INFO REVISIONS20031
JANUARY 15, 2021
BID SET
M501MECHANICAL DETAILS NORTH ENDAPARTMENTSCARMEL, IN12" = 1'-0"
MECHANICAL ROOM DETAIL 1
12" = 1'-0"
MECHANICAL ROOM DETAIL (CORRIDOR)2
12" = 1'-0"
REFRIGERATION PIPING DETAIL3
12" = 1'-0"
VERTICAL DRYER EXHAUST DUCT DETAIL4
12" = 1'-0"
WALL MOUNTED BATH EXHAUST FAN DETAIL5
12" = 1'-0"
LINESET SLEEVE DETAIL 6
12" = 1'-0"
LINESET HOOD DETAIL TO SIDE WALL7
12" = 1'-0"
GOOSENECK DETAIL8
12" = 1'-0"
CONDENSING UNIT DETAIL 10
12" = 1'-0"
AIR HANDLING UNIT RISER DIAGRAM9
12" = 1'-0"
VENT TERMINAL DETAIL11
6" = 1'-0"
PENTHOUSE ELEVATOR VENT12
# DESCRIPTION DATE
07/08/21