Loading...
HomeMy WebLinkAboutDelta Faucet System 2 Project 29632 SLD.pdfDelta Faucet - Meter 321-139-232 55 111th St. E. - Indianapolis, IN 46280 DRAWN BY CHECKED DATE SCALE SHEET NO. D. McClellan 12-6-2021 N/A 1 Duke Meter # 321-139-232 Duke Utility Delta Faucet (350kW AC [407.1kW DC] Total Solar Production) Meter 321-139-232 Account #37403050017 55 111th St. E. Indianapolis, IN 46280 AC Disconnect (1) 600A Outdoor 3-phase Disconnect (Located outside of building within 10 ft of the meter line of site) Or equivalent total amperage in 2 or 3 disconnects per disconnect availability 480/277V 3-Phase 1200A Switch-gear Panel with (1) 600A Breaker or appropriate ampacity per disconnect if mutiple disconnects used. (885) Bluesun 460 Watt BSM460M-72HBD Solar Panels (Panel Count 885) 350kW Total Production (5) Growatt MAC 70KTL3-X MV Grid-Support PV Inverter 5/8" x 8' Copper Ground Rod PV - 10AWG Copper Wire L1 L2 L3 L1 L2 L3 Facility Loads PE - 6AWG Copper Wire PE PE 2x500 MCM Copper Wire (380A, 75C 430A, 90C ampacity minimum PER CONDUCTOR or appropriate ampacity if split among multiple disconnects) 1200A minimum Switchgear with (1) 600A Breaker 2AWG Copper Wire 115A, 75C 130A, 90C ampacity minimum per inverter (System 2) AC Combiner 2x500 MCM Copper Wire (380A, 75C 430A, 90C ampacity minimum PER CONDUCTOR or appropriate ampacity if split among multiple disconnects) L1 L2 L3 PE