HomeMy WebLinkAboutDelta Faucet System 3 Project 29602 SLD.pdfDelta Faucet - Meter 321-143-149
55 111th St. E. - Indianapolis, IN 46280
DRAWN BY CHECKED DATE SCALE SHEET NO.
D.
McClellan 12-6-2021 N/A 1
Duke
Meter # 321-143-149
Duke
Utility
Delta Faucet (70kW AC [69kW DC] Total Solar Production)
Meter 321-143-149
Account #6740305001
55 111th St. E.
Indianapolis, IN 46280
AC Disconnect
(1) 115A Minimum Outdoor
3-phase Disconnect
(Located outside of building
within 10 ft of the meter line of site)
480/277V 3-Phase
1400A
Switch-gear Panel
with (1) 110A Breaker
(150) Bluesun 460 Watt
BSM460M-72HBD
Solar Panels
(Panel Quantity 150)
70kW Total Production
(1) Growatt MAC 70KTL3-X MV
Grid-Support PV Inverter
5/8" x 8' Copper
Ground Rod
PV - 10AWG Copper Wire
L1
L2
L3
L1
L2
L3 Facility Loads
PE - 6AWG Copper Wire PE
PE
1400A minimum
Switchgear
with (3) 400A
Breakers
(System 3)
2AWG
Copper Wire
115A, 75C
130A, 90C
ampacity
minimum
per inverter
2AWG
Copper Wire
115A, 75C
130A, 90C
ampacity
minimum
per inverter