Loading...
HomeMy WebLinkAboutDelta Faucet System 3 Project 29602 SLD.pdfDelta Faucet - Meter 321-143-149 55 111th St. E. - Indianapolis, IN 46280 DRAWN BY CHECKED DATE SCALE SHEET NO. D. McClellan 12-6-2021 N/A 1 Duke Meter # 321-143-149 Duke Utility Delta Faucet (70kW AC [69kW DC] Total Solar Production) Meter 321-143-149 Account #6740305001 55 111th St. E. Indianapolis, IN 46280 AC Disconnect (1) 115A Minimum Outdoor 3-phase Disconnect (Located outside of building within 10 ft of the meter line of site) 480/277V 3-Phase 1400A Switch-gear Panel with (1) 110A Breaker (150) Bluesun 460 Watt BSM460M-72HBD Solar Panels (Panel Quantity 150) 70kW Total Production (1) Growatt MAC 70KTL3-X MV Grid-Support PV Inverter 5/8" x 8' Copper Ground Rod PV - 10AWG Copper Wire L1 L2 L3 L1 L2 L3 Facility Loads PE - 6AWG Copper Wire PE PE 1400A minimum Switchgear with (3) 400A Breakers (System 3) 2AWG Copper Wire 115A, 75C 130A, 90C ampacity minimum per inverter 2AWG Copper Wire 115A, 75C 130A, 90C ampacity minimum per inverter