HomeMy WebLinkAboutM003.0 - TRUSS SEALS16023 Swingley Ridge Rd Chesterfield, MO 63017 314-434-1200 MiTek USA, Inc. RE: Design Code: IBC2018/TPI2014 Wind Code: ASCE 7-16 Wind Speed: 115 mph Roof Load: 40.0 psf Design Program: MiTek 20/20 8.5 1 of 1 This package includes 29 individual, dated Truss Design Drawings and 0 Additional Drawings. General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special Loading Conditions): Floor Load: N/A psf November 16, 2021 Liu, Xuegang The truss drawing(s) referenced above have been prepared by MiTek USA, Inc under my direct supervision based on the parameters provided by 84 Components - 0783. Truss Design Engineer's Name: Liu, XuegangMy license renewal date for the state of Indiana is July 31, 2022. 2200684-2200684A TG41 IMPORTANT NOTE: The seal on these truss component designs is a certification that the engineer named is licensed in the jurisdiction(s) identified and that the designs comply with ANSI/TPI 1. These designs are based upon parameters shown (e.g., loads, supports, dimensions, shapes and design codes), which were given to MiTek. Any project specific information included is for MiTek customers file reference purpose only, and was not taken into account in the preparation of these designs. MiTek has not independently verified the applicability of the designparameters or the designs for any particular building. Before use, the building designer should verify applicability of design parameters and properly incorporate these designs into the overall building design per ANSI/TPI 1, Chapter 2. Site Information: Lot/Block: 41Customer: Pyatt Builders Project Name: 2200684-2200684A Subdivision: The Grove at LegacyAddress: State: IndianaCity: Model: Tribeca No. Seal# Truss Name Date 1 I48803332 A01 11/16/2021 2 I48803333 A02 11/16/2021 3 I48803334 A03 11/16/2021 4 I48803335 B01 11/16/2021 5 I48803336 B02 11/16/2021 6 I48803337 B03 11/16/2021 7 I48803338 B04 11/16/2021 8 I48803339 B05 11/16/2021 9 I48803340 C01 11/16/2021 10 I48803341 CJ01 11/16/2021 11 I48803342 CJ02 11/16/2021 12 I48803343 J01 11/16/2021 13 I48803344 J02 11/16/2021 14 I48803345 J03 11/16/2021 15 I48803346 J04 11/16/2021 16 I48803347 J05 11/16/2021 17 I48803348 M01 11/16/2021 18 I48803349 M02 11/16/2021 19 I48803350 M03 11/16/2021 20 I48803351 M04 11/16/2021 No. Seal# Truss Name Date 21 I48803352 M05 11/16/2021 22 I48803353 M06 11/16/2021 23 I48803354 M07 11/16/2021 24 I48803355 M08 11/16/2021 25 I48803356 M09 11/16/2021 26 I48803357 MG01 11/16/2021 27 I48803358 V01 11/16/2021 28 I48803359 V02 11/16/2021 29 I48803360 V03 11/16/2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss A01 Truss Type GABLE Qty 1 Ply 2 TG41 Job Reference (optional) I48803332 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:00 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-z2?U9M?_p_UMLOjQlH2?H38J7T0BCNp8efFojHyIzZr Scale = 1:37.8 1 2 3 4 5 6 9 8 7 20 21 22 23 24 25 26 27 28 29 30 31 4x4 3x4 8x8 4x4 4x4 4x8 3x4 3x4 1.5x4 1.5x4 1.5x4 1.5x4 NAILED NAILED NAILED NAILED NAILED JUS24 JUS24 JUS24 JUS24 5-4-25-4-2 9-11-04-6-14 14-5-144-6-14 19-10-05-4-2 -0-11-0 0-11-0 5-4-2 5-4-2 9-11-0 4-6-14 14-5-14 4-6-14 19-10-0 5-4-2 0-5-85-5-00-5-86.00 12 Plate Offsets (X,Y)-- [6:0-2-11,0-0-14], [8:0-4-0,0-4-8] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.24 0.35 0.29 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.06 -0.12 0.02 0.04 (loc) 7-8 7-8 6 7-8 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 202 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x6 SP 2400F 2.0E WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)6=0-3-8, 2=0-3-8 Max Horz 2=73(LC 14) Max Uplift 6=-257(LC 15), 2=-232(LC 14) Max Grav 6=3150(LC 2), 2=1942(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-3624/530, 3-4=-3022/435, 4-5=-3024/436, 5-6=-5291/561 BOT CHORD 2-9=-423/3186, 8-9=-423/3186, 7-8=-452/4700, 6-7=-452/4700 WEBS 4-8=-280/2387, 5-8=-2409/218, 5-7=-64/1942, 3-8=-687/189, 3-9=-40/331 NOTES- 1) 2-ply truss to be connected together with 10d (0.131"x3") nails as follows: Top chords connected as follows: 2x4 - 1 row at 0-7-0 oc. Bottom chords connected as follows: 2x6 - 2 rows staggered at 0-9-0 oc. Webs connected as follows: 2x4 - 1 row at 0-9-0 oc. 2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated. 3) Unbalanced roof live loads have been considered for this design. 4) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 6-11-0, Exterior(2R) 6-11-0 to 12-11-0, Interior(1) 12-11-0 to 16-10-0, Exterior(2E) 16-10-0 to 19-10-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 5) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 6) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 7) Unbalanced snow loads have been considered for this design. 8) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 9) Gable studs spaced at 1-4-0 oc. 10) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 11) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 12) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb) 6=257, 2=232. Continued on page 2 November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss A01 Truss Type GABLE Qty 1 Ply 2 TG41 Job Reference (optional) I48803332 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:00 2021 Page 2 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-z2?U9M?_p_UMLOjQlH2?H38J7T0BCNp8efFojHyIzZr NOTES- 13) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. 14) Use MiTek JUS24 (With 4-10d nails into Girder & 2-10d nails into Truss) or equivalent spaced at 2-0-0 oc max. starting at 12-0-12 from the left end to 18-0-12 to connect truss(es) to front face of bottom chord. 15) Fill all nail holes where hanger is in contact with lumber. 16) "NAILED" indicates 3-10d Nails (0.148" x 3") toe-nails per NDS guidelines. 17) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 95 lb down and 34 lb up at 10-0-12 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. LOAD CASE(S) Standard 1) Dead + Snow (balanced): Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-4=-51, 4-6=-51, 14-17=-20 Concentrated Loads (lb) Vert: 8=-196(F=-119) 25=-196(F) 26=-119(F) 27=-119(F) 28=-616(F) 29=-616(F) 30=-616(F) 31=-616(F) 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss A02 Truss Type Common Qty 8 Ply 1 TG41 Job Reference (optional) I48803333 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:01 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-RFYsMi0caHcDzYIdI_ZEpGhUltIGxstItJ_MFkyIzZq Scale = 1:35.6 1 2 3 4 5 6 7 8 15 16 17 18 19 20 4x4 6x8 4x4 1.5x4 1.5x4 4x4 9-11-09-11-0 19-10-09-11-0 -0-11-0 0-11-0 5-9-6 5-9-6 9-11-0 4-1-10 14-0-10 4-1-10 19-10-0 5-9-6 20-9-0 0-11-0 0-5-85-5-00-5-86.00 12 Plate Offsets (X,Y)-- [2:0-1-11,0-2-0], [6:0-1-11,0-2-0], [8:0-4-0,0-3-4] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.24 0.61 0.18 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.14 -0.30 0.02 0.03 (loc) 8-11 8-11 6 8-11 l/defl >999 >786 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 67 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF 1650F 1.5E WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-3-8, 6=0-3-8 Max Horz 2=67(LC 14) Max Uplift 2=-59(LC 14), 6=-59(LC 15) Max Grav 2=848(LC 2), 6=848(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-1280/192, 3-4=-974/146, 4-5=-974/146, 5-6=-1280/192 BOT CHORD 2-8=-94/1089, 6-8=-94/1089 WEBS 4-8=-27/606, 5-8=-376/138, 3-8=-376/138 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 6-11-0, Exterior(2R) 6-11-0 to 12-11-0, Interior(1) 12-11-0 to 17-9-0, Exterior(2E) 17-9-0 to 20-9-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 6. 9) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss A03 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803334 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:03 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-NdgdnO1s6vsxCsR?QPcivhmseg7LPoVbKdTTKcyIzZo Scale = 1:36.5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 26 25 24 23 22 21 20 19 18 17 16 27 28 29 30 4x4 3x4 6x6 3x4 19-10-019-10-0 -0-11-0 0-11-0 9-11-0 9-11-0 19-10-0 9-11-0 20-9-0 0-11-0 0-5-85-5-00-5-86.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-SH 0.09 0.06 0.04 DEFL. Vert(LL) Vert(CT) Horz(CT) in 0.00 0.00 0.00 (loc) 15 15 14 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 89 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 19-10-0. (lb) - Max Horz 2=67(LC 14) Max Uplift All uplift 100 lb or less at joint(s) 2, 22, 23, 24, 25, 26, 14, 20, 19, 18, 17, 16 Max Grav All reactions 250 lb or less at joint(s) 2, 21, 22, 23, 24, 25, 14, 20, 19, 18, 17 except 26=251(LC 34), 16=251(LC 35) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) -0-11-0 to 2-1-0, Exterior(2N) 2-1-0 to 6-11-0, Corner(3R) 6-11-0 to 12-11-0 , Exterior(2N) 12-11-0 to 17-9-0, Corner(3E) 17-9-0 to 20-9-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 5) Unbalanced snow loads have been considered for this design. 6) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 7) All plates are 1.5x4 MT20 unless otherwise indicated. 8) Gable requires continuous bottom chord bearing. 9) Gable studs spaced at 1-4-0 oc. 10) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 11) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 12) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 22, 23, 24, 25, 26, 14, 20, 19, 18, 17, 16. 13) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss B01 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803335 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:04 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-rpE??k2VtC_oq?0C_77xRvJ?w4Oh8DskZHD0s2yIzZn Scale = 1:42.3 1 2 3 4 5 6 7 12 11 10 9 8 30 31 32 33 6x6 6x8 4x4 4x6 9-0-09-0-0 9-4-00-4-0 18-0-08-8-0 -0-11-0 0-11-0 4-6-5 4-6-5 9-0-0 4-5-11 13-5-11 4-5-11 18-0-0 4-6-5 18-11-0 0-11-0 0-7-56-7-50-7-58.00 12 Plate Offsets (X,Y)-- [2:Edge,0-2-15] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.25 0.37 0.16 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.11 -0.22 0.01 0.01 (loc) 12-26 12-26 2 12-26 l/defl >999 >497 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 93 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF 1650F 1.5E WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 8-11-8 except (jt=length) 2=0-3-8. (lb) - Max Horz 2=-121(LC 10) Max Uplift All uplift 100 lb or less at joint(s) 2, 12, 6, 11, 9, 8 Max Grav All reactions 250 lb or less at joint(s) 10, 9, 8 except 2=425(LC 30), 12=705(LC 2), 12=612(LC 1), 6=359(LC 31), 6=303(LC 1) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-356/20, 5-6=-348/39 BOT CHORD 2-12=-32/308 WEBS 5-12=-261/144, 3-12=-299/132 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 6-0-0, Exterior(2R) 6-0-0 to 12-0-0, Interior(1) 12-0-0 to 15-11-0, Exterior(2E) 15-11-0 to 18-11-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) All plates are 1.5x4 MT20 unless otherwise indicated. 7) Gable studs spaced at 1-4-0 oc. 8) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 9) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 12, 6, 11, 9, 8, 6. 11) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1.November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss B02 Truss Type Common Qty 12 Ply 1 TG41 Job Reference (optional) I48803336 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:06 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-nCMlQQ4lPqEV3JAa5X9PWKOLiu2?c7c10ai7wxyIzZl Scale = 1:41.3 1 2 3 4 5 6 7 8 15 16 17 18 6x6 6x8 4x4 1.5x4 1.5x4 6x6 9-0-09-0-0 18-0-09-0-0 -0-11-0 0-11-0 4-6-5 4-6-5 9-0-0 4-5-11 13-5-11 4-5-11 18-0-0 4-6-5 18-11-0 0-11-0 0-7-56-7-50-7-58.00 12 Plate Offsets (X,Y)-- [2:Edge,0-3-3], [6:Edge,0-3-3] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.17 0.45 0.14 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.09 -0.17 0.02 0.01 (loc) 8-11 8-11 6 8-11 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 68 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF 1650F 1.5E WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-3-8, 6=0-3-8 Max Horz 2=-121(LC 10) Max Uplift 2=-48(LC 12), 6=-48(LC 13) Max Grav 2=775(LC 2), 6=775(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-953/92, 3-4=-732/80, 4-5=-732/80, 5-6=-953/92 BOT CHORD 2-8=-76/747, 6-8=-6/747 WEBS 4-8=0/506, 5-8=-266/131, 3-8=-266/131 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 6-0-0, Exterior(2R) 6-0-0 to 12-0-0, Interior(1) 12-0-0 to 15-11-0, Exterior(2E) 15-11-0 to 18-11-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 6. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss B03 Truss Type Roof Special Qty 4 Ply 1 TG41 Job Reference (optional) I48803337 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:07 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-GOw7dm5NA7MMhTlmfFge3XxQkHFCLSwAFERgTNyIzZk Scale = 1:43.8 1 2 3 4 5 6 7 8 9 17 16 15 1211 10 14 13 26 27 28 4x6 1.5x4 3x4 4x8 6x8 3x4 1.5x4 1.5x4 6x6 6x6 3x4 6x10 4x8 6x8 1.5x4 1.5x4 3x4 1-11-131-11-13 3-11-01-11-3 7-3-03-4-0 9-0-01-9-0 18-0-09-0-0 -0-11-0 0-11-0 1-11-13 1-11-13 3-11-0 1-11-3 7-3-0 3-4-0 9-0-0 1-9-0 13-5-11 4-5-11 18-0-0 4-6-5 18-11-0 0-11-0 0-7-56-7-50-7-52-0-08.00 12 Plate Offsets (X,Y)-- [4:0-2-0,0-1-12], [8:Edge,0-3-3], [13:0-2-8,0-3-4], [14:0-6-12,0-2-4] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.53 0.96 0.65 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.19 -0.39 0.30 0.13 (loc) 15 15 8 15 l/defl >999 >557 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 98 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF No.2 *Except* 2-15,8-12: 2x4 SPF 1650F 1.5E, 13-14: 2x6 SP 2400F 2.0E WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 2-11-12 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing, Except: 6-0-0 oc bracing: 10-11. 6-0-0 oc bracing: 11-13 8-6-0 oc bracing: 14-16 JOINTS 1 Brace at Jt(s): 13, 14 REACTIONS. (size)2=0-3-8, 8=0-3-8 Max Horz 2=-121(LC 10) Max Uplift 2=-42(LC 12), 8=-45(LC 13) Max Grav 2=786(LC 2), 8=780(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-970/37, 3-4=-3938/250, 4-5=-1290/61, 5-6=-1249/111, 6-7=-738/77, 7-8=-962/89 BOT CHORD 2-17=-74/795, 8-10=-3/755, 4-14=-101/1929, 13-14=-220/3260 WEBS 3-17=-823/96, 14-17=-84/844, 4-13=-2236/216, 10-13=0/871, 6-13=-94/1324, 6-10=-397/51, 7-10=-270/129, 3-14=-161/2659 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 1-10-7, Interior(1) 1-10-7 to 6-0-0, Exterior(2R) 6-0-0 to 12-0-0, Interior(1) 12-0-0 to 15-11-0, Exterior(2E) 15-11-0 to 18-11-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 8. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss B04 Truss Type Common Qty 5 Ply 1 TG41 Job Reference (optional) I48803338 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:08 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-kbUWq55?xRUDIdKzDyBtclUh6hjR412KUuBD?qyIzZj Scale = 1:40.8 1 2 3 4 5 6 7 14 15 16 17 6x8 4x4 1.5x4 1.5x4 6x6 6x6 9-0-09-0-0 18-0-09-0-0 4-6-5 4-6-5 9-0-0 4-5-11 13-5-11 4-5-11 18-0-0 4-6-5 18-11-0 0-11-0 0-7-56-7-50-7-58.00 12 Plate Offsets (X,Y)-- [1:Edge,0-2-15], [5:Edge,0-2-15] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MSH 0.17 0.45 0.15 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.09 -0.18 0.02 0.02 (loc) 7-10 7-10 5 7-10 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 67 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF 1650F 1.5E WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)1=Mechanical, 5=0-3-8 Max Horz 1=-118(LC 10) Max Uplift 1=-33(LC 12), 5=-48(LC 13) Max Grav 1=719(LC 2), 5=776(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 1-2=-959/94, 2-3=-735/81, 3-4=-735/81, 4-5=-956/93 BOT CHORD 1-7=-78/753, 5-7=-7/749 WEBS 3-7=0/507, 4-7=-266/131, 2-7=-271/132 NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) 0-0-0 to 3-0-0, Interior(1) 3-0-0 to 6-0-0, Exterior(2R) 6-0-0 to 12-0-0, Interior(1) 12-0-0 to 15-11-0, Exterior(2E) 15-11-0 to 18-11-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5. 9) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss B05 Truss Type Common Supported Gable Qty 1 Ply 1 TG41 Job Reference (optional) I48803339 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:10 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-gzbGFn7FS2kxYwULKNELhAZ3MVWBYygdxCgK4iyIzZh Scale = 1:41.4 1 2 3 4 5 6 7 8 9 10 17 16 15 14 13 12 11 18 4x4 6x6 4x6 4x6 18-0-018-0-0 9-0-0 9-0-0 18-0-0 9-0-0 18-11-0 0-11-0 0-7-56-7-50-7-58.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-SH 0.06 0.05 0.08 DEFL. Vert(LL) Vert(CT) Horz(CT) in 0.00 0.00 0.00 (loc) 9 10 9 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 78 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF 1650F 1.5E OTHERS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 18-0-0. (lb) - Max Horz 1=-119(LC 10) Max Uplift All uplift 100 lb or less at joint(s) 15, 16, 17, 13, 12, 11, 1 Max Grav All reactions 250 lb or less at joint(s) 14, 15, 16, 13, 12, 11, 1, 9 except 17=256(LC 24) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) 0-0-0 to 3-0-0, Exterior(2N) 3-0-0 to 6-0-0, Corner(3R) 6-0-0 to 12-0-0, Exterior(2N) 12-0-0 to 15-11-0, Corner(3E) 15-11-0 to 18-11-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) All plates are 1.5x4 MT20 unless otherwise indicated. 7) Gable requires continuous bottom chord bearing. 8) Gable studs spaced at 2-0-0 oc. 9) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 10) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 11) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 15, 16, 17, 13, 12, 11, 1. 12) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss C01 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803340 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:11 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-8A9eT78uDMso942Yu5laDN6DtvsGHPomAsPuc9yIzZg Scale = 1:24.3 1 2 3 4 5 6 7 8 9 14 13 12 11 101516 4x4 4x4 4x4 NAILED NAILED NAILED NAILED 9-4-09-4-0 -0-11-0 0-11-0 4-8-0 4-8-0 9-4-0 4-8-0 10-3-0 0-11-0 0-7-53-8-100-7-58.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.07 0.06 0.02 DEFL. Vert(LL) Vert(CT) Horz(CT) in 0.00 -0.00 0.00 (loc) 8 8 8 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 39 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 OTHERS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 , Right: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 9-4-0. (lb) - Max Horz 2=68(LC 11) Max Uplift All uplift 100 lb or less at joint(s) 2, 8, 12, 13, 14, 11, 10 Max Grav All reactions 250 lb or less at joint(s) 2, 8, 12, 13, 14, 11, 10 FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) -0-11-0 to 2-0-0, Corner(3R) 2-0-0 to 7-4-0, Corner(3E) 7-4-0 to 10-3-0 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 4) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) All plates are 1.5x4 MT20 unless otherwise indicated. 7) Gable requires continuous bottom chord bearing. 8) Gable studs spaced at 1-4-0 oc. 9) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 10) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 11) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 8, 12, 13, 14, 11, 10. 12) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. 13) "NAILED" indicates 3-10d Nails (0.148" x 3") toe-nails per NDS guidelines. 14) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). LOAD CASE(S) Standard Continued on page 2 November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss C01 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803340 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:12 2021 Page 2 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-cMj0gT8W_g_fnEdkSoGpmbeOdIBV0s2vOW9R8byIzZf LOAD CASE(S) Standard 1) Dead + Snow (balanced): Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-5=-51, 5-9=-51, 2-8=-20 Concentrated Loads (lb) Vert: 14=-96(B) 10=-96(B) 15=-96(B) 16=-96(B) 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss CJ01 Truss Type Roof Special Girder Qty 1 Ply 1 TG41 Job Reference (optional) I48803341 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:13 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-4YHPup98lz6WPOCw?Wn2JoBVRiVxlJb3dAu_g1yIzZe Scale = 1:14.4 1 2 3 4 8 9 10 11 12 1.5x4 3x6 3x4 3x4 NAILED NAILED NAILED NAILED 5-11-125-11-5 -1-5-10 1-5-10 5-11-12 5-11-12 0-4-101-11-51-7-120-3-81-11-53.12 12 Plate Offsets (X,Y)-- [2:0-2-3,0-1-8], [4:0-2-0,0-0-0] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.33 0.17 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.02 -0.04 0.00 0.01 (loc) 4-7 4-7 2 4-7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 24 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x6 SP 2400F 2.0E WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 5-11-12 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-1-14, 4=0-1-8 Max Horz 2=52(LC 13) Max Uplift 2=-71(LC 10), 4=-24(LC 14) Max Grav 2=373(LC 21), 4=267(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3) -1-5-10 to 2-9-5, Exterior(2R) 2-9-5 to 5-10-1 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10; Min. flat roof snow load governs. 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2, 4. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. 11) "NAILED" indicates 3-10d skew 45 to 135 degrees (0.148" x 3") toe-nails per NDS guidelines. 12) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). LOAD CASE(S) Standard 1) Dead + Snow (balanced): Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-3=-51, 4-5=-20 Concentrated Loads (lb) Vert: 11=-11(B) 12=-6(F)November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss CJ02 Truss Type Jack-Open Girder Qty 1 Ply 1 TG41 Job Reference (optional) I48803342 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:14 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-Ylrn59AmWHFN0Yn7ZDIHr0jid6rIUmqCsqeYDTyIzZd Scale = 1:14.1 1 2 8 3 4 4x8 4-1-44-0-12 -1-6-5 1-6-5 4-1-4 4-1-4 0-7-52-3-01-10-102-3-04.80 12 Plate Offsets (X,Y)-- [2:0-3-8,Edge] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.23 0.16 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.01 -0.03 0.01 0.01 (loc) 4-7 4-7 3 4-7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 13 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-1-4 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)3=Mechanical, 4=Mechanical, 2=0-4-13 Max Horz 2=61(LC 14) Max Uplift 3=-36(LC 14), 2=-39(LC 10) Max Grav 3=123(LC 21), 4=71(LC 7), 2=322(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3) -1-6-5 to 2-8-9, Exterior(2R) 2-8-9 to 4-0-8 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 2. 9) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss J01 Truss Type Jack-Open Qty 1 Ply 1 TG41 Job Reference (optional) I48803343 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:15 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-1xP9IVBOHbNEeiMJ7wpWODGu3WB5DD4M5UN5lwyIzZc Scale = 1:14.4 1 2 3 4 3x4 3-8-53-8-5 -0-11-0 0-11-0 3-8-5 3-8-5 0-5-82-3-101-11-02-3-106.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.19 0.13 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.01 -0.02 0.00 0.01 (loc) 4-7 4-7 2 4-7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 10 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-8-5 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)3=Mechanical, 2=0-3-8, 4=Mechanical Max Horz 2=63(LC 14) Max Uplift 3=-39(LC 14), 2=-17(LC 14) Max Grav 3=120(LC 21), 2=259(LC 21), 4=67(LC 7) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 2. 9) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss J02 Truss Type Jack-Closed Qty 3 Ply 1 TG41 Job Reference (optional) I48803344 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:16 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-V7yXWrC02uV5GrxVheLlwRp26wTTygKVJ87fHMyIzZb Scale = 1:19.5 1 2 3 4 6 5 1.5x4 1.5x4 6x6 4-0-84-0-8 -0-11-0 0-11-0 4-0-8 4-0-8 0-7-53-3-108.00 12 Plate Offsets (X,Y)-- [2:Edge,0-3-3] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.24 0.44 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.03 -0.06 0.01 0.04 (loc) 6 6 2 6 l/defl >999 >772 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 14 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-0-8 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-3-8, 5=Mechanical Max Horz 2=84(LC 9) Max Uplift 2=-9(LC 12), 5=-35(LC 9) Max Grav 2=220(LC 2), 5=157(LC 24) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 3-6=-260/241 NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 6) Refer to girder(s) for truss to truss connections. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 5. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss J03 Truss Type Jack-Open Qty 1 Ply 1 TG41 Job Reference (optional) I48803345 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:16 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-V7yXWrC02uV5GrxVheLlwRp4nwZYygKVJ87fHMyIzZb Scale = 1:8.4 1 2 3 43x4 2-5-32-5-3 -0-11-0 0-11-0 2-5-3 2-5-3 0-3-111-1-70-9-41-1-74.00 12 Plate Offsets (X,Y)-- [2:0-1-8,0-0-0] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.06 0.05 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.00 -0.00 0.00 0.00 (loc) 7 7 4 7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 7 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 2-5-3 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)3=Mechanical, 2=0-1-12, 4=Mechanical Max Horz 2=34(LC 10) Max Uplift 3=-15(LC 14), 2=-39(LC 10) Max Grav 3=61(LC 21), 2=183(LC 21), 4=40(LC 7) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 2. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss J04 Truss Type Jack-Open Qty 1 Ply 1 TG41 Job Reference (optional) I48803346 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:17 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-zKWvjACepCdyt?WiELs_TeLFWJv5h7aeYosCpoyIzZa Scale = 1:9.2 1 2 3 4 3x4 2-1-122-1-12 -0-11-0 0-11-0 2-1-12 2-1-12 0-4-101-3-55.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.07 0.03 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in 0.00 -0.00 0.00 -0.00 (loc) 7 7 3 7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 6 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 2-1-12 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)3=Mechanical, 2=0-1-12, 4=Mechanical Max Horz 2=34(LC 14) Max Uplift 3=-17(LC 14), 2=-21(LC 14) Max Grav 3=55(LC 21), 2=175(LC 21), 4=36(LC 7) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 2. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss J05 Truss Type Roof Special Qty 4 Ply 1 TG41 Job Reference (optional) I48803347 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:18 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-RW4IxWDHaWloV95uo3ND0suPnjCdQaqonSclMFyIzZZ Scale = 1:8.5 1 2 3 4 3x4 1-0-01-0-0 -0-11-0 0-11-0 1-0-0 1-0-0 0-11-71-0-70-7-40-11-70-7-41-0-78.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.16 0.14 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) in 0.00 -0.00 0.00 (loc) 7 7 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 4 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 1-0-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing. REACTIONS. (size)4=Mechanical, 3=Mechanical Max Horz 4=-180(LC 18), 3=180(LC 18) Max Uplift 4=-23(LC 12) Max Grav 4=134(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 5) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 6) Refer to girder(s) for truss to truss connections. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. TRUSS IS ESPECIALLY DESIGNED FOR BEARING CONDITION AS SHOWN. THIS TRUSS MUST BE SUPPORTED BY THE ADEQUATE STRUCTURAL SUPPORT BY OTHERS. PROVIDE ADEQUATE LATERAL BRACING, BY OTHERS, TO THIS TRUSS TO PREVENT OUT-PLANE MOVEMENT OR OVER-TURNING OF TRUSS. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M01 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803348 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:19 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-vieg8sEvLptf7Jg4MmuSY3Ra17Zw91Ux?6LJuhyIzZY Scale = 1:29.6 1 2 3 4 5 6 7 8 14 13 12 11 10 9 15 16 17 3x4 -0-11-0 0-11-0 10-0-0 10-0-0 0-5-85-5-86.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.19 0.07 0.04 DEFL. Vert(LL) Vert(CT) Horz(CT) in -0.00 0.00 0.00 (loc) 1 1 9 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 47 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 10-0-0. (lb) - Max Horz 2=153(LC 11) Max Uplift All uplift 100 lb or less at joint(s) 9, 10, 11, 12, 13, 14 Max Grav All reactions 250 lb or less at joint(s) 9, 2, 10, 11, 12, 13 except 14=259(LC 2) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) -0-11-0 to 2-1-0, Exterior(2N) 2-1-0 to 6-10-4, Corner(3E) 6-10-4 to 9-10-4 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) All plates are 1.5x4 MT20 unless otherwise indicated. 7) Gable requires continuous bottom chord bearing. 8) Gable studs spaced at 1-4-0 oc. 9) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 10) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 11) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 9, 10, 11, 12, 13, 14. 12) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M02 Truss Type Monopitch Qty 6 Ply 1 TG41 Job Reference (optional) I48803349 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:20 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-NuC2MCFX67?WkTFGwUPh5HzglXqQuRN5Em5sQ7yIzZX Scale = 1:33.1 1 2 3 4 5 9 10 11 1.5x4 4x6 1.5x4 3x4 -0-11-0 0-11-0 5-0-3 5-0-3 10-0-0 4-11-13 0-5-85-5-85-2-00-3-85-5-86.00 12 Plate Offsets (X,Y)-- [2:0-0-0,0-0-9] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.45 0.44 0.25 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.23 -0.47 0.01 0.02 (loc) 5-8 5-8 2 5-8 l/defl >511 >253 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 41 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF 1650F 1.5E BOT CHORD 2x4 SP 2400F 2.0E WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SP No.3 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-1-12, 5=0-1-8 Max Horz 2=153(LC 13) Max Uplift 2=-37(LC 14), 5=-59(LC 14) Max Grav 2=452(LC 2), 5=449(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-471/142 BOT CHORD 2-5=-116/413 WEBS 3-5=-465/208 NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 6-10-4, Exterior(2E) 6-10-4 to 9-10-4 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 5 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2, 5. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 5. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M03 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803350 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:21 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-r5mQZYF9tR7NMdpTTBwwdUWt0xEpdxdETQqQyZyIzZW Scale = 1:14.8 1 2 3 4 6 5 1.5x4 1.5x4 3x4 1.5x4 1.5x4 -0-11-0 0-11-0 6-0-0 6-0-0 0-3-112-3-114.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.29 0.17 0.06 DEFL. Vert(LL) Vert(CT) Horz(CT) in -0.00 0.01 0.00 (loc) 1 1 5 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 19 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)5=6-0-0, 2=6-0-0, 6=6-0-0 Max Horz 2=66(LC 11) Max Uplift 5=-110(LC 21), 2=-39(LC 10), 6=-55(LC 14) Max Grav 5=16(LC 14), 2=229(LC 21), 6=480(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. WEBS 3-6=-375/340 NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) -0-11-0 to 2-1-0, Exterior(2N) 2-1-0 to 2-10-4, Corner(3E) 2-10-4 to 5-10-4 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) Gable requires continuous bottom chord bearing. 7) Gable studs spaced at 1-4-0 oc. 8) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 9) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 6 except (jt=lb) 5=110. 11) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M04 Truss Type Monopitch Qty 4 Ply 1 TG41 Job Reference (optional) I48803351 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:22 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-JHKomuGnekFE_mOf1uR9Ai3?HKVFMOpOi4azV0yIzZV Scale = 1:14.8 1 2 3 4 1.5x4 3x6 1.5x4 6-0-06-0-0 -0-11-0 0-11-0 6-0-0 6-0-0 0-3-112-3-112-0-30-3-82-3-114.00 12 Plate Offsets (X,Y)-- [2:0-1-8,0-0-0] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.51 0.48 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.08 -0.14 0.00 0.05 (loc) 4-7 4-7 2 4-7 l/defl >922 >486 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 17 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-1-12, 4=0-1-8 Max Horz 2=66(LC 13) Max Uplift 2=-50(LC 10), 4=-28(LC 14) Max Grav 2=327(LC 21), 4=273(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) -0-11-0 to 2-1-0, Interior(1) 2-1-0 to 2-10-4, Exterior(2E) 2-10-4 to 5-10-4 zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2, 4. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M05 Truss Type Monopitch Qty 5 Ply 1 TG41 Job Reference (optional) I48803352 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:23 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-oTuB_EHPP2N5bwzrbczOjvbCxku55r3XwkJW1SyIzZU Scale = 1:12.6 1 2 3 4 1.5x4 3x4 1.5x4 5-0-05-0-0 -0-11-0 0-11-0 5-0-0 5-0-0 0-3-111-11-111-8-30-3-81-11-114.00 12 Plate Offsets (X,Y)-- [2:0-1-8,0-0-0] LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.33 0.31 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.03 -0.07 0.00 0.02 (loc) 4-7 4-7 2 4-7 l/defl >999 >878 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 14 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 5-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-1-12, 4=0-1-8 Max Horz 2=56(LC 13) Max Uplift 2=-47(LC 10), 4=-23(LC 14) Max Grav 2=304(LC 21), 4=223(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2, 4. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M06 Truss Type Monopitch Qty 3 Ply 1 TG41 Job Reference (optional) I48803353 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:23 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-oTuB_EHPP2N5bwzrbczOjvbFUkx?5r3XwkJW1SyIzZU Scale = 1:12.4 1 2 3 4 1.5x4 3x4 1.5x4 3-8-03-8-0 -0-11-0 0-11-0 3-8-0 3-8-0 0-4-101-10-151-7-70-3-81-10-155.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.16 0.13 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.01 -0.02 0.00 0.01 (loc) 4-7 4-7 2 4-7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 11 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-8-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-1-12, 4=0-1-8 Max Horz 2=52(LC 13) Max Uplift 2=-27(LC 14), 4=-17(LC 14) Max Grav 2=247(LC 21), 4=159(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 2, 4. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M07 Truss Type Monopitch Qty 3 Ply 1 TG41 Job Reference (optional) I48803354 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:24 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-GgRZBaI19MVyD4Y29JUdF78QE8GEqIJg9O34ZuyIzZT Scale = 1:12.4 1 2 3 4 1.5x4 3x4 1.5x4 3-8-03-8-0 -0-11-0 0-11-0 3-8-0 3-8-0 0-4-101-10-151-7-70-3-81-10-155.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.16 0.13 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.01 -0.02 0.00 0.01 (loc) 4-7 4-7 2 4-7 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 11 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-8-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-3-8, 4=0-1-8 Max Horz 2=52(LC 13) Max Uplift 2=-27(LC 14), 4=-17(LC 14) Max Grav 2=247(LC 21), 4=159(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Bearing at joint(s) 4 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify capacity of bearing surface. 8) Provide mechanical connection (by others) of truss to bearing plate at joint(s) 4. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M08 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803355 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:25 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-ks?xPvIgwfdprE7Ei1?soKhaCYcWZlZqO2od5LyIzZS Scale = 1:12.4 1 2 3 4 1.5x4 1.5x4 3x4 -0-11-0 0-11-0 3-8-0 3-8-0 0-4-101-10-155.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.21 0.12 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) in -0.00 0.00 0.00 (loc) 1 1 4 l/defl n/r n/r n/a L/d 120 90 n/a PLATES MT20 Weight: 11 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 3-8-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)4=3-8-0, 2=3-8-0 Max Horz 2=52(LC 13) Max Uplift 4=-17(LC 14), 2=-27(LC 14) Max Grav 4=159(LC 21), 2=247(LC 21) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Corner(3E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1. 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 6) Gable requires continuous bottom chord bearing. 7) Gable studs spaced at 1-4-0 oc. 8) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 9) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4, 2. 11) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss M09 Truss Type MONO TRUSS Qty 9 Ply 1 TG41 Job Reference (optional) I48803356 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:26 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-C2ZJcFJIhzlgTOiQGkW5KYDnCyzUICpzciYAenyIzZR Scale = 1:6.5 1 2 3 4 3x4 0-10-00-10-0 -0-11-0 0-11-0 0-10-0 0-10-0 0-3-150-8-156.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.07 0.01 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in 0.00 0.00 -0.00 -0.00 (loc) 5 5 4 5 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 3 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 0-10-0 oc purlins. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)2=0-3-8, 4=Mechanical Max Horz 2=23(LC 14) Max Uplift 2=-26(LC 14), 4=-25(LC 20) Max Grav 2=133(LC 20), 4=15(LC 7) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Refer to girder(s) for truss to truss connections. 8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 2, 4. 9) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. VERTICAL SUPPORT OF FREE ENDOF CHORD IS REQUIRED. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss MG01 Truss Type Jack-Open Girder Qty 1 Ply 1 TG41 Job Reference (optional) I48803357 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:27 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-gF7hqbKwSHtX4YHdqS1Ktlmy3LHz1fb7rMHkADyIzZQ Scale = 1:14.4 1 2 3 5 4 9 3x6 4x6 3x4 4x4 Special Special 2-6-82-6-8 4-0-81-6-0 -0-11-0 0-11-0 2-6-8 2-6-8 4-0-8 1-6-0 0-7-52-3-102-0-22-3-108.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 20.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 NO IBC2018/TPI2014 CSI. TC BC WB Matrix-MP 0.12 0.19 0.03 DEFL. Vert(LL) Vert(CT) Horz(CT) Wind(LL) in -0.01 -0.02 0.00 0.00 (loc) 5-8 5-8 2 5-8 l/defl >999 >999 n/a >999 L/d 360 240 n/a 240 PLATES MT20 Weight: 16 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 WEDGE Left: 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 4-0-8 oc purlins, except 2-0-0 oc purlins: 3-4. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)4=Mechanical, 2=0-3-8, 5=Mechanical Max Horz 2=65(LC 12) Max Uplift 4=-14(LC 8), 2=-25(LC 12), 5=-28(LC 12) Max Grav 4=41(LC 1), 2=253(LC 1), 5=216(LC 1) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Unbalanced roof live loads have been considered for this design. 2) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 3) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=20.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10, Lu=50-0-0; Min. flat roof snow load governs. Rain surcharge applied to all exposed surfaces with slopes less than 0.500/12 in accordance with IBC 1608.3.4. 4) This truss has been designed for greater of min roof live load of 12.0 psf or 2.00 times flat roof load of 15.4 psf on overhangs non-concurrent with other live loads. 5) Provide adequate drainage to prevent water ponding. 6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 7) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 8) Refer to girder(s) for truss to truss connections. 9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4, 2, 5. 10) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. 11) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord. 12) Gap between inside of top chord bearing and first diagonal or vertical web shall not exceed 0.500in. 13) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 152 lb down and 152 lb up at 2-6-8 on top chord, and 57 lb down at 2-6-8 on bottom chord. The design/selection of such connection device(s) is the responsibility of others. 14) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). LOAD CASE(S) Standard Continued on page 2 November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss MG01 Truss Type Jack-Open Girder Qty 1 Ply 1 TG41 Job Reference (optional) I48803357 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:27 2021 Page 2 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-gF7hqbKwSHtX4YHdqS1Ktlmy3LHz1fb7rMHkADyIzZQ LOAD CASE(S) Standard 1) Dead + Snow (balanced): Lumber Increase=1.15, Plate Increase=1.15 Uniform Loads (plf) Vert: 1-3=-51, 3-4=-61, 5-6=-20 Concentrated Loads (lb) Vert: 3=-118(B) 9=-57(B) 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss V01 Truss Type Valley Qty 1 Ply 1 TG41 Job Reference (optional) I48803358 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:32 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-1CwatJO3HpWpBJ9ad?dVapTqxM0divIs?d?VrRyIzZL Scale = 1:9.3 1 2 3 3x4 1.5x4 1.5x4 2-7-0 2-7-0 0-0-41-3-86.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.05 0.03 0.00 DEFL. Vert(LL) Vert(CT) Horz(CT) in n/a n/a 0.00 (loc) - - 3 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 6 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 2-7-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)1=2-6-8, 3=2-6-8 Max Horz 1=27(LC 11) Max Uplift 1=-4(LC 14), 3=-11(LC 14) Max Grav 1=80(LC 20), 3=80(LC 20) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) Gable requires continuous bottom chord bearing. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss V02 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803359 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:35 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-RncjVKQxakuO2mu9I7ACCR5KOa23vGbIhbE9SlyIzZI Scale = 1:16.5 1 2 3 5 4 3x4 1.5x4 1.5x4 1.5x4 1.5x4 5-3-0 5-3-0 0-0-42-7-86.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.10 0.05 0.03 DEFL. Vert(LL) Vert(CT) Horz(CT) in n/a n/a 0.00 (loc) - - 4 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 15 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 5-3-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS. (size)1=5-3-0, 4=5-3-0, 5=5-3-0 Max Horz 1=66(LC 11) Max Uplift 4=-8(LC 11), 5=-44(LC 14) Max Grav 1=103(LC 20), 4=55(LC 20), 5=280(LC 20) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) Gable requires continuous bottom chord bearing. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4, 5. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 16023 Swingley Ridge RdChesterfield, MO 63017 Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Componentavailable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601Safety Information WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. Job 2200684-2200684A Truss V03 Truss Type GABLE Qty 1 Ply 1 TG41 Job Reference (optional) I48803360 8.520 s Aug 27 2021 MiTek Industries, Inc. Mon Nov 15 09:58:36 2021 Page 1 84 Components (Franklin), Franklin, IN - 46131, ID:Y6KbEUSnYVwk2YuHWHi4MazA3gj-vzA5jgRZL20FfwTLsriRkfeVq_NwejqRwFzi_CyIzZH Scale: 1/2"=1' 1 2 3 4 7 6 5 8 3x4 1.5x4 1.5x4 1.5x4 1.5x4 1.5x4 1.5x4 7-11-0 7-11-0 0-0-43-11-86.00 12 LOADING (psf) TCLL (roof) Snow (Pf/Pg) TCDL BCLL BCDL 20.0 15.4/20.0 10.0 0.0 * 10.0 SPACING- Plate Grip DOL Lumber DOL Rep Stress Incr Code 2-0-0 1.15 1.15 YES IBC2018/TPI2014 CSI. TC BC WB Matrix-P 0.12 0.07 0.03 DEFL. Vert(LL) Vert(CT) Horz(CT) in n/a n/a -0.00 (loc) - - 5 l/defl n/a n/a n/a L/d 999 999 n/a PLATES MT20 Weight: 26 lb FT = 10% GRIP 197/144 LUMBER- TOP CHORD 2x4 SPF No.2 BOT CHORD 2x4 SPF No.2 WEBS 2x4 SPF No.2 OTHERS 2x4 SPF No.2 BRACING- TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, except end verticals. BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing. REACTIONS.All bearings 7-11-0. (lb) - Max Horz 1=105(LC 11) Max Uplift All uplift 100 lb or less at joint(s) 5, 6, 7 Max Grav All reactions 250 lb or less at joint(s) 1, 5, 6 except 7=285(LC 20) FORCES.(lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown. NOTES- 1) Wind: ASCE 7-16; Vult=115mph (3-second gust) Vasd=91mph; TCDL=4.2psf; BCDL=6.0psf; h=25ft; Cat. II; Exp B; Enclosed; MWFRS (envelope) gable end zone and C-C Exterior(2E) zone; cantilever left and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60 2) TCLL: ASCE 7-16; Pr=20.0 psf (roof LL: Lum DOL=1.15 Plate DOL=1.15); Pg=20.0 psf; Pf=15.4 psf (Lum DOL=1.15 Plate DOL=1.15); Is=1.0; Rough Cat B; Partially Exp.; Ce=1.0; Cs=1.00; Ct=1.10 3) Unbalanced snow loads have been considered for this design. 4) Gable requires continuous bottom chord bearing. 5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads. 6) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. 7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 5, 6, 7. 8) This truss is designed in accordance with the 2018 International Building Code section 2306.1 and referenced standard ANSI/TPI 1. November 16,2021 PRODUCT CODE APPROVALSLATERAL BRACING LOCATIONIndicates location where bearings(supports) occur. Icons vary butreaction section indicates jointnumber where bearings occur.Min size shown is for crushing only.Indicated by symbol shown and/orby text in the bracing section of theoutput. Use T or I bracingif indicated.The first dimension is the plate width measured perpendicular to slots. Second dimension isthe length parallel to slots.Center plate on joint unless x, yoffsets are indicated.Dimensions are in ft-in-sixteenths.Apply plates to both sides of trussand fully embed teeth.1. Additional stability bracing for truss system, e.g. diagonal or X-bracing, is always required. See BCSI.2. Truss bracing must be designed by an engineer. For wide truss spacing, individual lateral braces themselves may require bracing, or alternative Tor I bracing should be considered.3. Never exceed the design loading shown and never stack materials on inadequately braced trusses.4. Provide copies of this truss design to the building designer, erection supervisor, property owner and all other interested parties.5. Cut members to bear tightly against each other.6. Place plates on each face of truss at each joint and embed fully. Knots and wane at joint locations are regulated by ANSI/TPI 1.7. Design assumes trusses will be suitably protected from the environment in accord with ANSI/TPI 1.8. Unless otherwise noted, moisture content of lumber shall not exceed 19% at time of fabrication.9. Unless expressly noted, this design is not applicable for use with fire retardant, preservative treated, or green lumber.10. Camber is a non-structural consideration and is the responsibility of truss fabricator. General practice is to camber for dead load deflection.11. Plate type, size, orientation and location dimensions indicated are minimum plating requirements.12. Lumber used shall be of the species and size, and in all respects, equal to or better than that specified.13. Top chords must be sheathed or purlins provided at spacing indicated on design.14. Bottom chords require lateral bracing at 10 ft. spacing, or less, if no ceiling is installed, unless otherwise noted.15. Connections not shown are the responsibility of others.16. Do not cut or alter truss member or plate without prior approval of an engineer.17. Install and load vertically unless indicated otherwise.18. Use of green or treated lumber may pose unacceptable environmental, health or performance risks. Consult with project engineer before use.19. Review all portions of this design (front, back, words and pictures) before use. Reviewing pictures alone is not sufficient.20. Design assumes manufacture in accordance with ANSI/TPI 1 Quality Criteria.21.The design does not take into account any dynamic or other loads other than those expressly stated.Failure to Follow Could Cause PropertyDamage or Personal Injury (Drawings not to scale)© 2012 MiTek® All Rights ReservedMiTek Engineering Reference Sheet: MII-7473 rev. 5/19/2020edge of truss.from outside"16/1-0ICC-ES Reports:ESR-1311, ESR-1352, ESR1988ER-3907, ESR-2362, ESR-1397, ESR-3282JOINTS ARE GENERALLY NUMBERED/LETTERED CLOCKWISEAROUND THE TRUSS STARTING AT THE JOINT FARTHEST TOTHE LEFT.CHORDS AND WEBS ARE IDENTIFIED BY END JOINTNUMBERS/LETTERS.W 4 - 6 W3-6W3- 7 W2-7W1-7C1-8 C5-6C6-7C7-8C4-5 C3-4C2-3C1-2TOP CHORD TOP CHORD 87654321BOTTOM CHORDSTOP CHORDSBEARING4 x 4PLATE SIZEThis symbol indicates the required direction of slots inconnector plates."16/1For 4 x 2 orientation, locateplates 0- 1"4/3PLATE LOCATION AND ORIENTATIONSymbolsNumbering SystemGeneral Safety Notes *Plate location details available in MiTek 20/20software or upon request.Industry Standards:ANSI/TPI1: National Design Specification for Metal Plate Connected Wood Truss Construction.DSB-89: Design Standard for Bracing.BCSI: Building Component Safety Information, Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses.6-4-8WEBSTrusses are designed for wind loads in the plane of the truss unless otherwise shown.Lumber design values are in accordance with ANSI/TPI 1 section 6.3 These truss designs rely on lumber values established by others.dimensions shown in ft-in-sixteenths