HomeMy WebLinkAboutE003.0-ElecDetails#1. " " DENOTES FEEDER REFERENCE. REFER TO SHEET E-2 FOR FEEDER/CIRCUIT SCHEDULE.
2. CONTRACTOR SHALL REFER TO CIVIL SHEETS FOR EXISTING LANDSCAPING TO REMAIN AND
PROPOSED LANDSCAPING.
3. CONTRACTOR SHALL HAND DIG AROUND ALL EXISTING UTILITIES.
4. CONDUIT ELBOWS SHALL BE SIZED PER NEC. CONTRACTOR SHALL VERIFY MANUFACTURER
ALLOWABLE FILL AND MINIMUM CONDUCTOR BENDING RADIUS. SEE FEEDER SCHEDULE FOR
CONDUIT & CONDUCTOR SPECIFICATIONS.
5. ALL CONDUITS ACCESSIBLE TO THE PUBLIC OR WHICH CAN BE DAMAGED SHALL BE RIGID
GALVANIZED STEEL.
6. PROPERTY LINE AND RIGHT-OF-WAY BOUNDARIES ARE SHOWN FOR REFERENCE ONLY. REFER
TO SURVEY BY OTHERS FOR EXACT LOCATION.
7. UTILITY EQUIPMENT INSTALLATIONS AND PREP WORK SHALL BE COORDINATED WITH THE
APPROPRIATE UTILITY ENGINEER TO ENSURE ACCURACY OF INSTALLATION.
8. ALL PROPOSED CONDUITS MUST MEET MINIMUM DEPTH REQUIREMENTS AS OUTLINED IN
TRENCH DETAILS, AS WELL AS MAINTAIN A MINIMUM OF 18" CLEAR OF ALL EXISTING
OBSTRUCTIONS INCLUDING (BUT NOT LIMITED TO) STORM PIPES, SANITARY PIPES, WATER LINES
AND OTHER UNDERGROUND UTILITIES.
9. PROPERTY LINE AND RIGHT-OF-WAY BOUNDARIES ARE SHOWN FOR REFERENCE ONLY. REFER
TO SURVEY BY OTHERS FOR EXACT LOCATION.
10. FOR TRAFFIC CONTROL PROCEDURES (IF APPLICABLE), SEE TRAFFIC CONTROL NOTES ON
SHEET GN-1.ELECTRICALEQUIPMENT PLANGENERAL SHEET NOTES
0' 10'5' SCALE: 1"=10'FULL SIZE A 11.05.21REV.DATEDESCRIPTIONDrawing Name: O:\2021\2021095\98 - TRT 18712 - Carmel, IN\dwg\2021095.98- Carmel, IN N Illinois - CD90.dwgJune 10, 2022 12:29 PM - jarchDESIGNERINSTALL MANAGER
E-1
JOB NO.
ISSUED FOR:
PERMIT
RECORD
CONSTRUCTION
BID
2021095.98
ABRWILL
CARTER11545 N ILLINOIS ST.(TESLA STATION) - TRT18712CARMEL, IN 46032B 11.19.21 ISSUED FOR 90% REVIEWC 04.25.22ISSUED FOR 90% REVIEWISSUED FOR SIGN AND SEALXXX
XXX
XXX
XXX
1 2 3 4
C
B
A
GPD GROUP, INC. ®
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax 330.572.2101
1 06.10.22 REVISIONS FOR CITY COMMENTS
PROVIDE PRIMARY SIDE BORING
PROVIDE & INSTALL PRIMARY SIDE CONDUITS W/ PULLWIRE
PROVIDE & INSTALL PRIMARY SIDE CONDUCTORS
PROVIDE & INSTALL UTILITY POLE (RISER BY CONTRACTOR)
PROVIDE & INSTALL UTILITY TRANSFORMER PAD
PROVIDE UTILITY TRANSFORMER
INSTALL UTILITY TRANSFORMER
INSTALL CONNECTIONS AT UTILITY TRANSFORMER (PRIMARY)
INSTALL CONNECTIONS AT UTILITY TRANSFORMER (SECONDARY)
PROVIDE METER
INSTALL METER
PROVIDE SECONDARY SIDE TRENCHING
PROVIDE & INSTALL SECONDARY SIDE CONDUITS W/ PULLWIRE
PROVIDE ROAD CUTS / ROAD BORES
PROVIDE & INSTALL PAVEMENT REPLACEMENT
ELECTRICAL SCOPE OF WORK RESPONSIBILITIES
PROVIDE & INSTALL PRIMARY SIDE OVERHEAD CONDUCTORS
NOTE: SCOPE SHOWN ABOVE WAS PROVIDED BY AES. FIELD VERIFY PRIOR TO CONSTRUCTION.
PROVIDE & INSTALL SECONDARY SIDE CONDUCTORS
SCOPE BY
UTILITY
BY
CONTRACTOR
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
PROVIDE CTs
INSTALL CTs (INSIDE H-FRAME)
x
x
AES
ATTN: RODNEY JOHNSON
(330) 261-5047
RODNEY.JOHNSON@AES.COM
POWER COMPANY CONTACTS
(8) PROPOSED TESLA
CHARGING POSTS (TYP.)C-3
10
2
x
x
PROVIDE METER BASE AND CT CABINET
INSTALL METER BASE
15'-0"
EXISTING ELECTRICAL EASEMENT
15'-0"ELEC. EASEMENTAPPROXIMATE LOCATION
ORDINANCE D-2116-12
SEE SURVEY
20'-0"
BERM ENCROACHMENT EASEMENT
20'-0"
LANDSCAPE BUFFER
PROPOSED ELECTRICAL LINE EASEMENT
1A
1B
1C
1D
2A
2B
2C
2D
1
(2) PROPOSED
TESLA CHARGING
CABINETS (TYP.)C-3
2
(4) PROPOSED TESLA
CHARGING POST
CONDUITS (1 PER
POST)
3 E-3
3
(4) PROPOSED TESLA
CHARGING POST
CONDUITS (1 PER
POST)
3
E-3
3
PROPOSED UTILITY TRANSFORMER WITH TAPS, 480V/277V,
3Ø, 4W SECONDARY ON CONCRETE PAD. REFER TO
SUPPLEMENTAL UTILITY PAD DETAIL PRIOR TO
INSTALLATION
PROPOSED UNDERGROUND
PRIMARY CONDUITS &
CONDUCTORS BY UTILITY.
PROPOSED CT CABINET, PT &
METER MOUNTED ON H-FRAME E-3
5
PROPOSED UNDERGROUND SERVICE
LATERAL CONDUITS FROM PROPOSED
TRANSFORMER TO PROPOSED CT CABINET
PER POWER COMPANY REQUIREMENTS
1
E-3
1
PROPOSED SWITCHGEAR
ASSEMBLY W/ INTEGRATED
MASTER CONTROLLER - DEAD
BACK
PROPOSED UNDERGROUND SERVICE
LATERAL CONDUITS FROM PROPOSED CT
CABINET TO PROPOSED SWITCHGEAR PER
POWER COMPANY REQUIREMENTS
1
E-3
1
(4) PROPOSED CONDUITS FROM SWITCHGEAR
TO CHARGING CABINETS (2 PER CHARGING
CABINET) ALONG WITH (2) CONDUITS FOR
COMMUNICATION CABLES FROM MASTER
CONTROLLER (1 PER CABINET)
E-3
2
25
PROPOSED CONDUITS
ROUTED FROM EACH CABINET
TO CENTER CABINET FOR
SHARED DC BUS CONNECTION
6 E-3
2
PROPOSED LOCATION FOR
RELOCATED LIGHT ON
CONCRETE FOUNDATION
(TYPICAL OF 1)
C-3
9
CONTRACTOR SHALL RELOCATE UNDERGROUND
LIGHTING CIRCUIT TO PROPOSED LOCATION.
PROVIDE HANDHOLE AND SPLICE & EXTEND
CONDUIT & WIRING TO NEW LOCATION. MATCH
SIZE AND MATERIAL.
06/10/22
07/06/22