Loading...
HomeMy WebLinkAboutE003.0-ElecDetails#1." " DENOTES FEEDER REFERENCE. REFER TO SHEET E-2 FOR FEEDER/CIRCUIT SCHEDULE.2.CONTRACTOR SHALL REFER TO CIVIL SHEETS FOR EXISTING LANDSCAPING TO REMAIN ANDPROPOSED LANDSCAPING.3.CONTRACTOR SHALL HAND DIG AROUND ALL EXISTING UTILITIES.4.CONDUIT ELBOWS SHALL BE SIZED PER NEC. CONTRACTOR SHALL VERIFY MANUFACTURERALLOWABLE FILL AND MINIMUM CONDUCTOR BENDING RADIUS. SEE FEEDER SCHEDULE FORCONDUIT & CONDUCTOR SPECIFICATIONS.5.ALL CONDUITS ACCESSIBLE TO THE PUBLIC OR WHICH CAN BE DAMAGED SHALL BE RIGIDGALVANIZED STEEL.6.PROPERTY LINE AND RIGHT-OF-WAY BOUNDARIES ARE SHOWN FOR REFERENCE ONLY. REFERTO SURVEY BY OTHERS FOR EXACT LOCATION.7.UTILITY EQUIPMENT INSTALLATIONS AND PREP WORK SHALL BE COORDINATED WITH THEAPPROPRIATE UTILITY ENGINEER TO ENSURE ACCURACY OF INSTALLATION.8.ALL PROPOSED CONDUITS MUST MEET MINIMUM DEPTH REQUIREMENTS AS OUTLINED INTRENCH DETAILS, AS WELL AS MAINTAIN A MINIMUM OF 18" CLEAR OF ALL EXISTINGOBSTRUCTIONS INCLUDING (BUT NOT LIMITED TO) STORM PIPES, SANITARY PIPES, WATER LINESAND OTHER UNDERGROUND UTILITIES.9.PROPERTY LINE AND RIGHT-OF-WAY BOUNDARIES ARE SHOWN FOR REFERENCE ONLY. REFERTO SURVEY BY OTHERS FOR EXACT LOCATION.10.FOR TRAFFIC CONTROL PROCEDURES (IF APPLICABLE), SEE TRAFFIC CONTROL NOTES ONSHEET GN-1.ELECTRICAL EQUIPMENT PLAN GENERAL SHEET NOTES0'10'5'SCALE: 1"=10'FULL SIZEA 11.05.21 REV.DATE DESCRIPTION Drawing Name: O:\2021\2021095\98 - TRT 18712 - Carmel, IN\dwg\2021095.98- Carmel, IN N Illinois - CD90.dwgJune 10, 2022 12:29 PM - jarch DESIGNERINSTALL MANAGERE-1JOB NO.ISSUED FOR:PERMITRECORDCONSTRUCTIONBID2021095.98ABRWILLCARTER11545 N ILLINOIS ST. (TESLA STATION) - TRT18712 CARMEL, IN 46032 B 11.19.21 ISSUED FOR 90% REVIEW C 04.25.22 ISSUED FOR 90% REVIEW ISSUED FOR SIGN AND SEAL XXXXXXXXXXXX1234CBAGPD GROUP, INC.®520 South Main Street, Suite 2531Akron, OH 44311330.572.2100Fax 330.572.21011 06.10.22 REVISIONS FOR CITY COMMENTSPROVIDE PRIMARY SIDE BORINGPROVIDE & INSTALL PRIMARY SIDE CONDUITS W/ PULLWIREPROVIDE & INSTALL PRIMARY SIDE CONDUCTORSPROVIDE & INSTALL UTILITY POLE (RISER BY CONTRACTOR)PROVIDE & INSTALL UTILITY TRANSFORMER PADPROVIDE UTILITY TRANSFORMERINSTALL UTILITY TRANSFORMERINSTALL CONNECTIONS AT UTILITY TRANSFORMER (PRIMARY)INSTALL CONNECTIONS AT UTILITY TRANSFORMER (SECONDARY)PROVIDE METERINSTALL METERPROVIDE SECONDARY SIDE TRENCHINGPROVIDE & INSTALL SECONDARY SIDE CONDUITS W/ PULLWIREPROVIDE ROAD CUTS / ROAD BORESPROVIDE & INSTALL PAVEMENT REPLACEMENTELECTRICAL SCOPE OF WORK RESPONSIBILITIESPROVIDE & INSTALL PRIMARY SIDE OVERHEAD CONDUCTORSNOTE: SCOPE SHOWN ABOVE WAS PROVIDED BY AES. FIELD VERIFY PRIOR TO CONSTRUCTION.PROVIDE & INSTALL SECONDARY SIDE CONDUCTORSSCOPEBYUTILITYBYCONTRACTORxxxxxxxxxxxxxxxxxPROVIDE CTsINSTALL CTs (INSIDE H-FRAME)xxAESATTN: RODNEY JOHNSON(330) 261-5047RODNEY.JOHNSON@AES.COMPOWER COMPANY CONTACTS(8) PROPOSED TESLACHARGING POSTS (TYP.)C-3102xxPROVIDE METER BASE AND CT CABINETINSTALL METER BASE15'-0"EXISTING ELECTRICAL EASEMENT15'-0" ELEC. EASEMENT APPROXIMATE LOCATIONORDINANCE D-2116-12SEE SURVEY20'-0"BERM ENCROACHMENT EASEMENT20'-0"LANDSCAPE BUFFERPROPOSED ELECTRICAL LINE EASEMENT1A1B1C1D2A2B2C2D1(2) PROPOSEDTESLA CHARGINGCABINETS (TYP.)C-32(4) PROPOSED TESLACHARGING POSTCONDUITS (1 PERPOST)3E-33(4) PROPOSED TESLACHARGING POSTCONDUITS (1 PERPOST)3E-33PROPOSED UTILITY TRANSFORMER WITH TAPS, 480V/277V,3Ø, 4W SECONDARY ON CONCRETE PAD. REFER TOSUPPLEMENTAL UTILITY PAD DETAIL PRIOR TOINSTALLATIONPROPOSED UNDERGROUNDPRIMARY CONDUITS &CONDUCTORS BY UTILITY.PROPOSED CT CABINET, PT &METER MOUNTED ON H-FRAMEE-35PROPOSED UNDERGROUND SERVICELATERAL CONDUITS FROM PROPOSEDTRANSFORMER TO PROPOSED CT CABINETPER POWER COMPANY REQUIREMENTS1E-31PROPOSED SWITCHGEARASSEMBLY W/ INTEGRATEDMASTER CONTROLLER - DEADBACKPROPOSED UNDERGROUND SERVICELATERAL CONDUITS FROM PROPOSED CTCABINET TO PROPOSED SWITCHGEAR PERPOWER COMPANY REQUIREMENTS1E-31(4) PROPOSED CONDUITS FROM SWITCHGEARTO CHARGING CABINETS (2 PER CHARGINGCABINET) ALONG WITH (2) CONDUITS FORCOMMUNICATION CABLES FROM MASTERCONTROLLER (1 PER CABINET)E-3225PROPOSED CONDUITSROUTED FROM EACH CABINETTO CENTER CABINET FORSHARED DC BUS CONNECTION6E-32PROPOSED LOCATION FORRELOCATED LIGHT ONCONCRETE FOUNDATION(TYPICAL OF 1)C-39CONTRACTOR SHALL RELOCATE UNDERGROUNDLIGHTING CIRCUIT TO PROPOSED LOCATION.PROVIDE HANDHOLE AND SPLICE & EXTENDCONDUIT & WIRING TO NEW LOCATION. MATCHSIZE AND MATERIAL.06/10/22