HomeMy WebLinkAboutEN010.0-ElecGenNotes1.NEUTRAL MUST BE INCLUDED FOR PROPER OPERATION OF TESLA SUPERCHARGERS.2.PROPOSED UTILITY CTs SHALL BE LOCATED IN UTILITY APPROVED CTCOMPARTMENTS MOUNTED ON H-FRAME. PROPOSED METER SHALL BE MOUNTED ONCT CABNIET.3.ALL CONDUIT FURNISHED AND INSTALLED BY CONTRACTOR.4.ALL WIRING FURNISHED BY TESLA AND INSTALLED BY CONTRACTOR UNLESS NOTEDOTHERWISE. SEE SHEET E-1 FOR UTILITY/CONTRACTOR SCOPE OF WORK.5.THE TESLA PROVIDED CHARGING CABINETS AND THE CHARGING POSTS USED ONTHIS PROJECT COMPLY WITH THE FOLLOWING STANDARDS:·TUV CERTIFIED TO UL 22026.ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY ANATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITEDSTATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION.ONE-LINE DIAGRAM
& PANEL SCHEDULE FEEDER/CIRCUIT SCHEDULENOCONFIGURATION1234(4) SETS - EACH IN 4" CONDUIT(3) 500 MCM Al(1) 500 MCM Al NEUT5SHIELDED CAT6 COMMUNICATION CABLE IN 1"CONDUIT.FACTORY INSTALLED WIRING6600/3 UTILITY PAD MOUNTEDTRANSFORMER WITH TAPS480/277V, 3Ø, 4W(BY UTILITY)1200/3100%RATED1PROPOSED 1200A SERVICE EQUIPMENT480/277V, 3Ø, 4W, 65 KAIC, NEMA 3R, LOCKABLESERVICE ENTRANCEMAIN DISCONNECTSWITCH w/ GROUNDFAULT PROTECTION& ARC ENERGYREDUCTION SWITCHPROPOSEDGROUND BYUTILITY25TYP OF 1
600/3
TYP OF 1
NOTE:CONTRACTOR SHALL VERIFY ACAND DC WIRING REQUIREMENTSWITH VENDOR'S SCHEMATICWIRING DRAWINGSA3VEHICLE CHARGING POST(TOTAL OF 8) TYPICAL OF 4POSTS PER CABINETTYPICAL CHARGINGCABINET ONLY (TYP. OF 1)BCDINTEGRAL DISCONNECT FOR EACHCHARGING POST FOR SERVICING OFEQUIPMENT (TYPICAL EACH CABINET)CHARGINGCABINET/CENTER DCCABINET FORSHARED DC BUSINTERCONNECTIONTYPICAL OF 1(2) SETS - EACH IN 3" CONDUIT.(2) 600 MCM Al (ONE +, ONE -)(1) #3/0 AWG Al DC MID(1) #1/0 AWG Cu GND(1) #3/0 AWG Al DC MID DISC.36" LONG IN EA. CABINET, NOT ROUTED IN CONDUITCENTERCABINETTYPICALCABINETABCDGNDNEUTSERVICE GROUND.SEE SHEET E-36NOTE:1.ALL AC CONDUCTORS SHALL BE XHHW-2, 600V RATED, U.N.O.2.ALL DC CONDUCTORS SHALL BE XHHW-2, 1000V RATED, U.N.O.3.FOR APPROVED COPPER/ALUMINUM EQUIPMENT GROUNDINGCONDUCTOR EQUIVALENTS, SEE TABLE BELOW. ALL ALUMINUMEQUIPMENT GROUND CONDUCTORS SHALL BE TERMINATED INOUTDOOR ENCLOSURES LISTED AND IDENTIFIED FOR THEENVIRONMENT PER NEC 2020, ARTICLE 250.64(A)(2).4.SEE "RACEWAY AND BOXES" NOTES ON SHEET EN-1 FOR CONDUITUSE TYPES FOR ABOVE AND BELOW GRADE APPLICATIONS.1000V1000VLOCKABLE INOPENPOSITION(TYPICAL)(1) SET IN 4" CONDUIT(4) 350 MCM Al (TWO +, TWO -)(1) #1 AWG Cu GND OR #2/0 AWG Al GND(1) 1000V, CLASS 1, COMM CABLE(2) SETS - EACH IN 4" CONDUIT(3) 500 MCM Al(1) 500 MCM Al NEUT(1) #1 AWG Cu GND OR #2/0 AWG Al GNDPANEL BOARD NOTES1.CIRCUITS SHALL BE REARRANGED AS REQUIRED TO MAINTAIN THE MOST BALANCED LOADS ON EACH PHASE WITHIN EACHPANEL. PROVIDE TYPED PANEL DIRECTORY MOUNTED PER MANUFACTURERS RECOMMENDATIONS WITH SERVICEEQUIPMENT.2.OCPD FOR CHARGING CABINETS ARE CALCULATED AS FOLLOWS: 465A AC INPUT TO CABINET x 1.25 = 581.25A ==> 600ABRANCH BREAKER REQUIRED.GENERAL SHEET NOTESA 11.05.21
REV.DATE DESCRIPTION
Drawing Name: O:\2021\2021095\98 - TRT 18712 - Carmel, IN\dwg\2021095.98- Carmel, IN N Illinois - CD90.dwgJune 10, 2022 12:29 PM - jarch
DESIGNERINSTALL MANAGERE-2JOB NO.ISSUED FOR:PERMITRECORDCONSTRUCTIONBID2021095.98ABRWILLCARTER11545 N ILLINOIS ST.
(TESLA STATION) - TRT18712
CARMEL, IN 46032
B 11.19.21 ISSUED FOR 90% REVIEW
C 04.25.22
ISSUED FOR 90% REVIEW
ISSUED FOR SIGN AND SEAL
XXXXXXXXXXXX1234CBAGPD GROUP, INC.®520 South Main Street, Suite 2531Akron, OH 44311330.572.2100Fax 330.572.21011 06.10.22 REVISIONS FOR CITY COMMENTSINTEGRATED SITE MASTERCONTROLLER (COMPONENTS BYMANUFACTURER, PC BY TESLA)DC OUTPUTCURRENT TOCHARGE POSTCHARGEPOSTMODELAC INPUTVOLTAGE TOCABINETAC INPUTCURRENT TOCABINETTESLA V3 CHARGING CABINET & POST ELECTRICAL SPECSDC OUTPUTVOLTAGE TOCHARGE POSTSHORT CIRCUITCURRENTRATINGkVA INPUTTOCABINETV3380V-480V0V - 500V85 KAICDC SHAREDBUS CURRENT350A640A465A387kVACCP
30/2
CCP
30/1
3A
FNQ-R4
20/1
20/1
SPARE
5A
FNQ-R
HEATER
SPARESEENOTE 2M106/10/22